Securing the unit
We recommend that you secure the unit to the concrete pad by using four (4) TAPCON screws and washers.
(See drawing below.)
Pool Heat Pump _9
POOL HEAT PUMP INSTALLATION
Condensation and Drainage
The evaporator coil will produce condensation while the unit is running and drain at a steady rate, usually three to five
gallons per hour, depending on the ambient air temperature and humidity.
It is normal for condensation to drip out the
CONDENSATION WATER DRAIN PIPE
that is located on the side of the unit.
(See drawing below.)
A:
CONDENSATION WATER DRAIN PIPE
B:
WINTERIZING DRAIN (with plastic caps)
A:
Concrete Pad
B:
1/4” x 1-1/2” Stainless Steel Concrete Screw
and Washer (Provided by installer)
C:
3/16” Drilled Hole
3” minimum
A
B
C
A
B