DOLD MK 9063N Translation Of The Original Instructions Download Page 5

5

11.01.21 en / 335A

Auxiliary voltage A1/A2
Nominal auxiliary voltage U

H

MK 9063N, MH 9063:

 

DC 24 V 

     (0.9 ... 1.1 x U

H

)

   

AC/DC 24 ... 230 V   (0,8 ... 1,1 x U

H

)

   

(on request)

MH 9063:

 

AC/DC 110 ... 400 V (0.8 ... 1.1 x U

H

)

Nominal frequency:

 

50 / 60 Hz

Frequency range::

 

45 ... 400 Hz

Input current

At DC 24 V: 

50 mA

At AC 230 V: 

15 mA

Current Measuring Input i+/k

Measuring range

Internal resistance

Max. current

AC/DC 1 ... 20 mA

1.5 

0.7 A

AC/DC 4 ... 100 mA

150 m

2.0 A

AC/DC 20 ... 500 mA

30 m

5.0 A

AC/DC 0.4 ... 10 A

3 m

15 A

other on request

Nominal frequency:

 

50 / 60 Hz

Frequency range

 

AC: 

10 ... 400 Hz

Setting Range (absolute, via button and LCD-display)

Measuring accuracy
at nominal frequency: 

±

 1 %  

±  

2 Digit

Hysteresis

(in % of setting value):

 

2 ...  50 %

Reaction time:

 

< 350 ms

Adjustable on delay (t

v

):

 

0 ... 10 sec (in steps of  0.1 sec)

Adjustable start up delay (t

a

):

  0.2 ... 10 sec (in steps of 0,1 sec)

Output Circuit (Rel1: 11/12/14; Rel2: 21/22/24)

Contacts:   

 

MK 9063N: 

1 changeover contact

MH 9063: 

1 changeover contact (Rel1) and 

   

1 changeover contact (Rel2)

Thermal current I

 th

:

 

2 x 4 A

Switching capacity

To AC 15 
NO contacts: 

3 A / AC 230 V      IEC/EN 60947-5-1

NC contacts: 

1 A / AC 230 V      IEC/EN 60947-5-1

To DC 13 
NO contacts: 

1 A / DC 24 V      IEC/EN 60947-5-1

NC contacts: 

1 A / DC 24 V      IEC/EN 60947-5-1

Electrical life

  

To AC 15 at 3 A, AC 230 V: 

 2 x 10

5

 switch. cycl.  IEC/EN 60947-5-1

Permissible switching 
frequency:

 

1800 / h

Short circuit strength
Max. fuse rating:

 

4 A gG / gL 

IEC/EN 60947-5-1

Mechanical life

30 x 10

6

 switching cycles

General Data

Nominal operating mode:

 

Continuous operation

Temperature range: 
Operation: 

- 20... + 60°C

 

(at range 0 ... - 20°C limited

 

function of the LCD display)

Storage: 

- 25... + 60°C

Altitude:

 

< 2000 m

Clearance and creepage distance

Overvoltage category: 

III

Rated impulse voltage /
pollution degree: 

 

IEC/EN 60664-1

MK:
Auxiliary voltage / meas. input:  4 kV / 2
Auxiliary voltage / contact: 

6 kV / 2

Measuring input / contact: 

6 kV / 2

MH:
Auxiliary voltage / meas. input:   4 kV / 2   (U

H

 = DC 24 V)

Auxiliary voltage / meas. input:  6 kV / 2
Auxiliary voltage / contacts: 

6 kV / 2

Measuring input / contacts: 

6 kV / 2

Contacts 11,12,14 / 21,22,24:  4 kV / 2     

EMC

Electrostatic discharge (ESD):  8 kV (air) 

IEC/EN 61000-4-2

HF irradiation
80 MHz … 2.7 GHz: 

20 V / m 

IEC/EN 61000-4-3

Damped oscillatory wave
immunity test
Differential mode voltage: 

1 kV 

IEC/EN 61000-4-18

Common mode voltage: 

2.5 kV 

IEC/EN 61000-4-18

Fast transients:  

2 kV 

IEC/EN 61000-4-4

Surge voltage
Between
wires for power supply:  

1 kV 

IEC/EN 61000-4-5

Between wire and ground:  

2 kV 

IEC/EN 61000-4-5

HF-wire guided:  

10 V 

IEC/EN 61000-4-6

Interference suppression: 

Limit value class A*)

 

*) The device is designed for the usage

 

under industrial conditions (Class A,

 

EN 55011).

 

When connected to a low voltage public

 

system (Class B, EN 55011) radio inter-  

 

ference can be generated. To avoid this, 

 

appropriate measures have to be taken.

