DOLD BG 5914.08 0 Series Operating Instructions Manual Download Page 12

12

BG 5914.08/_0_ _ _, BH 5914.08/_0_ _ _ / 03.11.20 / 314A

Tension assignée

:  

U

N

: DC 24 V (provient du module de    

 

 

base BH 5911)

Plage de tensions

à 5 % max. d'ondulation 
résiduelle: 

0,85 ...l,15 U

N

Consommation nomin.

max. 60mA 

 

(sorties à semi-conducteurs non  

 

   chargées)

Protection des modules

interne par PTC

Entrées

Tension de commande

par  X1, X2, X42,  48.58: 

DC 23 V sous U

N

Courant de commande 

par 

S11, S12, S13, S14, S21,
S22, S23, S24, S31, S32, 
S33, S34, S41, S42, S43,
S44: 

4,5 mA sous U

N

Tension minimale

sur S12, S14, S22, S24, 
S32, S34, S42, S44 

DC 16 V

Sorties 

Sortie sur bornes 48 et 58: 

à transistors, commutation front positif

Tension assignée sortie: 

DC 24 V. max. 100 mA courant permanent

 

max. 400 mA pour 0.5 s 

 

Protection interne contre courts- 

 

 

circuits, échauffement et surcharges

Temps de traitement 

 

(jusqu'à la réaction de la sortie corresp.):  

 

Durée d'enclenchement réf. sous U

N

:

Modules d'entrée

BG 5914 et BH 5914

Démar. manuel

Démarrage automatique
démarrage

démarrage

Arrêt d'urgence

max. 75ms

max. 1 s

max. 75ms

Temps de coupure

 (temps de réaction):

Modules d'entrée

BG 5914 et BH 5914
Arrêt d'urgence

max. 33ms

Caractéristiques générales 

Type nominal de service 

service permanent

Plage de températures:

 

+ 0 ...+ 50 °C

   

Pour une température de service de  

 

   

50°, une distance de 3 à 5 mm entre  

 

   

les modules doit être respectée. 

Distances dans l'air
et lignes de fuite

Catégorie de surtension /
degré de contamination: 

4 kV / 2 (isolation de base) IEC 60 664-1

CEM: 

IEC/EN 61 326-3-1, IEC/EN 62 061

Antiparasitage: 

seuil classe A 

EN 55 011

Remarque: Ceci est un appareil développé pour environement indu-
striel. Des problèmes soit conduits par cable ou émis peuvent appa-
raitre en d‘autres environnements.

Degré de protection

boîtier: 

IP 20 

IEC/EN 60 529

bornes: 

IP 20 

IEC/EN 60 529

Boîtier:

 

thermoplastique à comportement V0

 

selon UL Subject 94

Résistance aux vibrations:

 

amplitude 0,35 mm

Résistance aux chocs

accélération: 

10 g

durée d'impulsion: 

16 ms

nombre de chocs: 

1000 par axe sur 3 axes

Résistance climatique:

 

0 / 050 / 04 

IEC/EN 60 068-1

Repérage des bornes:

  

EN 50 005

Connectique:

 

DIN 46 228-1/-2/-3/-4

Fixation des conducteurs:

 

vis cruciformes imperdables M3,5 bornes 
en caisson avec protection conducteurs

Fixation instantanée:

 

sur rail 

IEC/EN 60715

Dimensions   

largeur x hauteur x profondeur

BG 5914: 

22,5 x 84 x 121 mm

BH 5914: 

45 x 84 x 121 mm

BG 5914.08/00MF0: 

8 entrées hors potentiel 

 

(largeur 22,5 mm)

Référence: 0056633

BH 5914.08/00MF0: 

8 entrées hors potentiel ou liées

 

(largeur 45 mm)

Référence: 

0056460  

Caractéristiques techniques

Caractéristiques techniques

Version standard

Summary of Contents for BG 5914.08 0 Series

Page 1: ...OT AUS 1 kanalig 1 NOT AUS 2 kanalig Auto Start 5 NOT AUS 1 kanalig 1 NOT AUS 2 kanalig 1Meldeeingang Auto Start 8 NOT AUS 1 kanalig manueller Start 6 NOT AUS 1 kanalig 1 NOT AUS 2 kanalig manueller S...

Page 2: ...astern T1 T4 und den Sicher heitsausg ngen Relais erfolgt ber DIP Schalter Die Einstellung der Funktionskombination erfolgt ber die Drehschalter Potis Um Manipu lationen auszuschlie en sind die Einste...

