Dri-Eaz Products, Inc. 

Monthly 

Clean pump check valve and basin

. In normal use, 

dust can accumulate and can restrict airflow, reducing 
performance and causing the unit to overheat. Clean 
when dust accumulation is visible. Remove grills and 
cover as shown in Fig. B. Use a vacuum cleaner with a 
brush tool and a soft cloth to remove any debris. Take 
care not to damage any interior components.  

To maintain appearance

, wipe interior and exterior sur-

faces with a damp cloth. For deep cleaning and a last-
ing, protective shine, use an automotive interior cleaner.  

As Needed 

Clean pump check valve and basin. 

If the unit displays 

the message “ER9 PUMP BLOCKED PUMP & HOSE”, 
the pump check valve and pump basin may need to be 
cleaned. Remove grills and cover as shown in Fig. B. 
Remove screws from pump base and lift out pump. Wipe 
out pump basin with a damp cloth. Unthread barbed fit-
ting with check valve and rinse fitting and check valve 
with clean water. Reinstall barbed fitting into pump. Do 
not overtighten. Reinstall pump on base. Reinstall cover 
and grills.

 

Clean coils.

 With the cover removed, inspect both coils. 

If excessive dust and debris is present, vacuum thor-
oughly and/or clean with coil cleaner.

 

PUMP PURGE BUTTON 

The Control Panel will display the following messages when the Pump Purge Button is pressed. 

 

C O N T R O L   P A N E L  

M E S S A G E

 

E X P L A N A T I O N

 

--- 

PUMP PURGING XX 

Pump is purging with countdown in seconds. Press key again to stop if needed.  

SYSTEM MESSAGES 

The Control Panel will display the following messages based on system performance and environmental conditions. User 
action, if any is required, is indicated in the third column. 

 

C O N T R O L   P A N E L  

M E S S A G E

 

E X P L A N A T I O N

 

U S E R   A C T I O N

 

INITIALIZING 

Unit is powering up. 

None 

FIRMWARE VERSION 

XXX 

Indicates control board firmware version number. 

None 

FXXX-XXX 

Model number. 

None 

OFF 

Unit has finished powering up and is operating. 

None 

PLEASE WAIT 

COMP. DELAY XX 

60s delay before compressor turns on. Allows system pres-
sure to equalize. 

None 

UNIT ON XXXX HRS 

INLET XXX°F / XX% 

First line: indicates total operating hours.  
Second line: Toggles between inlet temperature and inlet RH 
every 2 seconds. 

None 

HUMIDISTAT 

INLET XXX°F / XX% 

First line: indicates unit is in humidistat mode  
Second line: Toggles between inlet temperature and inlet RH 
every 2 seconds. 

None 

LOW TEMP 

INLET XXX°F/ XX% 

F515 only. Unit shuts off if inlet temp below 45° F. Turns back 
on when inlet reaches 50° F.  

None 

HI TEMP CYCLE 

REMAINING XX MIN 

Unit overload limit reached. Cool-down initiated. 

None 

--- 

DEFROST XX 

Unit is defrosting, with countdown in seconds. 

None 

WAIT FOR 

DEFROST XXX 

Unit turned off when coil is cold or already in a defrost cycle. 
Proceeds to finish cycle or initiate one to clear the coils of ice 
before storage. 

None 

WAIT FOR 

UNIT DRYING XXX 

Occurs when unit is turned off and coil is not frozen. Clears the 
coils of water before storage.  

None 

CLEAN FILTER > 

--- 

Prompt to clean or change filter. 

Change or clean filter. Press the 
> key to reset 

CLEAN COILS > 

--- 

Prompt to clean coils and interior. 

Clean coils. Press the > key to 
reset 

Summary of Contents for F515

Page 1: ...adapter Never cut off third prong Do not use an extension cord The unit must be operated on a 115V 60Hz circuit protected by a Ground Fault Circuit Interrupter GFCI device Keep motor and wiring dry Do...

Page 2: ...use a bucket or other container for water collection check it regularly to prevent over flows NOTICE Uncoil and straighten the entire drain hose Do not leave any part of the hose coiled and do not pl...

Page 3: ...y and the machine will begin operation immedi ately DISPLAY MENU Press to cycle through the display of additional dehumidifier conditions and User Settings To return to the main menu press the ON OFF...

Page 4: ...OUTLET 100 80 115 30 For information only 3 GRAIN DPR XX GPP XX X g kg for 230V models 4 FILTER CLEANED XXX HRS 5 FILTER CLEANED 0 HRS Press to clear filter hours 5 COIL CLEANED XXX HRS 5 COIL CLEANED...

Page 5: ...area 3 Press the PURGE key When the purge cycle is complete turn the unit off 4 Remove the external drain hose drain it carefully coil it and secure it with one of the straps provided on the side of t...

Page 6: ...in to stop if needed SYSTEM MESSAGES The Control Panel will display the following messages based on system performance and environmental conditions User action if any is required is indicated in the t...