Degree of protection

Housing: 

IP 40 

DIN EN 60529

Terminals:  

IP 20 

DIN EN 60529

Housing: 

 

Thermoplastic with VO behaviour

 

according to UL Subject 94

Vibration resistance:

 

Amplitude 0.35 mm, 

 

frequency 10 ... 55 Hz  IEC/EN 60068-2-6

Climate resistance: 

 

20 / 060 / 04 

EN 60068-1

Wire connection:

 

DIN 46228-1/-2/-3/-4

Screw terminal
(fixed):

 

1 x 4 mm

2

 solid or

   

1 x 2.5 mm

2

 stranded ferruled (isolated) or

   

2 x 1.5 mm

2

 stranded ferruled (isolated) or 

   

2 x 2.5 mm

2

 solid

Insulation of wires or 
sleeve length: 

8 mm

Terminal block
with screw terminals

Max. cross section: 

1 x 2.5 mm

2

 solid or

   

1 x 2.5 mm

2

 stranded ferruled (isolated)

Insulation of wires or 
sleeve length: 

8 mm 

Terminal block
with cage clamp terminals

Max. cross section: 

1 x 4 mm

2

 solid or

   

1 x 2.5 mm

2

 stranded ferruled (isolated)

Min. cross section: 

0.5 mm

2

Insulation of wires or 
sleeve length: 

12 

+0.5 

mm

Wire fixing:

 

Plus-minus terminal screws M3,5 box 

   

terminals with wire protection

   

or cage clamp terminals

Fixing torque:

 

0.8 Nm

Mounting:

 

DIN rail  

EN 60715

Weight:

 

MK 9063N: 

Approx. 140 g

MH 9063: 

Approx. 250 g

Dimensions

Width x height x depth:

 

MK 9063N: 

22.5 x 90 x 99  mm

MH 9063: 

   45 x 90 x 99  mm

Technical Data

Technical Data

Vibration and 
shock resistance: 

Category 1, Class B 

IEC/EN 61373

Ambient temperature:  

T1 compliant

 

T2, T3 and TX with operational limitations

Protective coating of the PCB:

 No

Classification to DIN EN 50155

Summary of Contents for MK 9063N

Page 1: ... 2 relay outputs The current monitoring can be assigned ro relay 1 and or relay 2 Circuit Diagrams MK 9063N 11 MH 9063 12 Example overcurrent monitoring with de energized on trip t t t ta tv M10935 I Hyst 11 14 I UH 21 11 A1 k 22 12 24 14 A2 M10936_c 11 12 14 21 22 24 i i k 11 A1 12 A2 14 M10937_a 11 12 14 The current relays MK 9063N and MH 9063 of the varimeter family provide a solution for an op...

Page 2: ...es Pressing Esc for more than 3 sec starts the input mode If the setting value is exceeded the relay switches and the display indica tes this state The display is inverted flashes and shows the error The fault memory is selectable With button the fault memory can be deleted On the unit MH 9063 it is possible to assign different functions to the diffe rent relays so one can be used as pre warning a...

Page 3: ...e corresponding relay output switches after the selected time delay tv and the fault is indicated on the display Manual reset can be activated or de activated and is operated with on the unit Limit values for Rel 1 and Rel 2 Selectable with buttons Factory setting I Response value undercurrent Undercurrent relay OFF I Response value overcurrent Overcurrent relay Hyst Response value hysteresis 5 tv...

Page 4: ...nt is disabled the relays are in failure mode and the indicator LED is orange With the buttons the different setting values can be chosen Move cursor position One character to the right Esc One character to the left Back to the Display Run Mode Press button 3 s OK New values stored or Press button Esc 3 s Break Values unchanged RUN on the display confirm with to change to display Run mode Display ...

Page 5: ... kV 2 Measuring input contacts 6 kV 2 Contacts 11 12 14 21 22 24 4 kV 2 EMC Electrostatic discharge ESD 8 kV air IEC EN 61000 4 2 HF irradiation 80 MHz 2 7 GHz 20 V m IEC EN 61000 4 3 Damped oscillatory wave immunity test Differential mode voltage 1 kV IEC EN 61000 4 18 Common mode voltage 2 5 kV IEC EN 61000 4 18 Fast transients 2 kV IEC EN 61000 4 4 Surge voltage Between wires for power supply 1...

Page 6: ...o the right and left 4 Please note that the terminal blocks have to be mounted on the belonging plug in terminations Screw terminal PS plugin screw Cage clamp terminal PC plugin cage clamp Options with Pluggable Terminal Blocks Notes Set Up Procedure Safety Notes MK 9063N 11 AC DC 0 4 10 A DC 24 V Article number 0065457 Measuring range AC DC 0 4 10 A Auxiliary voltage UH DC 24 V Output 1 changeove...

Reviews: