Operating the generator
19
8.5
Stopping the generator
➤
Stop the generator with the on/off switch (fig.
3
2, page 4).
If the generator does not stop: switch it off with the main switch (fig.
2
1,
page 4).
8.6
Display messages
Display message
Description
Generator behaviour
Measures
LOW BATTERY
The battery voltage has fallen
below the minimum value for
starting up (9V).
The generator does not start.
Charge the battery.
OIL CHANGE
The number of prescribed oper-
ating hours has been reached for
changing the engine oil.
The generator continues to run.
Change the oil (see chapter
“Changing the oil (fig.
6
,
page 6)” on page 26), then
restart the generator by pressing
and holding down the start but-
ton.
NO FUEL
The fuel in the tank is in reserve.
The generator continues to run.
Refuel.
OIL ALERT
Insufficient engine oil.
The generator stops.
Fill up with oil (see chapter
“Checking the oil level” on
page 21).
GENERATOR ALERT!
General alarm message
Example: The control ring on the
throttle valve of the carburettor
(stepper motor) is faulty.
The generator stops.
Check the system by referring to
the troubleshooting table.
If the problem persists, contact
the manufacturer's branch office
in your country (addresses on the
back page).
OVERLOAD!
The consumers generate an
overload at the output.
The inverter switches off, there-
fore no voltage is supplied but
the engine carries on running
until it goes off.
Reduce the connected load and
start the generator again.
SHORT CIRCUIT
The consumers cause a short cir-
cuit at the output.
The inverter switches off, there-
fore no voltage is supplied but
the engine carries on running
until it goes off.
Check the connected consum-
ers then start the generator
again.