DOLD BG 5914.08 0 Series Operating Instructions Manual Download Page 8

8

BG 5914.08/_0_ _ _, BH 5914.08/_0_ _ _ / 03.11.20 / 314A

Voltage Supply

Nominal voltage U

N

:

 

DC 24 V

   

(comes from basic module BH 5911)

Voltage range:

 

with max. 5% residual ripple: 

0.85 ... 1.15 U

N

Nominal consumption:

 

max. 60 mA

   

(no load on semiconductor outputs)

Short-circuit protection  

of the modules:

 

internally with PTC

Inputs:

Control voltage over 

 

   

  

X1, X2, X42, 48, 58: 

DC 23 V at U

N

Control current over 

S11, S12, S13, S14, S21,

S22, S23, S24, S31, S32, 

S33, S34, S41, S42, S43

S44: 

4.5 mA each at U

N

Minimum voltage at

S12, S14, S22,

S24, S32, S34 S42, S44

 

DC 16 V

Outputs

Output on terminal

48 and 58: 

  Transistor outputs, plus-connected

Output nominal voltage: 

  DC 24 V, max. 100 mA constant current, 

 

  max. 400 mA for 0.5 s 

  Internal overtemperature and

 

  overload protection

Reaction times 

(time till reaction of the assigned output):

Typ. operating time with U

N

:

Input modules
BG 5914 and
BH 5914

Manual start

Automatic start

First start

Restart

Emergency stop

max. 75 ms

max. 1 s

max. 75 ms

Break time

 (reaction time):

Input modules
BG 5914 and
BH 5914

Emergency stop

max. 33 ms

General Data

Operating mode:

 

Continuous operation

Temperature range: 

±

 0 ... + 50 

°

C

   

At an operating temperature of 50 °C

   

the modules must be mounted with

   

a distance of 3 - 5 mm.

Clearance and creepage  

distances

rated impulse voltage /

pollution degree: 

4 kV / 2 (basis insulation)  IEC 60 664-1

EMC: 

IEC/EN 61 326-3-1, IEC/EN 62 061

Radio interference 
suppression: 

Limit value class A 

EN 55 011

Remark:  This device is designed for industrial ambient conditions. 
When used in other environment, it is possible that wire bound or 
radiated interference occurs.
Degree of protection

Housing: 

IP 20 

IEC/EN 60 529

Terminals: 

IP 20 

IEC/EN 60 529

Housing:

 

Thermoplast with V0 behavior

 

according to UL Subject 94

Vibration resistance:

 

Amplitude 0.35 mm 

Shock resistance

Acceleration: 

10 g

Pulse duration: 

16 ms

Number of shocks: 

1000 per axis on three axes

Climate resistance:

 

0 / 050/ 04 

IEC/EN 60 068-1

Terminal designation:

  

EN 50 005

Wire connection:

 

DIN 46 228-1/-2/-3/-4

Wire fixing:

 

Box terminal with wire protection, remov-
able terminal strips

Mounting:

 

DIN rail  

      IEC/EN 60715

Dimensions

Width x height x depth:

BG 5914:  

 

22.5 x 84 x 121 mm

BH 5914: 

45 x 84 x 121 mm

BG 5914.08/00MF0: 

8 floating inputs 

 

(width 22,5 mm)

Article number:  

0056633

BH 5914.08/00MF0: 

8 floating inputs or 

 

non-floating inputs

 

(width 45 mm)

Article number: 

0056460

Technical Data

Technical Data

Standard Types

Summary of Contents for BG 5914.08 0 Series

Page 1: ...OT AUS 1 kanalig 1 NOT AUS 2 kanalig Auto Start 5 NOT AUS 1 kanalig 1 NOT AUS 2 kanalig 1Meldeeingang Auto Start 8 NOT AUS 1 kanalig manueller Start 6 NOT AUS 1 kanalig 1 NOT AUS 2 kanalig manueller S...

Page 2: ...astern T1 T4 und den Sicher heitsausg ngen Relais erfolgt ber DIP Schalter Die Einstellung der Funktionskombination erfolgt ber die Drehschalter Potis Um Manipu lationen auszuschlie en sind die Einste...

Page 3: ...en oder beim Auftreten eines Fehlers bet tigt 5 Eingangsfehler Kurzschluss Unterbrechung 6 Fehler in der Steuereinheit Eingangs oder Ausgangsfehler in der Steuereinheit erkannt Anzahl von kurzen Blink...

