48
41
NTP failed
Communication with Network Time
Server has failed.
Try pinging the Network Time Server’s IP
Address as it is configured. If the ping
test is successful, then check the port
setting and verify the port is not being
blocked on your network.
42
Timed Tick
Toggles state at constant rate as
configured by the Timed Tick timer
variable. Useful in testing integrity of
SNMP trap alarm reporting.
To turn the feature off, set the Timed Tick
timer to 0.
43
Serial 1 RcvQ
full
Serial port 1 (or appropriate serial port
number) receiver filled with 8 K of data
(4 K if BAC active).
Check proxy connection. The serial port
data may not be getting collected as
expected.
44
Dynamic
memory full
Not expected to occur.
Call DPS Tech Support (559) 454-1600
45
Unit reset
Unit has rebooted.
If unintentional, call DPS Tech Support:
(559) 454-1600.