35
12.5
Ashtray empty warning function
When this function is activated, the boiler's controller warns about the ashtray of the boiler is full
and must be emptied, depending on boiler's fuel consumption (kg). The parameter
“Ashtray status”
of
“User Menu”
allows checking the actual fill level. When it is full, an
"Empty the ashtray"
warning is
activated.
By default this function is supplied activated and set to a general default rough value, so it should
be adjusted depending on the quality and type of fuel used. The following table shows the default
value of this parameter in kilograms of fuel consumption (depending of boiler model):
Model
Fuel Kg
BioClass TR 10
650 kg
BioClass TR 16
750 kg
BioClass TR 25
1000 kg
Select
“Ashtray empty warning”
(
) parameter of
“Setup menu”
and press
to access. The value is set by pressing "
+
" and "
-
"
symbols of DHW
(19)
. It is possible to deactivate this function by
setting the value of this parameter to "
OFF
".
NOTE:
Each time a new value is set for this parameter, the ashtray must be emptied.
12.6
Manual setting of feed auger calibration
When this parameter is displayed (
) on
"Setup menu"
, press
to
access and set the value desired by pressing "
+
" o "
-
" of DHW
(19)
.
The range of values selectable is OFF, 0.500 - 5.000 kg.
12.7
Screen contrast setting
When this parameter of the
"Setup menu"
is displayed, press
to
access and set the value desired by pressing "
+
" o "
-
" of DHW
(19)
.
The range of values selectable is 1 - 5.