background image

Measuring principle of HVAC temperature sensors in general:
The measuring principle of temperature sensors is based on an internal sensor that outputs a temperature-dependent resistance signal.  
The type of the internal sensor determines the output signal. The following active ⁄ passive temperature sensors are distinguished: 

a)  Pt 100 measuring resistor  (according to DIN EN 60 751)
b)  Pt 1000 measuring resistor  (according to DIN EN 60751)
c)  Ni 1000 measuring resistor  (according to DIN EN 43 760, TCR = 6180 ppm ⁄ K)
d)  Ni 1000_TK 5000 measuring resistor  (TCR = 5000 ppm ⁄ K)
e)  LM235Z, semiconductor IC  (10 mV ⁄ K, 2.73 V ⁄ °C). Ensure correct po ⁄– when connecting!
f)  NTC  (according to DIN 44070)
g) PTC
h)  KTY silicon temperature sensors

The most important resistance characteristics are shown on the last page of these operating instructions. According to their characteristics, 
 individual temperature sensors exhibit different slopes in the range between 0 °C and +100 °C (TK value). Maximum-possible measuring ranges 
also vary from sensor to sensor (for some examples to this see under technical data).

Design of HVAC temperature sensors in general:
Sensors are distinguished by shape type as follows: surface-contacting sensors, cable temperature sensors, and housing-type and built-in 
 temperature  sensors.
– On surface-contacting sensors, the temperature sensor has at least one contact area that must be brought in contact, e.g. with the surface of 

radiators or pipes. If the contact area is not positioned correctly relative to the surface to be measured, significant temperature measurement 
errors may occur. Good contact area and temperature conduction must be ensured, dirt and unevenness must be avoided, and heat-conductive 
paste is to be used where necessary. 

– On cable temperature sensors, the temperature sensor is installed inside a sensor sleeve, from which a connecting cable is leading out. In 

addition to the standard insulating materials PVC, silicone, and fibreglass with stainless steel texture, other versions are also available that 
may allow a wider range of application.

– On housing-type sensors, the temperature sensor is embedded in a respective housing. Different designs of housings are available, e.g. with an 

external sensor sleeve (see outside temperature sensor ATF2). Housing-type sensors are normally distinguished into in-wall (FSTF) and on-wall 
(RTF, ATF) types and indoor and wet room versions. Connection terminals are placed on a plate inside the connecting housing.

– Duct and built-in temperature sensors are distinguished into temperature sensors with interchangeable measuring insert and without inter-

changeable measuring insert. Connection parts are placed inside a connecting head. Standard process connection for immersion sensors is a 
pipe thread (sizes in inches) and a mounting flange for duct sensors. However, it may be designed differently. When a built-in sensor has a neck 
tube, the  application range is usually somewhat wider since ascending heat cannot flow directly and immediately into the connecting head. This 
is to be noted especially when transmitters are installed. The temperature sensor in built-in sensors is always placed inside the front part of 
the protective tube. On temperature sensors with short reaction times, protective tubes are stepped. 

Note!
Select immersion depth for built-in sensors so that the error caused by heat dissipation stays within the admissible error margins. A standard 
value is: 10 x diameter of protection tube + sensor length. In connection with housing-type sensors, particularly with outdoor sensors, please 
consider the influence of thermal radiation. For that purpose, a sunshade and radiation protector SS-02 can be attached. 

G  

General notes

Component ................................................................  max. thermal load

Connecting cable
PVC, normal ....................................................................................+70 °C
PVC, heat-stabilized.................................................................... +105 °C
Silicone  ......................................................................................... +180 °C
PTFE  ............................................................................................. +200 °C
Fibreglass insulation with stainless steel texture  ............... +400 °C

Housing ⁄ Sensor
see table "Technical Data"

Maximum thermal load on components:

On principle, all temperature sensors shall be  protected 
against unacceptable overheating!

Standard values for individual components and  materials 
selected are shown for operation under  
neutral  atmos phere and otherwise normal conditions  
(see table to the right).

For combinations of different insulating materials,  
the  lowest temperature limit shall always apply.