Page 3: ...en oder beim Auftreten eines Fehlers bet tigt 5 Eingangsfehler Kurzschluss Unterbrechung 6 Fehler in der Steuereinheit Eingangs oder Ausgangsfehler in der Steuereinheit erkannt Anzahl von kurzen Blink...

Page 4: ...zwischen den Modulen ein Abstand von ca 3 5 mm einge halten werden Luft und Kriechstrecken Bemessungssto spannung Verschmutzungsgrad 4 kV 2 Basisisolierung IEC 60 664 1 EMV IEC EN 61 326 3 1 IEC EN 6...

Page 5: ...nual start 6 E STOP single channel 1 E STOP 2 channel manual start 5 E STOP single channel 1 E STOP 2 channel 1 signal input manual start As an alternative to the 2 channel E STOP a light curtain LC t...

Page 6: ...nd BH 5914 are completely identical The modules are assigned to the start buttons and the safety outputs via the DIP switches The function is set via the rotary switches To prevent accidently adjust m...

Page 7: ...error recognized in the con trol unit number of short flashing impulses followed by a longer space Permanently OFF Pulsing Permanent ON Output 48 all relays inactive due to system error one input func...

Page 8: ...mperature range 0 50 C At an operating temperature of 50 C the modules must be mounted with a distance of 3 5 mm Clearance and creepage distances rated impulse voltage pollution degree 4 kV 2 basis in...

Page 9: ...A U 1 canal 1 A U 2 canaux avec d marrage auto 5 A U 1 canal 1 A U 2 canaux 1 entr e de signalisation avec d marrage auto 8 A U 1 canal avec d marrage manuel 6 A U 1 canal 1 A U 2 canaux avec d marrag...

Page 10: ...de 45 mm L affectation de l unit centrale aux boutons start T1 T4 et aux sorties de s curit relais s effectue par interrupteurs DIP Le r glage de la fonction s effectue au moyen de potentiom tres Pour...

Page 11: ...ies de s curit correspondantes est autoris e DEL run 1 Tous relais inactifs suite d faut syst me D faut de fonct quand DEL run 2 allum e ou d faut syst me quand DEL run 2 tein ou clignote L activation...

Page 12: ...mp ratures 0 50 C Pour une temp rature de service de 50 une distance de 3 5 mm entre les modules doit tre respect e Distances dans l air et lignes de fuite Cat gorie de surtension degr de contaminatio...

Page 13: ...unctions 1 or 5 FR BG 5914 6 A U 1 canal 1 A U 2 canaux avec d tection de court circuit fonctions 1 5 DE Anwendungsbeispiele EN Application examples FR Exemples d utilisation X1 X2 S12 S14 S22 S24 S32...

Page 14: ...R BG 5914 5 arr t d urgence 1 canal 1 EPES de type 4 1 contact de signalisation interrupteurs gradins 3 et 7 DE Anwendungsbeispiele EN Application examples FR Exemples d utilisation X1 X2 S12 S14 S22...

Page 15: ...7 FR BH 5914 5 A U 1 canal 1 A U commun 2 canaux avec d tection de court circuit par c blage 1 contact de signalisation interrupteurs gradins 3 7 DE Anwendungsbeispiele EN Application examples FR Exe...

Page 16: ...1 48 X1 58 X2 X1 X2 X1 X2 X2 M8742 S11 S31 S14 S34 S21 X1 X2 X1 X2 X1 X2 X1 X2 S41 S22 S42 S23 S43 S24 S44 S12 S32 S13 S33 48 58 A1 A1 X1 S44 S42 S34 S32 S24 S22 S14 S12 X2 48 58 input module PTC inpu...

Page 17: ...Dimensions dimensions en mm M10050 45 Hutschiene DIN EN 60715 121 118 84 35 DE Montage Demontage der Klemmenbl cke EN Mounting disassembly of the terminal blocks FR D montage des borniers ammovibles D...

Page 18: ...HD 3 53E 09 h 1 HFT Hardware Fehlertoleranz Hardware failure tolerance Tol rance d fauts Hardware Anforderung seitens der Sicherheitsfunktion an das Ger t Intervall f r zyklische berpr fung der Sicher...

Page 19: ...multifonctions Produktbezeichnung Type designation D signation du produit Beschreibung Description Description BH5911 03 00MF0 DC24V Steuereinheit Control Unit Unit centrale BH5911 22 00MF0 DC24V BG59...

Page 20: ...BG 5914 08 _0_ _ _ BH 5914 08 _0_ _ _ 03 11 20 314A E DOLD S HNE KG D 78120 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 3...

Reviews: