69
ED50
01-2020
DL4615-001
dormakaba ED50 Installation Instructions – Fine cover
Chapter 20
20.1 Separately commission active and inactive doors
20 Double door first commissioning
20.1.1 Commission active door first.
1. Refer to Chapter 19 and commission active door.
20.1.2 Commission inactive door.
1. Refer to Chapter 19 and commission inactive door.
20.2 Set operator parameters for double door operation
20.2.1 Full width cover option –
Active door, set parameter PS to 1.
1. Set program switch to CLOSE.
Step 1
Press
Press and hold PRG > 3 s to enter
program mode, AS parameter
displayed.
Step 2
Press
Scroll to
PS
(Program switch type)
parameter.
Step 3
Press
Displays "00" , factory setting.
Step 4
Press
"00" starts flashing.
Step 5
Press
Scroll to select parameter value "1",
External mechanical program switch
connected to operator terminal board.
Fig. 20.2.1 Single program switch located on inactive
door.
CAUTION
Full width cover option – single program
switch.
Parameter
PS
must be set to 1. Reference
Para. 19.3
Automatic
Close
Permanent open
Step 6
Press
Saves value entered. Display stops
flashing.
Step 7
Press
Returns to program switch parameter.
Step 8
Press
Exits program mode.