Page 4: ...zwischen den Modulen ein Abstand von ca 3 5 mm einge halten werden Luft und Kriechstrecken Bemessungssto spannung Verschmutzungsgrad 4 kV 2 Basisisolierung IEC 60 664 1 EMV IEC EN 61 326 3 1 IEC EN 6...

Page 5: ...nual start 6 E STOP single channel 1 E STOP 2 channel manual start 5 E STOP single channel 1 E STOP 2 channel 1 signal input manual start As an alternative to the 2 channel E STOP a light curtain LC t...

Page 6: ...nd BH 5914 are completely identical The modules are assigned to the start buttons and the safety outputs via the DIP switches The function is set via the rotary switches To prevent accidently adjust m...

Page 7: ...error recognized in the con trol unit number of short flashing impulses followed by a longer space Permanently OFF Pulsing Permanent ON Output 48 all relays inactive due to system error one input func...

Page 8: ...mperature range 0 50 C At an operating temperature of 50 C the modules must be mounted with a distance of 3 5 mm Clearance and creepage distances rated impulse voltage pollution degree 4 kV 2 basis in...

Page 9: ...A U 1 canal 1 A U 2 canaux avec d marrage auto 5 A U 1 canal 1 A U 2 canaux 1 entr e de signalisation avec d marrage auto 8 A U 1 canal avec d marrage manuel 6 A U 1 canal 1 A U 2 canaux avec d marrag...

Page 10: ...de 45 mm L affectation de l unit centrale aux boutons start T1 T4 et aux sorties de s curit relais s effectue par interrupteurs DIP Le r glage de la fonction s effectue au moyen de potentiom tres Pour...

Page 11: ...ies de s curit correspondantes est autoris e DEL run 1 Tous relais inactifs suite d faut syst me D faut de fonct quand DEL run 2 allum e ou d faut syst me quand DEL run 2 tein ou clignote L activation...

Page 12: ...mp ratures 0 50 C Pour une temp rature de service de 50 une distance de 3 5 mm entre les modules doit tre respect e Distances dans l air et lignes de fuite Cat gorie de surtension degr de contaminatio...

Page 13: ...unctions 1 or 5 FR BG 5914 6 A U 1 canal 1 A U 2 canaux avec d tection de court circuit fonctions 1 5 DE Anwendungsbeispiele EN Application examples FR Exemples d utilisation X1 X2 S12 S14 S22 S24 S32...

Page 14: ...R BG 5914 5 arr t d urgence 1 canal 1 EPES de type 4 1 contact de signalisation interrupteurs gradins 3 et 7 DE Anwendungsbeispiele EN Application examples FR Exemples d utilisation X1 X2 S12 S14 S22...

Page 15: ...7 FR BH 5914 5 A U 1 canal 1 A U commun 2 canaux avec d tection de court circuit par c blage 1 contact de signalisation interrupteurs gradins 3 7 DE Anwendungsbeispiele EN Application examples FR Exe...

Page 16: ...1 48 X1 58 X2 X1 X2 X1 X2 X2 M8742 S11 S31 S14 S34 S21 X1 X2 X1 X2 X1 X2 X1 X2 S41 S22 S42 S23 S43 S24 S44 S12 S32 S13 S33 48 58 A1 A1 X1 S44 S42 S34 S32 S24 S22 S14 S12 X2 48 58 input module PTC inpu...

Page 17: ...Dimensions dimensions en mm M10050 45 Hutschiene DIN EN 60715 121 118 84 35 DE Montage Demontage der Klemmenbl cke EN Mounting disassembly of the terminal blocks FR D montage des borniers ammovibles D...

Page 18: ...HD 3 53E 09 h 1 HFT Hardware Fehlertoleranz Hardware failure tolerance Tol rance d fauts Hardware Anforderung seitens der Sicherheitsfunktion an das Ger t Intervall f r zyklische berpr fung der Sicher...

Page 19: ...multifonctions Produktbezeichnung Type designation D signation du produit Beschreibung Description Description BH5911 03 00MF0 DC24V Steuereinheit Control Unit Unit centrale BH5911 22 00MF0 DC24V BG59...

Page 20: ...BG 5914 08 _0_ _ _ BH 5914 08 _0_ _ _ 03 11 20 314A E DOLD S HNE KG D 78120 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 3...

Reviews: