49
23
TECHNICAL DATA
MODELO
BioClass HM
25
BioClass HM
43
BioClass HM
66
Nominal heat output
kW
25,3
42,7
64,8
Efficiency at maximum heat output
%
95
94
92,1
Minimum heat output
kW
6,9
11,4
18,0
Efficiency at minimum heat output
%
92
94,5
94,8
CO at maximum heat output (10% O
2
)
mg/m
3
45
25
185
OGC (organic gaseous substances) at
maximum heat output (10% O
2
)
mg/m
3
<5
<5
4
Particles content at maximum heat
output (10% O2)
mg/m
3
20
20
16
CO at minimum heat output (10% O
2
)
mg/m
3
240
60
150
OGC (organic gaseous substances) at
minimum heat output (10% O
2
)
mg/m
3
5
<5
5
Boiler class (according to EN 303-5)
-
Clase 5
Maximum operating pressure
bar
3
Maximum operating temperature
ºC
80
Water volume
ºC
110
Minimum flue draught
litros
73
104
154
Maximum flue draught
mbar
0,10
Electrical supply
mbar
0,20
Boiler chimney diameter
mm
150
150
175
Fuel
-
Pellet de madera de Ø6 - 8 mm.
Longitud máxima 35 mm.
Maximum water content of the fuel
%
7
Minimum return temperature
ºC
25 ºC
Water pressure drop (dT = 20 K)
mbar
140
180
22
Stand by power
W
7
Weight (net)
Kg
300
368
486