16
5.9
Fault codes
Fault code
Fault description
Troubleshooting
F00, F01
Power supply fault
1.
Bring box for repair
F02
Phase failure
1.
Check power supply for:
- completeness of phases
- load capacity of phases
F03
Open circuit on motor
1.
Check the motor connectors for dirt and
damage
2.
Bring box for repair
F04
Overvoltage in DC link
1.
Check power supply
F05
Motor overcurrent
1.
Run the motor with less power
F07
Powerbox overheating
1.
Allow the Powerbox to cool, check the function
of the fan, if necessary refit the water cooling
circuit
F51
Motor overheating
1.
Run motor with less load or increase cooling
water flow rate.
Attention: Regular overheating in the motor
shortens the service life!
F09
Speed sensor fault
1.
Check the motor connectors for dirt and
damage
2.
Bring motor and box for repair
F12
Earth leakage
1.
Check the motor connectors for dirt and
damage
2.
Bring motor for repair
F13, F14
Internal hardware fault
1.
Disconnect box from mains, bring box for
repair if fault reoccurs
F15
Release fault
1.
Check emergency stop
2.
Check the motor connectors for dirt and
damage
F20
Undervoltage
1.
Check power supply
F21
Overvoltage
1.
Check power supply
F52
Axis controller watchdog
1.
Disconnect the Powerbox from the mains for
10 seconds
F53
Start protection
1.
Release handle switch on motor
F62
Safety coupling engaged
1. Restart motor
F63
Motor communication interrupted
1.
Check earth conductor
2.
Disconnect the Powerbox from the mains for
10 seconds
5.10 Automatic shut-off in the event of overload
As already described under 5.4, the drive unit shuts off in the event of constant overload. The unit is reset
by pressing the green button again.