DOLD MK 9063N Translation Of The Original Instructions Download Page 1

1

11.01.21 en / 335A

Monitoring technique

VARIMETER

Current relay
MK 9063N, MH 9063

Your Advantages

•  Preventive maintenance

•  For better productivity

•  Quicker fault locating

•  Precise and reliable

•  Min-, Max. value or window monitoring

•  Measuring ranges up to AC/DC 10 A 

•  Simple configuration and fault diagnostic

•  Auxiliary voltage ranges DC 24 V, AC/DC 24 ... 230 V or 

  AC/DC 110 ... 400 V

Features

  According to IEC/EN 60255-1

•  AC/DC current measuring (single-phase)

•  Start up delay, on delay

•  Manual reset 

•  LCD for indication of the measuring values

•  Relay output

  MK 9063N:  

      1 changeover contact

  MH 9063:  

2 x 1 changeover contacts

•  Relay function selectable (energized/de-energized on trip)

•  As option with plugable terminal blocks for easy exchange of devices

 

- With screw terminals

 

- Or with cage clamp terminals

•  Width MK 9063N:  22.5 mm

•  Width MH 9063:    45.0 mm

•  Current monitoring AC/DC single-phase
•  Current dependent switching at under- or overcurrent

0273448

MH 9063

MK 9063N

•  MH 9063

  The MH 9063 has 2 relay outputs. 
 The 

current monitoring can be assigned ro relay 1 and /or relay 2

 

Circuit Diagrams

MK 9063N.11

MH 9063.12

Example: overcurrent monitoring with de-energized on trip

t

t

t

t

a

t

v

M10935

>I
Hyst

11
14

I

U

H

21

11

A1

(+)

k

22

12

24

14

A2

M10936_c

11

12 14

21

22 24

i

(+)

i

(+)

k

11

A1

+

12

A2

14

M10937_a

11

12 14

The current relays MK 9063N and MH 9063 of the varimeter family provide 
a solution for an optimised monitoring of the function or the load current 
of an electrical device. Single-phase AC and also DC can be measured, 
undercurrent, overcurrent and current window are monitored and the 
measured value is displayed on the front.

Terminal designation

Signal description

A1(+), A2

Auxiliary voltage AC or DC

i(+)

Current measuring circuit (+) 
Input DC, AC

k

Current measuring circuit
Output DC, AC

11,12,14

Indicator relay (C/O contact)

21, 22, 24

Indicator relay (C/O contact)

Product Description

More Information

Function Diagram

Approvals and Markings

Applications

Connection Terminals

Translation

of the original instructions

All technical data in this list relate to the state at the moment of edition. We reserve the right for 
technical improvements and changes at any time.

Summary of Contents for MK 9063N

Page 1: ... 2 relay outputs The current monitoring can be assigned ro relay 1 and or relay 2 Circuit Diagrams MK 9063N 11 MH 9063 12 Example overcurrent monitoring with de energized on trip t t t ta tv M10935 I Hyst 11 14 I UH 21 11 A1 k 22 12 24 14 A2 M10936_c 11 12 14 21 22 24 i i k 11 A1 12 A2 14 M10937_a 11 12 14 The current relays MK 9063N and MH 9063 of the varimeter family provide a solution for an op...

Page 2: ...es Pressing Esc for more than 3 sec starts the input mode If the setting value is exceeded the relay switches and the display indica tes this state The display is inverted flashes and shows the error The fault memory is selectable With button the fault memory can be deleted On the unit MH 9063 it is possible to assign different functions to the diffe rent relays so one can be used as pre warning a...

Page 3: ...e corresponding relay output switches after the selected time delay tv and the fault is indicated on the display Manual reset can be activated or de activated and is operated with on the unit Limit values for Rel 1 and Rel 2 Selectable with buttons Factory setting I Response value undercurrent Undercurrent relay OFF I Response value overcurrent Overcurrent relay Hyst Response value hysteresis 5 tv...

Page 4: ...nt is disabled the relays are in failure mode and the indicator LED is orange With the buttons the different setting values can be chosen Move cursor position One character to the right Esc One character to the left Back to the Display Run Mode Press button 3 s OK New values stored or Press button Esc 3 s Break Values unchanged RUN on the display confirm with to change to display Run mode Display ...

Page 5: ... kV 2 Measuring input contacts 6 kV 2 Contacts 11 12 14 21 22 24 4 kV 2 EMC Electrostatic discharge ESD 8 kV air IEC EN 61000 4 2 HF irradiation 80 MHz 2 7 GHz 20 V m IEC EN 61000 4 3 Damped oscillatory wave immunity test Differential mode voltage 1 kV IEC EN 61000 4 18 Common mode voltage 2 5 kV IEC EN 61000 4 18 Fast transients 2 kV IEC EN 61000 4 4 Surge voltage Between wires for power supply 1...

Page 6: ...o the right and left 4 Please note that the terminal blocks have to be mounted on the belonging plug in terminations Screw terminal PS plugin screw Cage clamp terminal PC plugin cage clamp Options with Pluggable Terminal Blocks Notes Set Up Procedure Safety Notes MK 9063N 11 AC DC 0 4 10 A DC 24 V Article number 0065457 Measuring range AC DC 0 4 10 A Auxiliary voltage UH DC 24 V Output 1 changeove...