Downflo Workstation, DWST 4-1 to 6-4
10
Problem
Probable Cause
Remedy
Control Box with Pulse Cleaning Control
Pulse cleaning does not
operate
Defective wiring
Check wiring to solenoid valves
Defective solenoid valves
Check solenoid coils and replace as necessary.
Timer control box not energized
Check supply voltage to timer board. Check the timer
board's fuse. Replace with one of equal value. If supply
voltage and fuse are good, observe the control board.
The outlet LED indicates if the control board is attempting
to pulse. LED's flash to indicate power to the solenoid.
Check output with an analog volt meter using the 150-Volt
AC scale. The needle deflects if voltage is present when
LED flashes. If LED's do not flash or no voltage is present,
replace the timer board.
Pulse cleaning does not
operate with the selector
switch in the ON position
Defective wiring
Check wiring to solenoid valves.
Defective solenoid valves
Check solenoid coils and replace as necessary.
Timer control board not energized
Check supply voltage to timer board. Check the timer
board's fuse. Replace with one of equal value. If supply
voltage and fuse are good, observe the control board. The
outlet LED indicates if the control board is attempting to
pulse. LED's flash to indicate power to solenoid. Check
output with an analog volt meter using the 150-Volt AC
scale. The needle deflects if voltage is present when LED
flashes. If LED's do not flash or no voltage is present,
replace the timer board.
Pulse cleaning does not
operate with the selector
switch in the GAUGE
position
Defective wiring
Check wiring to solenoid valves.
Defective solenoid valves
Check solenoid coils and replace as necessary.
Timer control board not energized
Check supply voltage to timer board. Check the timer
board's fuse. Replace with one of equal value. If supply
voltage and fuse are good, observe the control board. The
outlet LED indicates if the control board is attempting to
pulse. LED's flash to indicate power to solenoid. Check
output with an analog volt meter using the 150-Volt AC
scale. The needle deflects if voltage is present when LED
flashes. If LED's do not flash or no voltage is present,
replace the timer board.
Defective Photohelic air lines
Check tubing and fittings for leaks or obstructions.