50 Hz: G625 - G690 - G750XW/XF
OPERATION & MAINTENANCE MANUAL
22
60 Hz: G655 - G750 - G800 - G850XW/XF
STOP / RESET MODE
Stop/Reset Mode
is activated by pressing the
Stop/Reset Mode
button.
The
Stop/Reset
icon is displayed to indicate
Stop/Reset Mode
operations.
In
Stop/Reset Mode
, the module removes the generator from load (if necessary) before stopping the engine if it is
already running.
If the engine does not stop when requested, the FAIL TO STOP alarm is activated (subject to the setting of the
Fail to
Stop
timer). To detect the engine at rest the following must occur :
•
Engine speed is zero as detected by the CANbus ECU.
•
Generator AC Voltage and Frequency must be zero.
•
Engine Charge Alternator Voltage must be zero.
•
Oil pressure sensor must indicate low oil pressure.
When the engine has stopped, it is possible to send configuration files to the module from DSE Configuration Suite PC
software and to enter the Front Panel Editor to change parameters.
Any latched alarms that have been cleared are reset when
Stop/Reset Mode
is entered.
The engine is not started when in
Stop/Reset Mode
. If remote start signals are given, the input is ignored until
Auto
Mode
is entered.
When left in
Stop/Reset Mode
with no presses of the fascia buttons and configured for
Power Save Mode,
the mod-
ule enters
Power Save Mode
. To ‘wake’ the module, press any fascia control buttons.
NOTE:
If a digital input configured to
panel lock
is active, changing module modes is not possible. Viewing the
instruments and event logs is NOT affected by panel lock.
NOTE:
For further details of module configuration, refer to DSE Publication:
057-185 DSE71xx MKII Configuration
Software Manual.
Power Save Mode in the
DSE Configuration Suite
Software