Digital Monitoring Products, Inc. | 7800 Series Installation and Programming Guide
21
Activate Zone 3 Request to Exit
Selecting
YES
activates the zone 3 Request to Exit (REX)
option. Selecting
NO
allows standard zone operation on
zone 3. Default setting is
NO
.
Connect a motion sensing device or a mechanical switch to
zone 3 to provide REX capability to the system. Zone 3 can be
used to activate the strike relay and bypass or activate bypass
only. For zone wiring details, refer to Figure 7.
Activate Strike Relay and Bypass
Wire zone 3 as normally open with a 1K Ohm EOL resistor.
When zone 3 shorts, the onboard Form C relay activates for
the programmed number of seconds. See Zone 3 REX Strike
Time. During this time, the user can open the protected door
to start the programmed zone 2 bypass entry/exit timer. After
the programmed number of seconds, the relay restores the
door to its locked state.
Activate Bypass Only
Wire zone 3 as normally closed with an in-line 1K Ohm resistor.
When zone 3 opens from a normal state, only a bypass occurs:
the onboard relay does not activate.
ACTIVATE ZONE 3
REX?
NO
YES