Rack Monitor 8800E/8801E
Document: Operation Manual
Date: 16-Jun-2011
Version: A.6
Page 32 of 35 H71343
Condition
Possible Cause
Solution
- The Rack Monitor 8800E/8801E
doesn’t turn ON
- The mains isn’t connected.
- Connect the mains.
- Check if the main wiring is
connected according to the
installation instruction.
- Check if there is any power
available at the terminal of the Rack
Monitor 8800E/8801E.
- The fuses are broken.
- Replace the fuses for new ones.
- System goes directly into ‘NON
PERMISSIVE’
- The dead man switch is not
connected.
- Connect the cable according to the
installation manual.
- Connect a bypass wire between
pin 1 & 2 according to the
installation manual.
- System does not indicate correct
amount of compartments in 5-
Wire mode
- bad connections in sensor
housing and/or plug/socket.
- Check green and white wires
- Clean pin 5 and 10 on plug and
socket
For all other possible inflictions/damages to the Rack Monitor 8800E/8801E, contact
OPW Fluid Transfer Group
Europe BV
and ask for assistance to obtain a safe and right use.