DOLD BG 5914.08 0 Series Operating Instructions Manual Download Page 7

7

BG 5914.08/_0_ _ _, BH 5914.08/_0_ _ _ / 03.11.20 / 314A

This module is intended for applications in which numerous one-channel 
Emergency off contacts are to be monitored.

The settings 2, 3, 6, and 7 are required for example when several modules 
are connected to a common Emergency stop sensor. Short-circuit reco-
gnition can be realized externally by means of proper wiring.

With a LC type 4 (according to IEC/EN 61496-1), short-circuit monitoring 
takes place in the light curtain itself.

Note:

With single-channel safety inputs, safety function can only be realized 
when voltfree contacts are used (see wiring examples). 

With static, voltage signals, it is imperative to use 2-channel signal
sensors.

Automatic start is performed only when supply voltage is switched on, or 
when enabling has been cancelled by pressing Emergency stop.

All other errors nevertheless require confirmation by a start key.

To start the system, do not keep the start key pressed for more than 3 
seconds. A module may also be assigned several start keys.

Function errors are indicated by the white LED Run 1 and by output 48; 
the white LED Run 2 remains on. Output 58 remains on as long as the 
error is pending; it flashes regularly as soon as enabling via the assigned 
start button is possible again:

Error codes*

1)  Emergency stop
2)  Time error: Start button has been kept pressed for more than 3 se-

conds

3)  Time error: The 2 signals of the 2-channel Emergency stop fail to 

correspond for too long (250 ms)

4)  Error on start button (kept permanently pressed)
5)   Input error (short-circuit, interruption)
6)  Error in the control unit (input or output error recognized in the con-

trol unit)

* number of short flashing impulses, followed by a longer space

Permanently OFF

Pulsing

Permanent ON

Output 

48

all relays inactive

due to system 

error

one input function 

not available

Activation of the 

assigned safety

outputs is 

permissible

LED

Run 1

all relays inactive

due to system 

error

one input function 

not available

(LED run 2 ON) or 

system error when 
LED Run 2 is OFF

or flashing

Activation of

the assigned

safety

outputs is 

permissible

Output

58

Activation of the 

assigned safety 

outputs is permis-

sible or system 

error

Wait for start

one input function 

not available or

K1 and K2 active 

and indicator con-

tact inactive

LED

Run 2

all relays inactive

due to system 

error or 

K1 and K2 active 

and indicator con-

tact inactive

all relays inactive

due to system 

error

No system error

These errors are indicated by flashing codes of the white LEDs Run 1 and/
or Run 2. The green LEDs and all outputs turn inactive. The system will 
only restart after the supply voltage has been switched off and on again. 

Error codes*

0) 

(both white LEDs are off): 

 

Another input module indicates a system error.

1)  

To 4): not used

5) 

Incorrect setting of function:

 

- The rotary switches for channel 1 and 2 has different or 

 

   incorrect positions

 

- The setting of the 4 upper Dip-switches (channel 1) are not 

 

  identically to the 4 lower Dip-switches (channel 2)

6) 

LED Run 1 flashes: Undervoltage

 

LED Run 2 flashes: Overvoltage

7), 8) Not used
9) 

Connection error between the input modules

 

No terminating connector available.

 

·  Control or input module defective

10), 11), 12), 13) a. 14) Internal errors

* number of short flashing impulses, followed by a longer space

Setting of the Module

Single-Channel Emergency-Stop

Automatic Start

Manual Start

Function Error Indication

Indication

Indication of System Errors:

Summary of Contents for BG 5914.08 0 Series

Page 1: ...OT AUS 1 kanalig 1 NOT AUS 2 kanalig Auto Start 5 NOT AUS 1 kanalig 1 NOT AUS 2 kanalig 1Meldeeingang Auto Start 8 NOT AUS 1 kanalig manueller Start 6 NOT AUS 1 kanalig 1 NOT AUS 2 kanalig manueller S...

Page 2: ...astern T1 T4 und den Sicher heitsausg ngen Relais erfolgt ber DIP Schalter Die Einstellung der Funktionskombination erfolgt ber die Drehschalter Potis Um Manipu lationen auszuschlie en sind die Einste...

Page 3: ...en oder beim Auftreten eines Fehlers bet tigt 5 Eingangsfehler Kurzschluss Unterbrechung 6 Fehler in der Steuereinheit Eingangs oder Ausgangsfehler in der Steuereinheit erkannt Anzahl von kurzen Blink...

