dormakaba ED50 Installation Instructions – Fine cover
Appendix A
Parameter
Value
range
Units
Factory
setting Description
Status relay function, X7 terminals
0
Status relay is deactivated.
27
0 - 6
1
1
Status relay activated as soon as door reaches door "closed" position.
2
Status relay activated as soon as door reaches door "open" position.
3
Status relay activated when error codes are displayed on 2 digit operator display.
4
"Door closed and locked" activates status relay.
5
Status relay activated when information or error codes are displayed on 2 digit
operator display.
6
1. Status relay activated when door is opened further than opening angle
parameter
OA
, set during learning cycle.
2. Parameter
OA
value can only be changed using dormakaba handheld or by
performing another learning cycle.
Locking device output configuration;
output X3, 1G (24V) and input X6, 4/4a
Reference Chapter 7
28
0 - 1
0
0
Locking device output terminal X3, 1G (24V) is independent of Input X6, 4/4a.
1
1. Locking device output terminal X3, 1G (24V) is turned on as soon as contact at
X6, 4/4a is opened..
2. Terminal X3, 1G 24V output is on for as long as contact at X6, 4/4a is open,
motor lock with a 100% duty factor is required.
3. This function is not available for DCW motor locks.
Cycle counter
1. Total number of opening and closing cycles displayed is shown in increments of 10000.
• Display value, "4", 40,000 cycles.
• Display value, "53", 530,000 cycles.
2. Total number of cycles can be displayed on dormakaba handheld.
3. A display value of "99" means 990,000 cycles or greater.
29
0 - 99
* 10000
cycles
Delete error log
30
0 - 1
0
0
No function.
1
1. When "1" entered, Error log is deleted.
2. Parameter is then automatically reset to "0".
Reset service interval display,
operator yellow LED
31
0 - 1
0
0
No function.
1
1. When "1" entered:
• Service cycle counter is reset to 200,000.
• Service interval is reset to 12 months.
• Yellow LED not illuminated.
2. Parameter is then automatically reset to "0".
3. Values other than default values must be set using dormakaba USA, Inc.
handheld:
• Maintenance interval
• Maintenance cycles
A.1.1 Driving parameters detail.