2
Specifications
2
Dimensions:
1.72" H x 17.026" W x 9.636" D
(4.4 cm x 43.25 cm x 24.48 cm)
Weight:
1.5lb
AC Inputs
:
1 AC input feed with 8 outputs
OR
2 AC inputs with 3 outputs each
Range: 85 to 250 VAC
AC inputs support 20 amps max current at 120 VAC
Unit requires 14W max for internal functions
Output Relays
:
Max output is 10 amps @ 125 VAC per outlet
Control Buttons
:
Located on the front panel; used for switching power on/off while on-site
Interfaces
:
1 DB9 craft port
1 - Rj45 10BaseT half-duplex ethernet port
1 - DPS sensor jack (RJ11) for external temperature probe
16 D-Wire sensors
(
Optional) 33.6 Telco modem for backup remote access
OR
(
Optional) 1 RS232 or RS485 serial port
SNMP:
v1 and v2c
Controls
:
2 - Ctrl Commands: On, Off and Reset (off-on)
Web Interface
:
HTTP or HTTPS via SSL encryption
Mounting
:
19" or 23" rack mountable; 1 rack unit
Firmware Upgrade
:
Upgradeable via LAN or serial
TTY Interface:
Yes, through front DB9 craft port and dialup, Telnet on TCP port 2002
Op. Temperature:
32°–104° F (0°– 40° C)
Op. Humidity:
0%–95% non-condensing
Storage Temperature
:
-4°–131° F (-20°– 55° C)
MTBF:
60 years
Windows Compatibility:
Windows XP, 2000, Vista, 7 32/64 bit
RoHS:
5 of 6
RTU Build Only:
Alarm Termination
:
Via 50-pin Amphenol connector on back panel
Discrete alarms
:
16
Analogs:
4
Internal Temp:
1
This unit does not contain any operator-serviceable parts.