Page 7: ...r ER4 OULET SENSOR CONNECT Temp sensor is open missing or shorted Check that temp sensors are installed cor rectly on control panel If error persists contact service ER5 SENSOR CONNECTION ON BD Inlet...

Page 8: ...rometer Increase room temperature Check filter Clean or replace as necessary Check heat exchange block and coils Clean as necessary If the problem you are experiencing is not listed here call your loc...

Page 9: ...cable de alimentaci n en un tomaco rriente con descarga a tierra adecuado No use adaptadores Nunca corte la tercera clavija No use cables prolongadores La unidad debe utilizarse en un circuito el ctr...

Page 10: ...a Ubicaci n del deshumidificador Para obtener los mejores resultados utilice los deshumi dificadores en un rea cerrada Coloque el deshumidifi cador lejos de obstrucciones y mant ngalo alejado de cualq...

Page 11: ...del panel de control que se encuentra m s ade lante Mensajes de error Si el diagn stico incorporado al PHD 200 detecta un problema la unidad mostrar un mensaje de error Con sulte Mensajes del sistema...

Page 12: ...a presionando DIS PLAY MENU MEN DE PANTALLA Con cada pulsa ci n del bot n se mostrar el siguiente par metro vea la lista m s adelante Cuando llegue al par metro que quiera ajustar presione MENU SELECT...

Page 13: ...ENTRADA SALIDA 100 80 115 30 S lo para informaci n 3 ENTRADA SALIDA XX X g kg 4 FILTRO LIMPIAR XXX HR 5 FILTRO LIMPIAR 0 HRS Presione para borrar las horas de limpieza del filtro 5 LIMPIAR BOBINA XXX...

Page 14: ...cuidado enr llela y suj tela con una de las tiras al costado de la unidad TRANSPORTE Y ALMACENAMIENTO AVISO Manipule la unidad con cuidado No la tire ni la apoye en lugares donde pueda caerse Si no tr...

Page 15: ...y posibles lesiones a los ocupantes del veh culo PROGRAMA DE MANTENIMIENTO ADVERTENCIA PELIGRO DE DESCARGA EL C TRICA Desconecte la unidad antes de limpiarla o darle mantenimiento ADVERTENCIA Riesgo d...

Page 16: ...ware del tablero de con trol Ninguna FXXX XXX N mero de modelo Ninguna APAGADO La unidad ha terminado de encender y est funcionando Ninguna POR FAVOR ESPERE RETAR COMPRS XX 60s de espera antes de que...

Page 17: ...n instalados correctamente en el panel de control Si el error persiste comun quese al centro de servicio ER5 CONEXION SENSOR TABLERO Sensor de temperatura humedad relativa de entrada abierto faltante...

Page 18: ...edad con un higr metro Aumente la temperatura de la habitaci n Controle el filtro L mpielo o reempl celo si es necesario Controle el bloque de intercambio de calor y los serpentines L mpielos si es ne...

Page 19: ...s la terre V rifier l tat du cordon d alimentation avant utilisation Ne pas l utiliser si le cordon est en dommag Pour d brancher toujours saisir la prise et non le cordon Enfoncer les trois fiches de...

Page 20: ...shumidifi cateur l cart de toute obstruction et de tout ce qui pourrait bloquer la circulation d air d entr e et de sortie de l appareil Pour plus d informations sur la cr ation d un environnement de...

Page 21: ...aucun compte rebours pour le compresseur n est affich un d lai n est pas n cessaire et l appareil commencera fonctionner imm diatement MENU D AFFICHAGE Appuyer pour faire d filer l affichage pour des...

Page 22: ...100 80 115 30 Pour information seulement 3 ENTRADA SALIDA XX X g kg 4 FILTRO LIMPIAR XXX HR 5 FILTRO LIMPIAR 0 HRS Appuyer sur pour effacer les heures du filtre 5 LIMPIAR BOBINA XXX HRS 5 LIMPIAR BOB...

Page 23: ...ttendez que le tableau de commande reprenne son af fichage normal avant de continuer 2 Basculez l g rement la machine pour s assurer que l eau restant sur les surfaces int rieures s coule dans le puis...

Page 24: ...A TA PADA BOMBA MANGUERA le clapet anti retour et le r servoir de la pompe peuvent avoir besoin d tre netto y s Retirer les grilles et le couvercle comme indiqu sur la figure B Retirer les vis de la b...

Page 25: ...ROSTATO ENTRADA XXX C XX Premi re ligne indique que l unit est en mode hygros tat Seconde ligne Alterne entre la temp rature d entr e et RH d entr e toutes les 2 secondes Aucune BAJA TEMP ENTRADA XXX...

Page 26: ...emp rature sont install s correctement sur le panneau de commande Si l er reur persiste contacter le fournisseur de services ER5 CONEXION SENSOR TABLERO Le capteur de la temp rature Rh d entr e est ou...

Page 27: ...ambiante V rifier le filtre Le nettoyer ou le remplacer si n cessaire V rifier bobines Les nettoyer si n cessaire Si le probl me que vous rencontrez ne figure pas dans ce tableau veuillez contacter vo...

Reviews: