50 Hz: G625 - G690 - G750XW/XF
OPERATION & MAINTENANCE MANUAL
28
60 Hz: G655 - G750 - G800 - G850XW/XF
ENGINE RUNNING
Once the engine is running and all starting timers have expired, the animated
Engine Running
icon is displayed.
The generator is placed on load if configured to do so.
If all start requests are removed, the
stopping sequence
begins.
STOPPING SEQUENCE
The
Return Delay
timer operates to ensure that the starting request has been permanently removed and isn’t just a short
term removal. Should another start request be made during the cooling down period, the set returns on load.
If there are no starting requests at the end of the
Return Delay
timer, the load is removed from the generator to the mains
supply and the
cooling
timer is initiated.
The
Cooling Down
timer allows the set to run off load and cool sufficiently before being stopped. This is particularly
important where turbo chargers are fitted to the engine.
After the
Cooling Down
timer has expired, the set is stopped.
NOTE:
The load transfer signal remains inactive until the Oil Pressure has risen. This prevents excessive wear on the
engine.