20
7800 Series Installation and Programming Guide | Digital Monitoring Products, Inc.
Zone 2 Bypass Time
Enter the number of bypass seconds to elapse before the
bypass timer expires. Range is 20-250 seconds. Press any
select area to clear the keypad display and enter the number
of seconds. Default is
40
seconds.
Relock on Zone 2 Change
Select
NO
(default) to leave the relay on when Zone 2 changes
to an open or short condition during bypass. Select
YES
to
turn the relay off when Zone 2 changes to open or short
during bypass.
ZONE 2 BYPASS
TIME:
40
System Armed
TODAY
WEDNESDAY
82
98 77
CURRENT
HI LO
85 68
HI LO
98 77
Panic
Chime
Reset
Favorites
ARMED
5 Second
Strike
40-Second Zone 2 Bypass
entry/exit timer.
10 seconds before
the bypass time expires,
the device beeps if
the door is still open.
End of
timer.
40
Seconds
A zone open/short is
indicated if the door
remains open.
Figure 11: Zone 2 Bypass Timeline
RELOCK ON ZONE 2
CHANGE?
NO
YES