![Doosan G625XF Operation & Maintenance Manual Download Page 94](http://html.mh-extra.com/html/doosan/g625xf/g625xf_operation-and-maintenance-manual_2521479094.webp)
50 Hz: G625 - G690 - G750XW/XF
OPERATION & MAINTENANCE MANUAL
94
60 Hz: G655 - G750 - G800 - G850XW/XF
• Motion of operation mechanisms
Figs. 24 - 27 illustrate the motion of the charging and ON-
OFF mechanisms.
Fig. 24 Closing motion 1 (discharge motion)
For manual closing operation, ON button (1) rotates
counterclockwise. For electrical closing operation, push
rod (1) protrudes downward from the latch release coil
(LRC) and charge latch trigger (2) rotates clockwise. This
rotates closing trigger shaft (3) clockwise and closing
release lever (4) disengages from a semicircular pawl
and rotates clockwise. And charging cam (5) rotates
counterclockwise, so that charging lever (7) disengages
from closing spring (6) and rotates counterclockwise.
Closing cam (8) is pushed up by charging lever (7) and
rotates clockwise. At this time, each component is
positioned as shown in Fig. 26. Continued to Fig. 25.
Fig. 25 Closing motion 2
Closing cam (8) rotating clockwise causes closing link
and top link (9) to be pushed straight. This rotates closing
toggle cam (10) connected with closing link (9)
counterclockwise, so that crossbar (11) rotates clockwise
and thus moving contact (12) comes in contact with
stationary contact (13). At this time, each component is
positioned as shown in Fig. 27.