36
2.Functional Description :- The parameters function and setpoint.
3.Unit :- The setpoint unit.
4.Set range :- The set range of parameters, those parameters without a limited set range
should be adjusted according to the site conditions.
5.Factory Settings :- Parameter factory settings, those parameters without fixed factory
settings should be adjusted according to the site conditions.
6.Settings during operation:
○ :- Settable during operation
× :- Not settable during operation
Control authority :-
J :- Person with the authority to monitor the running state of the MVC.
C :- Operator with the authority to operate the MVC.
T :- Commissioning personnel with the authority to commission the MVC and modify system
parameters.
G :- Responsible person with the authority to modify the MVC control logic.
Remarks:
☆
:- Settings and modification of special parameters may be performed only after RXPE
assesses the site conditions, otherwise unforeseen consequences may occur.
Chart or text that explains parameter functions.
3.3 Parameter List
3.3.1 Speed Control Parameters
Pa
ra
m
ete
r
N
am
e
Fu
n
ctio
n
al
D
esc
rip
tio
n
Uni
t
S
et
R
an
ge
Fa
cto
ry
S
ettin
gs
S
et
D
u
rin
g
O
p
er
atio
n
Co
n
tr
ol
A
u
th
or
ity
Re
m
ar
k
s
Acceleration 1
The set time of MVC to rise from
minimum frequency to transition
frequency 1 in speed up process.
S
>0
30
×
T/G
☆
Deceleration 1
The set time of MVC to drop
from transition frequency 1 to
minimum frequency in speed
down process.
S
>0
30
×
T/G
☆
Acceleration 2
The set time of MVC to rise from
transition frequency 1 to
transition frequency 2 in speed up
process.
S
>0
30
×
T/G
☆
Deceleration 2
The set time of MVC to drop
from transition frequency 2 to
transition frequency 1 in speed
down process.
S
>0
30
×
T/G
☆