The unit needs a connected auxiliary supply.
It is designed for single phase AC/DC measurement.

The LED indicates the state.

Green: 

On, when auxiliary voltage present

Orange (flashes): 

No measurement;  

 

unit in input mode

Red (short On, short Off): 

Failure overvoltage

If the measured value is higher then the upper end of scale value, the 
display shows the fault message "OL"

The Device is programmable for AC- or DC- measuring. 
On AC-measurement the rectified mean value is measured. 
On sinusoidal input signals the RMS value is  displayed. 

After connecting the auxiliary supply to terminals A1-A2 the startup delay 
disables the monitoring function so that changes on the input have no 
influence on the relay output of the VARIMETER. 
The device is in display (RUN) mode and continuously measures the actu-
al values. Pressing  

Esc

 for more than 3 sec starts the input mode.

If the setting value is exceeded the relay switches and the display indica-
tes this state. The display is inverted, flashes and shows the error.

The fault memory is selectable 
With button 

 the fault memory can be deleted.

On the unit MH 9063 it is possible to assign different functions to the diffe-
rent relays so one can be used as pre-warning and the other as alarm out-
put. Relay output 1 switches when actual value exceeds the pre-warning 
setting. If a second setting assigned to relay output 2 the unit gives an 
Alarm signal.

M11492_a

Change to setup mode (3...6s)

Change to Run mode (3...6s)

LED status indication

Error memory 1 active

Error memory 2 active

Display “Rel.2” active

Display “Rel.1” active

Selection of
Functions / Setting and
measuring values

Active manual reset
Manual reset activated: Lashes when 
memory mode is ON and relay in failure state.
Reset with button "

"

Contact state of the output relays

Function

Setting

Indicators

Cursor LCD Display

Remarks

Summary of Contents for MK 9063N

Page 1: ... 2 relay outputs The current monitoring can be assigned ro relay 1 and or relay 2 Circuit Diagrams MK 9063N 11 MH 9063 12 Example overcurrent monitoring with de energized on trip t t t ta tv M10935 I Hyst 11 14 I UH 21 11 A1 k 22 12 24 14 A2 M10936_c 11 12 14 21 22 24 i i k 11 A1 12 A2 14 M10937_a 11 12 14 The current relays MK 9063N and MH 9063 of the varimeter family provide a solution for an op...

Page 2: ...es Pressing Esc for more than 3 sec starts the input mode If the setting value is exceeded the relay switches and the display indica tes this state The display is inverted flashes and shows the error The fault memory is selectable With button the fault memory can be deleted On the unit MH 9063 it is possible to assign different functions to the diffe rent relays so one can be used as pre warning a...

Page 3: ...e corresponding relay output switches after the selected time delay tv and the fault is indicated on the display Manual reset can be activated or de activated and is operated with on the unit Limit values for Rel 1 and Rel 2 Selectable with buttons Factory setting I Response value undercurrent Undercurrent relay OFF I Response value overcurrent Overcurrent relay Hyst Response value hysteresis 5 tv...

Page 4: ...nt is disabled the relays are in failure mode and the indicator LED is orange With the buttons the different setting values can be chosen Move cursor position One character to the right Esc One character to the left Back to the Display Run Mode Press button 3 s OK New values stored or Press button Esc 3 s Break Values unchanged RUN on the display confirm with to change to display Run mode Display ...

Page 5: ... kV 2 Measuring input contacts 6 kV 2 Contacts 11 12 14 21 22 24 4 kV 2 EMC Electrostatic discharge ESD 8 kV air IEC EN 61000 4 2 HF irradiation 80 MHz 2 7 GHz 20 V m IEC EN 61000 4 3 Damped oscillatory wave immunity test Differential mode voltage 1 kV IEC EN 61000 4 18 Common mode voltage 2 5 kV IEC EN 61000 4 18 Fast transients 2 kV IEC EN 61000 4 4 Surge voltage Between wires for power supply 1...

Page 6: ...o the right and left 4 Please note that the terminal blocks have to be mounted on the belonging plug in terminations Screw terminal PS plugin screw Cage clamp terminal PC plugin cage clamp Options with Pluggable Terminal Blocks Notes Set Up Procedure Safety Notes MK 9063N 11 AC DC 0 4 10 A DC 24 V Article number 0065457 Measuring range AC DC 0 4 10 A Auxiliary voltage UH DC 24 V Output 1 changeove...

Reviews: