DOLD MK 9063N Translation Of The Original Instructions Download Page 3

3

11.01.21 en / 335A

Display (Run) - Mode

Input-Mode

 UP  /  

 DOWN

After power up the relay is in display (Run) mode. 

The measurement is interrupted, the relays are in failure state and the 
indicator LED has orange color

 

 

 Buttons have no function

 

 

 Selection of parameters and setting of thresholds

 ENTER

Manual reset, when manual reset is selected for output relay

- Shifts cursor to the right

Reset works only when fault is removed

- Saves the value no-voltage safe
- Pressing for more than 3 sec: Change to display (Run) mode

Esc

 Esc

- Pressing for more than 3 sec: Change to input mode

- Shifts cursor to the left
- Leave setting without saving

LCD-Display

Rel.1 Rel.2 Sp1 Sp2

Rel.1 Rel.2 Sp1 Sp2

<I

Rel.1 Rel.2 Sp1 Sp2

>I

Rel.1 Rel.2 Sp1 Sp2

<I

Setting Parameter

< I        Fault, when value drops under set point
> I        Fault, when value exceeds set point
OFF     Measurement disabled

If the adjusted threshold of at least one measuring function is exceeded, the corresponding relay output switches after the selected time delay tv and 
the fault is indicated on the display.

Manual reset can be activated or de-activated and is operated with 

 on the unit.

Limit values for Rel.1 and Rel.2
Selectable with buttons 

 

 

.

Factory

setting

<I:

Response value undercurrent  
(Undercurrent relay)

OFF

>I:

Response value overcurrent ,  
(Overcurrent  relay)

*

Hyst: Response value hysteresis

5 %

t

v

:

On delay for relays  ( 0 ... 10 sec )

0 s

A / R: Seting open- / closed circuit operation

R

Sp:

Error storage ( ON / OFF )

OFF

Response values can be deactivated. (OFF)
*) dependent to device-variant (measuring range)

Selectable with buttons  

 

 

.

Factory

setting

t

a

:

Start up delay, when auxiliary voltage connected 
( 0.2 ... 10 s)

0,2 s

AC/DC Measuring current AC or DC

AC

 

Restore Factory Settings

(Restore factory settings)
Before auxiliary voltage connected press button 

Esc

 .

During start press and hold.

 

Indicator output

The switching mode energized or de-energized on trip can be set in input 
mode. The MH 9063 has 2 relay outputs. Monitoring function can be assig-
ned to Relay 1 and/or to Relay 2.

Operating

Adjustable Parameter

Further Setting Parameter

Summary of Contents for MK 9063N

Page 1: ... 2 relay outputs The current monitoring can be assigned ro relay 1 and or relay 2 Circuit Diagrams MK 9063N 11 MH 9063 12 Example overcurrent monitoring with de energized on trip t t t ta tv M10935 I Hyst 11 14 I UH 21 11 A1 k 22 12 24 14 A2 M10936_c 11 12 14 21 22 24 i i k 11 A1 12 A2 14 M10937_a 11 12 14 The current relays MK 9063N and MH 9063 of the varimeter family provide a solution for an op...

Page 2: ...es Pressing Esc for more than 3 sec starts the input mode If the setting value is exceeded the relay switches and the display indica tes this state The display is inverted flashes and shows the error The fault memory is selectable With button the fault memory can be deleted On the unit MH 9063 it is possible to assign different functions to the diffe rent relays so one can be used as pre warning a...

Page 3: ...e corresponding relay output switches after the selected time delay tv and the fault is indicated on the display Manual reset can be activated or de activated and is operated with on the unit Limit values for Rel 1 and Rel 2 Selectable with buttons Factory setting I Response value undercurrent Undercurrent relay OFF I Response value overcurrent Overcurrent relay Hyst Response value hysteresis 5 tv...

Page 4: ...nt is disabled the relays are in failure mode and the indicator LED is orange With the buttons the different setting values can be chosen Move cursor position One character to the right Esc One character to the left Back to the Display Run Mode Press button 3 s OK New values stored or Press button Esc 3 s Break Values unchanged RUN on the display confirm with to change to display Run mode Display ...

Page 5: ... kV 2 Measuring input contacts 6 kV 2 Contacts 11 12 14 21 22 24 4 kV 2 EMC Electrostatic discharge ESD 8 kV air IEC EN 61000 4 2 HF irradiation 80 MHz 2 7 GHz 20 V m IEC EN 61000 4 3 Damped oscillatory wave immunity test Differential mode voltage 1 kV IEC EN 61000 4 18 Common mode voltage 2 5 kV IEC EN 61000 4 18 Fast transients 2 kV IEC EN 61000 4 4 Surge voltage Between wires for power supply 1...

Page 6: ...o the right and left 4 Please note that the terminal blocks have to be mounted on the belonging plug in terminations Screw terminal PS plugin screw Cage clamp terminal PC plugin cage clamp Options with Pluggable Terminal Blocks Notes Set Up Procedure Safety Notes MK 9063N 11 AC DC 0 4 10 A DC 24 V Article number 0065457 Measuring range AC DC 0 4 10 A Auxiliary voltage UH DC 24 V Output 1 changeove...