Editing Control Relays
Description
User-definable description for the NetGuardian 16's control.
Mom. Time
Stands for "Momentary Time," which is the time (in milli-seconds) when you quick-
latch the relay from Monitor Mode, T/Mon or other SNMP manager.
Notification devices
Check which notification device(s), 1 through 8, you want to send alarm notifications
for the control.
Analogs
11.7
Each of the NetGuardian 16's analog channels may be individually configured to monitor analog changes in your
environment. The analog inputs natively measures voltage on a range of -90 to +90 VDC. By removing the lid of the
unit, you can move a jumper to set the point to monitor 4 - 20mA.
Internal and external temperature sensors monitor the ambient temperature. Both sensors measure a range of 32° F
to 140° F (0° C to 60° C) within an accuracy of ± 1°. The external temperature sensor provides external temperature
readings by plugging the optional probe into the temperature port on the NetGuardian 16's back panel.
11.7.1 Basic Configuration
Basic configuration for the NetGuardian 16's analog channels can be accomplished from the
Edit
>
Analogs
menu.
From this screen, you enable or disable the analog channels, select notification devices, and set thresholds.
Fig. 11.10
- The basic Edit > Analogs menu
Editing Analogs - Basic
Enab (Enable)
Checking the box in the
Enab
column enables monitoring of the analog
channel. Analog channels that are not enabled will not show in the
Monitor
Menus > Analogs
screen.
Description
User-definable description for the analog channel
Rev (Reverse)
Check this box to reverse the polarity.
(This is not typically used. Reversing
polarity is the same as reversing your wiring.
Example: -54VDC b54VDC)
Notification devices
Check which notification device(s), 1 through 8, you want to send alarm
notifications for that analog alarm. Check the box in the green bar (top) to have a
notification device send an alarm for all analog channels.
MjU (Major Under)
Threshold settings. These user-defined value are used to indicate the severity of