AssuredSAN Ultra48 Series Setup Guide
83
B
Environmental requirements and specifications
Safety requirements
Install the system in accordance with the local safety codes and regulations at the facility site. Follow all
cautions and instructions marked on the equipment.
IMPORTANT:
Also see the hard copy
AssuredSAN Product Regulatory Compliance and Safety
document
(included in your product ship kit).
.
Alternatively, you can access the document online. See Dot Hill’s customer resource center (CRC) web site
for additional information:
Select
AssuredSAN & R/Evolution Products
>
4004 Series
to download the PRC&S document.
Site requirements and guidelines
The following sections provide requirements and guidelines that you must address when preparing your site
for the installation.
When selecting an installation site for the system, choose a location not subject to excessive heat, direct
sunlight, dust, or chemical exposure. These conditions greatly reduce the system’s longevity and might void
your warranty.
Site wiring and AC power requirements
The following are required for all installations using AC power supplies:
.
•
All AC mains and supply conductors to power distribution boxes for the rack-mounted system must be
enclosed in a metal conduit or raceway when specified by local, national, or other applicable
government codes and regulations.
•
Ensure that the voltage and frequency of your power source match the voltage and frequency inscribed
on the equipment’s electrical rating label.
•
To ensure redundancy, provide two separate power sources for the enclosures. These power sources
must be independent of each other, and each must be controlled by a separate circuit breaker at the
power distribution point.
•
The system requires voltages within minimum fluctuation. The customer-supplied facilities’ voltage must
maintain a voltage with not more than
±
5 percent fluctuation. The customer facilities must also provide
suitable surge protection.
•
Site wiring must include an earth ground connection to the AC power source. The supply conductors
and power distribution boxes (or equivalent metal enclosure) must be grounded at both ends.
•
Power circuits and associated circuit breakers must provide sufficient power and overload protection. To
prevent possible damage to the AC power distribution boxes and other components in the rack, use an
external, independent power source that is isolated from large switching loads (such as air conditioning
motors, elevator motors, and factory loads).
Table 31
Power requirements - AC Input
Measurement
Rating
Input power requirements
100-240 VAC, 50/60 Hz
Maximum input power
640 W maximum continuous
Heat dissipation
2,245 BTUs/hour
Summary of Contents for AssuredSAN 4544
Page 8: ...8 Figures ...
Page 10: ...10 Tables ...
Page 14: ...14 About this guide ...
Page 50: ...50 Connecting hosts ...
Page 52: ...52 Basic operation ...
Page 70: ...70 Troubleshooting ...
Page 90: ...90 Electrostatic discharge ...
Page 94: ...94 USB device connection ...
Page 96: ...96 SFP option for CNC ports ...
Page 100: ...100 Index ...