Installation
(for qualified installers only)
35
© Travis Industries
4140514
100-01374
Mantel Requirements
Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured from the
non-combustible facing) must fall within the shaded portion of the table.
Any material above the fireplace that protrudes more than 3/4” (19mm) from the non-combustible facing is
considered a mantel and must meet the mantel requirements.
Mantel Column Clearances
Combustible mantel columns (legs) that protrude more than ¾” (19mm) from the front of the fireplace
require a 3” (77mm) clearance to the side of the fireplace.
Combustible mantel columns (legs) that protrude ¾” (19mm) or less from the glass frame must meet the
facing clearances (minimum 0” (0mm) from the side of the fireplace).
Non-combustible mantel columns do not have a minimum clearance.
Maximum Mantel Depth (b)
Mantel
Height
Above
Base (a)
46" (1169mm)
0" (0mm)
1" (25mm)
2" (51mm)
8" (203mm)
7" (178mm)
6" (152mm)
5" (127mm)
4" (102mm)
3" (76mm)
9" (229mm)
10" (254mm)
11" (279mm)
12" (305mm)
45" (1143mm)
44" (1118mm)
43" (1093mm)
42" (1067mm)
41" (1042mm)
40" (1016mm)
47" (1194mm)
39" (991mm)
37 (940mm)
38" (966mm)