Summary of Contents for THERMASGARD RTF KTY81-210 Series

Page 1: ...ing Installation Room temperature sensors and measuring transducers on wall 6000 2600 0000 1XXD1 26000 2020 D1 V105 03 2020 Gratulujeme Zakoupili jste produkt německé kvality Congratulations You have bought a German quality product Domat Control System s r o U Panasonicu 376 530 06 Pardubice Stare Civice CZ Česká republika Tel 420 461 100 823 Fax 420 226 013 092 info domat cz www domat int com ...

Page 2: ...THERMASGARD RTF xx G Rozměry Kryt Baldur 1 Dimensional drawing Housing Baldur 1 Rozměry Kryt Baldur 2 Dimensional drawing Housing Baldur 2 T K ø 6 0 85 85 27 2 28 9 T K ø 6 0 98 98 32 6 34 6 ...

Page 3: ... drážky ve středu mírně zatlačte dolů a zvedněte spodní část krytu Vytáhněte horní kryt dopředu To open the housing set a screwdriver 2 0 in the groove at centre press down and lift up the bottom frame slightly Pull top cover forward and hold it Kryt Baldur Housing ...

Page 4: ...abelů vzadu s předem určeným bodem zlomu pro vstup kabelu v horní dolní části Elektrické připojení 0 14 1 5 mm přes šroubové svorky pouze pro bezpečné nízké napětí max 24 V DC Přípustná vlhkost max 90 r H bez kondenzujících par Třída ochrany III podle EN 60 730 Stupeň krytí IP 30 podle EN 60 529 Označení Standard je rozšiřující se symbol se střední polohou nevyplněný volitelný speciální tisk THERM...

Page 5: ...5 14 13 12 11 10 9 8 7 6 T1 Žádaná Offset THERMASGARD RTFxxT Provedení se senzorem a tlačítkem max 24 V DC max 10 mA Baldur 1 THERMASGARD RTFxxLT Provedení se senzorem LED diodou zelená a tlačítkem max 24 V DC max 10 mA Baldur 1 THERMASGARD RTFxxPT Provedení se senzorem a Potenciometrem 1 kOhm max 0 1 W a tlačítkem max 24 V DC max 10 mA Baldur 1 1 2 3 18 17 16 4 5 S1 15 14 13 12 11 10 9 8 7 6 T1 L...

Page 6: ... LED zelená a tlačítkem max 24 V DC max 10 mA Baldur 1 THERMASGARD RTFxxPW Provedení se senzorem Potenciometrem 1 kOhm max 0 1 W a kolébkovým přepínačem max 24 V AC DC max 130 mA Baldur 1 THERMASGARD RTFxxPD Provedení se senzorem Potenciometrem 1 kOhm max 0 1 W a otočným přepínačem max 24 V AC DC max 130 mA Baldur 2 1 2 3 18 17 16 P1 P2 4 5 S1 15 14 13 12 11 10 9 8 7 6 W1 Žádaná Offset 1 2 3 4 21 ...

Page 7: ...lay 1 2 3 18 17 16 P1 P2 4 5 S1 15 14 13 12 11 10 9 8 7 6 Žádaná Offset THERMASGARD RTFxxP RTFxxPU RTM U PU Provedení se senzorem a Potenciometrem 1 kOhm max 0 1 W 1 2 3 4 5 6 min max korektura T Potencio metr integ rovaný Senzor 3 4 5 6 Rx 1 2 Výstupní teplota 0 10V UB Napájení napětí 24V AC DC UB GND Výstup potenciometru 0 10V ...

Page 8: ...ř na radiátor nebo trubku Pokud není kontakt správně umístěn vzhledem k povrchu může dojít k výrazným chybám měření Dbejte na zajištění správného kontaktu a teplotní vodivosti Vyvarujte se nečistot a nerovností povrchu V případě potřeby je vhodné užít teplovodní pasty U kabelových čidel teploty je čidlo je umístěno uvnitř jímky ze které je vyveden připojitelný kabel Kromě standardních izolačních m...

Page 9: ... platným pro dané místo Zejména VDE VDI směrnice vztahující se k technickému měření teploty za všech okolností se vyvarujte paralelní pokládky se silovým vedením pokyny a nařízení pro elektromagnetickou kompatibilitu EMC doporučuje se použití stíněných kabelů se stíněním připojeným jednostranně na straně PLC či vstupních modulů Před instalací se ujistěte že technické parametry daného teploměru nej...

