43
The unit will refresh the sensor ID on that channel.
Description
User-definable description for the sensor channel.
Parse
Checks to see if the
Description
field contains a valid equation.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm notifications
for that alarm point.
Advanced Sensor Configuration (Details>>)
Record Freq
The amount of time, in minutes (min) or seconds (s), between each recorded sensor
value.
Deadband
The amount (in native units) that the channel needs to go above or below a threshold
in order to cause an alarm.
Qual Time (Qualification
Time)
The length of time that must pass, without interruption, in order for the condition to be
considered an Alarm or a Clear.
Qual. Type (Qualification
Type)
Allows you to choose whether you want to apply the Qualification Time to the alarm
Set, Clear, or Both.
Thresholds
These settings are set to indicate the severity of the alarm depending on which
threshold values have been passed. Enter values for Major Under (MjU), Minor Under
(MnU), Minor Over (MnO), and Major Over (MjO).
Post On
Select the threshold alarms to post. All thresholds, Major Only, Minor Only, Mojor
Over Only, Major Under Only.
Analog Gauge Type
Select the color-coded gauge that best represents your data. Selecting
None
will
disable the analog gauge and only a numerical representation of the value will be
displayed under
Monitor
>
Sensors
.
Note:
Before plugging in any additional D-Wire Sensors, set up the internal sensor.
Summary of Contents for D-PK-NG224-12003
Page 9: ...5...
Page 11: ...7 Optional Shipping Items Available by Request 3 1 Small WAGO connector 2 802 01020 00...
Page 16: ...12 66Block diagrams 6 3 66 block pinout for Amphenol 1 TTL Discretes 1 24...
Page 17: ...13 66 block pinout for Amphenol 2 Controls 1 2...
Page 77: ...73...
Page 78: ......