Installation
(for qualified installers only)
33
© Travis Industries
4140514
100-01374
Facing Requirements – Extended (Tile-Over) Install
The included fiber board is required and must remain attached to the fireplace (see “a” below).
Drywall (or other combustible) may be placed above the fiber board (see “b” below) and to the sides and
below the face of the fireplace.
Tile or other non-combustible facing may be placed along the front of the fireplace around the perimeter of the
glass opening (see “c” below). Typical installations use 12” (305mm) or greater of non-combustible facing
around the perimeter of the glass opening. Do not install facing over the ledge to the glass opening.
WARNING
: Do not use adhesive to secure the facing. The high temperatures of the
fireplace may cause adhesives to emit odors. Use mastic or thin set (or other non-
combustible, non-odorous adherent) to attach the facing.
NOTE
: Screws may be used to secure cement board or tile backer to the fireplace. Do not
penetrate the fireplace more than 1/2” (13mm).
(a) Fiber Board
(included
with
fireplace)
(b) Drywall (or
other
combustible)
(c) Tile (or other
non-
combustible)
Adhesive
a
b
10-3/8"
264mm
15-3/4"
401mm
11-1/4"
286mm
c
37-1/4"
947mm