Page 10: ...sou výslovně zmíněny a jsou možné z hlediska technického pokroku a neustálého zlepšování našich produktů V případě jakýchkoli změn provedených uživatelem záruka zaniká Toto zařízení nesmí být umístěno v blízkosti zdrojů tepla nebo být vystaveno jejich vlivu Také se zcela vyhněte přímému dopadu slunečního záření nebo ozařování zařízení z podobných zdrojů světla Používání zařízení v blízkosti jiných...

Page 11: ......

Page 12: ...xes for cable entry from the back with predetermined breaking point for on wall cable entry from top bottom in case of plain on wall installation Electrical connection 0 14 1 5 mm via terminal screws on safety extra low voltage max 24 V DC only Humidity max 90 r H non precipitating air Protection class III according to EN 60 730 Protection type IP 30 according to EN 60 529 Lettering standard is sw...

Page 13: ... mA Baldur 1 THERMASGARD RTFxxLT Version with sensor LED green and pushbutton max 24 V DC max 10 mA Baldur 1 THERMASGARD RTFxxPT Version with sensor potentiometer 1 kOhm max 0 1 W and pushbutton max 24 V DC max 10 mA Baldur 1 1 2 3 18 17 16 4 5 S1 15 14 13 12 11 10 9 8 7 6 T1 1 2 3 18 17 16 4 5 S1 15 14 13 12 11 10 9 8 7 6 T1 LD1 1 2 3 18 17 16 P1 P2 4 5 S1 15 14 13 12 11 10 9 8 7 6 T1 setpoint of...

Page 14: ...D RTFxxPW Version with sensor potentiometer 1 kOhm max 0 1 W and rocker switch max 24 V AC DC max 130 mA Baldur 1 THERMASGARD RTFxxPD Version with sensor potentiometer 1 kOhm max 0 1 W and turn switch max 24 V AC DC max 130 mA Baldur 2 1 2 3 18 17 16 P1 P2 4 5 S1 15 14 13 12 11 10 9 8 7 6 T1 LD1 setpoint offset 1 2 3 4 21 20 19 5 6 S1 1 2 3 0 15 16 17 18 14 13 12 11 10 9 8 7 P1 P2 setpoint offset ...

Page 15: ... RTFxxPU RTM U PU Version with sensor and potentiometer 1 kOhm max 0 1 W Baldur 1 Baldur 1 Baldur 1 3 4 5 6 Rx 1 2 Output temperature 0 10V UB supply voltage 24V AC DC UB GND Output potentiometer 0 10V 1 2 3 4 5 6 min max Korrektur T Potentio meter int Sensor 1 2 3 18 17 16 P1 P2 4 5 S1 15 14 13 12 11 10 9 8 7 6 setpoint offset ...

Page 16: ...pplication On housing type sensors the temperature sensor is embedded in a respective housing Different designs of housings are available e g with an external sensor sleeve see outside temperature sensor ATF2 Housing type sensors are normally distinguished into in wall FSTF and on wall RTF ATF types and indoor and wet room versions Connection terminals are placed on a plate inside the connecting h...

Page 17: ...rement e g such as welding instructions etc Particularly the following shall be regarded VDE VDI directive technical temperature measurements measurement set up for temperature measurements The EMC directives must be adhered to It is imperative to avoid parallel laying of current carrying lines We recommend to use shielded cables with the shielding being attached at one side to the DDC PLC Before ...

Page 18: ...re exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to heat sources e g radiators or be exposed to their heat flow Direct sun irradiation or heat ...

Page 19: ...ezchybnou kvalitu zaručujeme v rámci našich Všeobecných obchodních podmínek Subject to errors and technical changes All statements and data herein represent our best knowledge at date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are used under a wide range of dif...

Page 20: ...461 1760 1625 4 3552 3817 3930 120 130 149 8 1498 1833 3676 4008 130 140 153 6 1536 1909 3802 4166 140 150 157 3 1573 1987 3929 4280 150 NTC 1 8 kOhm NTC 2 2 kOhm NTC 3 kOhm NTC 5 kOhm NTC 10 kOhm NTC 10 kPRE NTC 20 kOhm NTC 50 kOhm C Ω Ω Ω Ω Ω Ω Ω Ω C 50 50 40 39073 806800 2017000 40 30 22301 27886 53093 88488 175785 135200 413400 1033500 30 20 13196 16502 29125 48541 96597 78910 220600 551500 20...

Reviews: