Web Power Switch
Pro
13
Setup Page
The
Setup
page allows the admin to configure:
Controller and Outlet Names
Use the controller name field to assign a name to the Pro.
An example is
Rack 4 PDU.
. The Controller Name will appear on top of
all pages. Assign a separate name to each outlet, such as
DSL Router
1
or
Email Server
to aid identification. Check the
Confirm
box to the
right of the outlet name if you would like a pop-up window to appear
before switching critical outlets.
Power-On Sequence Delay
When a time value is entered in the
All ON Sequence Delay
field,
the Pro will pause for a period of time before switching each outlet
on in sequence. This delay helps prevent power surges and blown
circuit breakers which can occur when multiple devices are switched
on simultaneously. A delay of 60 seconds is suggested for server
applications.
You may also enter a screen refresh delay in this section. If
Enable
screen refresh
is checked, and a delay value is entered, your browser
should periodically update the status screen.
Wrong Password Lockout
After three failed login attempts, the Pro can disable access for a
selected period of time.
Power Loss Recovery Modes
The power loss recovery mode setting has a very important setting that
determines operation after a power failure:
1. Turn all outlets off (all systems will be switched off until
manually turned on later, possibly by a script).
2. You can automatically turn all outlets on using the sequence
delay timer described above.
3. You can return to the same outlet settings that were used prior
to the power loss. ie. 1 On, 2 Off, etc. The ON Sequency delay
timer is used here as well.
Note: If you have written a power-on script, the recovery mode takes
effect before script execution begins. Scripts start after self-test,
approximately 30 seconds after power-up.