Page 4: ...zwischen den Modulen ein Abstand von ca 3 5 mm einge halten werden Luft und Kriechstrecken Bemessungssto spannung Verschmutzungsgrad 4 kV 2 Basisisolierung IEC 60 664 1 EMV IEC EN 61 326 3 1 IEC EN 6...

Page 5: ...nual start 6 E STOP single channel 1 E STOP 2 channel manual start 5 E STOP single channel 1 E STOP 2 channel 1 signal input manual start As an alternative to the 2 channel E STOP a light curtain LC t...

Page 6: ...nd BH 5914 are completely identical The modules are assigned to the start buttons and the safety outputs via the DIP switches The function is set via the rotary switches To prevent accidently adjust m...

Page 7: ...error recognized in the con trol unit number of short flashing impulses followed by a longer space Permanently OFF Pulsing Permanent ON Output 48 all relays inactive due to system error one input func...

Page 8: ...mperature range 0 50 C At an operating temperature of 50 C the modules must be mounted with a distance of 3 5 mm Clearance and creepage distances rated impulse voltage pollution degree 4 kV 2 basis in...

Page 9: ...A U 1 canal 1 A U 2 canaux avec d marrage auto 5 A U 1 canal 1 A U 2 canaux 1 entr e de signalisation avec d marrage auto 8 A U 1 canal avec d marrage manuel 6 A U 1 canal 1 A U 2 canaux avec d marrag...

Page 10: ...de 45 mm L affectation de l unit centrale aux boutons start T1 T4 et aux sorties de s curit relais s effectue par interrupteurs DIP Le r glage de la fonction s effectue au moyen de potentiom tres Pour...

Page 11: ...ies de s curit correspondantes est autoris e DEL run 1 Tous relais inactifs suite d faut syst me D faut de fonct quand DEL run 2 allum e ou d faut syst me quand DEL run 2 tein ou clignote L activation...

Page 12: ...mp ratures 0 50 C Pour une temp rature de service de 50 une distance de 3 5 mm entre les modules doit tre respect e Distances dans l air et lignes de fuite Cat gorie de surtension degr de contaminatio...

Page 13: ...unctions 1 or 5 FR BG 5914 6 A U 1 canal 1 A U 2 canaux avec d tection de court circuit fonctions 1 5 DE Anwendungsbeispiele EN Application examples FR Exemples d utilisation X1 X2 S12 S14 S22 S24 S32...

Page 14: ...R BG 5914 5 arr t d urgence 1 canal 1 EPES de type 4 1 contact de signalisation interrupteurs gradins 3 et 7 DE Anwendungsbeispiele EN Application examples FR Exemples d utilisation X1 X2 S12 S14 S22...

Page 15: ...7 FR BH 5914 5 A U 1 canal 1 A U commun 2 canaux avec d tection de court circuit par c blage 1 contact de signalisation interrupteurs gradins 3 7 DE Anwendungsbeispiele EN Application examples FR Exe...

Page 16: ...1 48 X1 58 X2 X1 X2 X1 X2 X2 M8742 S11 S31 S14 S34 S21 X1 X2 X1 X2 X1 X2 X1 X2 S41 S22 S42 S23 S43 S24 S44 S12 S32 S13 S33 48 58 A1 A1 X1 S44 S42 S34 S32 S24 S22 S14 S12 X2 48 58 input module PTC inpu...

Page 17: ...Dimensions dimensions en mm M10050 45 Hutschiene DIN EN 60715 121 118 84 35 DE Montage Demontage der Klemmenbl cke EN Mounting disassembly of the terminal blocks FR D montage des borniers ammovibles D...

Page 18: ...HD 3 53E 09 h 1 HFT Hardware Fehlertoleranz Hardware failure tolerance Tol rance d fauts Hardware Anforderung seitens der Sicherheitsfunktion an das Ger t Intervall f r zyklische berpr fung der Sicher...

Page 19: ...multifonctions Produktbezeichnung Type designation D signation du produit Beschreibung Description Description BH5911 03 00MF0 DC24V Steuereinheit Control Unit Unit centrale BH5911 22 00MF0 DC24V BG59...

Page 20: ...BG 5914 08 _0_ _ _ BH 5914 08 _0_ _ _ 03 11 20 314A E DOLD S HNE KG D 78120 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 3...

Reviews: