background image

 

6.

 

MAIN FUNCTIONS 

6.1

 

TO SET THE CURRENT TIME AND DAY (ONLY FOR INSTRUMENTS 

WITH RTC) 

When the instrument is switched on, it’s necessary to program the time and day. 

1.

 

Enter the Pr1 programming menu, by pushing the SET + 

keys for 3s. 

2.

 

The rtc parameter is displayed. Push the SET key to enter the real time clock menu. 

3.

 

The Hur (hour) parameter is displayed. 

4.

 

Push the SET and set current hour by the UP and Down keys, then push SET to confirm 

the value.. 

5.

 

Repeat the  same operations on the Min (minutes) and dAy (day) parameters. 

To exit: Push SET+UP keys or wait for 15 sec without pushing any keys. 

6.2

 

HOW TO SEE THE SET POINT 

 

1.

 

Push and immediately release the SET key: the display will show the Set 

point value; 

2.

 

Push and immediately release the SET key or wait for 5 seconds to  

display the probe value again. 

6.3

 

HOW TO CHANGE THE SET POINT 

1.

 

Push the SET key for more than 2 seconds to change the Set point value; 

2.

 

The value of the set point will be displayed and the “°C” or “°F” LED starts blinking; 

3.

 

To change the Set value push the 

or 

n

 arrows within 10s. 

4.

 

To memorise the new set point value push the SET key again or wait 10s. 

6.4

 

HOW TO START A MANUAL DEFROST 

 

Push the DEF key for more than 2 seconds and a manual defrost will start. 

6.5

 

HOW TO CHANGE A PARAMETER VALUE 

To change the parameter’s value operate as follows:  

1.

 

Enter the Programming mode by pressing the Set + 

n

 keys for 3s (the “°C” or “°F” LED starts 

blinking). 

2.

 

Select the required parameter. Press the “SET” key to display its value 

3.

 

Use “UP” or “DOWN” to change its value. 

4.

 

Press “SET” to store the new value and move to the following parameter. 

To exit: Press SET + UP or wait 15s without pressing a key. 

NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.6

 

THE HIDDEN MENU 

The hidden menu Includes all the parameters of the instrument. 

6.6.1  HOW TO ENTER THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing the Set + 

n

 keys for 3s (the “°C” or “°F” LED starts 

blinking). 

2.

 

Released the keys, then push again the Set+

n

  keys for more than 7s. The Pr2 label will be 

displayed immediately followed from the HY parameter.  

NOW YOU ARE IN THE HIDDEN MENU. 

3.

 

Select the required parameter. 

4.

 

Press the “SET” key to display its value 

5.

 

Use 

or 

n

 to change its value. 

6.

 

Press “SET” to store the new value and move to the following parameter. 

To exit: Press SET + 

or wait 15s without pressing a key. 

NOTE1: if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep the keys 

pushed till the Pr2 message is displayed.  

NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.6.2  HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user 

level) by pressing “SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is on. 

6.7

 

HOW TO LOCK THE KEYBOARD 

1. 

 

Keep pressed for more than 3 s the UP +  DOWN keys. 

2. 

 

The “POF” message will be displayed and the keyboard will be locked. At this point it will be 

possible only to see the set point or the MAX o Min temperature stored 

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed. 

6.8

 

TO UNLOCK THE KEYBOARD 

Keep pressed together for more than 3s the 

and 

n

  keys, till the “Pon”  message will be 

displayed. 

6.9

 

THE CONTINUOUS CYCLE 

When defrost is not in progress, it can be activated by holding the “

o

” key pressed for about 3 

seconds. The compressor operates to maintain the “ccS” set point for the time set through the “CCt” 

parameter. The cycle can be terminated before the end of the set time using the same activation key 

o

” for 3 seconds. 

 

6.10

 

THE ON/OFF FUNCTION 

 

 

With “onF = oFF”, pushing the ON/OFF key, the instrument is switched off. The “OFF” 

message is displayed. In this configuration, the regulation is disabled.  

To switch the instrument on, push again the ON/OFF key. 

 

WARNING: Loads connected to the normally closed contacts of the relays are always supplied 

and under voltage, even if the instrument is in stand by mode.  

7.

 

PARAMETERS 

rtc  Real time clock menu (only for controller with RTC): to set the time and date and defrost start 

time. 

REGULATION 
Hy Differential
: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN is 

Set Point +  differential (Hy). Compressor Cut OUT is when the temperature reaches the set 

point. 

LS  Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point. 

US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum value for set point. 

Ot  Thermostat probe calibration: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of 

the thermostat probe. 

P2P  Evaporator probe presence: n= not present: the defrost stops by time; y= present: the defrost 

stops by temperature. 

OE Evaporator probe calibration: (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of 

the evaporator probe. 

P3P  Third probe presence (P3): n= not present:, the terminals 13-14 operate as digital input.; y= 

present:, the terminals 13-14  operate as third probe. 

O3 Third probe calibration  (P3): (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of the 

third probe. 

OdS Outputs activation delay at start up: (0÷255min) This function is enabled at the initial start up 

of the instrument and inhibits any output activation for the period of time set in the parameter.  

AC  Anti-short cycle delay: (0÷50 min) minimum interval between the compressor stop and the 

following restart. 

rtr  Percentage of the second and first probe for regulation (0÷100; 100 = P1, 0 = P2 ): it allows 

to set the regulation according to the percentage of the first and second probe,  as for the 

following formula (rtr(P1-P2)/100 + P2). 

CCt Compressor ON time during continuous  cycle: (0.0÷24.0h; res. 10min) Allows to set the 

length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be 

used, for instance, when the room is filled with new products. 

CCS Set point for continuous cycle: (-50÷150°C) it sets the set point used during the continuous 

cycle. 

COn Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is 

active in case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With COF=0 compressor is always active. 

DISPLAY 
CF Temperature measurement unit:  
  °C=Celsius;  °F=Fahrenheit. WARNING: When the 

measurement unit is changed the SET point and the values  of the parameters Hy, LS, US, Ot, 

ALU and ALL have to be checked and modified if necessary). 

rES  Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display. 

Lod  Instrument display: (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by the 

instrument: P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe(only for model with 

this option enabled); P4 = NOT SET IT, SET = set point;  dtr = percentage of visualization. 

rEd  X- REP display (optional): (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by X- 

REP: P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe(only for model with this 

option enabled); P4 = NOT SET IT, SET = set point;  dtr = percentage of visualization. 

dLy  Display delay: (0 ÷20.0m; resul. 10s) when the temperature increases, the display is updated of 

1 °C/1°F after this time. 

dtr  Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 = 

P1, 0 = P2 ): if Lod = dtr it allows to set the visualization according to the percentage of the first 

and second probe, as for the following formula (dtr(P1-P2)/100 + P2). 

DEFROST 
EdF  Defrost mode (only for controller with RTC):
    

 

rtc  =  Real Time Clock mode. Defrost time follows Ld1÷Ld6  parameters on workdays and 

Sd1÷Sd6 on holidays. 

in = interval mode. The defrost starts when the time “Idf” is expired. 

tdF   Defrost type: EL = electrical heater; in = hot gas 

dFP  Probe selection for defrost termination: nP  = no probe; P1  =thermostat probe; P2 = 

evaporator probe; P3 =configurable probe; P4 = NOT SET IT. 

dtE  Defrost termination temperature: (-50÷50 °C/  

-58÷122°F) (Enabled only when EdF=Pb) sets the temperature measured by the evaporator 

probe, which causes the end of defrost. 

IdF   Interval between defrost cycles: (0÷120h) Determines the time interval between the beginning 

of two defrost cycles. 

MdF  (Maximum) length for defrost: (0÷255min) When P2P = n, (not evaporator probe: timed 

defrost) it sets the defrost duration, when P2P = y (defrost end based on temperature) it sets the 

maximum length for defrost. 

dSd Start defrost delay: ( 0÷99min) This is useful when different defrost start times are necessary to 

avoid overloading the plant.  

dFd  Temperature displayed during defrost: (rt = real temperature; it = temperature at defrost start; 

SEt = set point; dEF = “dEF” label) 

dAd MAX display delay after defrost: (0÷255min). Sets the maximum time between the end of 

defrost and the restarting of the real room temperature display. 

Fdt  Drip time: (0

÷

120 min) time interval between reaching defrost termination temperature and the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water 

drops that might have formed due to defrost. 

dPo  First defrost after start-up: (y = immediately; n = after the IdF time) 

dAF  Defrost delay after continuous cycle: (0

÷

23.5h) time interval between the end of the fast 

freezing cycle and the following defrost related to it. 

FANS 
FnC Fans operating mode
C-n= runs with the compressor, OFF during defrost;  

o-n = continuous mode, OFF during defrost;  

C-Y = runs with the compressor, ON during defrost;  

o-Y = continuous mode, ON during defrost;  

Fnd Fans delay after defrost: (0÷255min) Interval between end of defrost and evaporator fans start. 

Fct  Temperature differential avoiding short cycles of fans (0÷59°C; Fct=0 function disabled). If 

the difference of temperature between the evaporator and the room probes is more than the 

value of the Fct parameter, the fans are switched on. 

FSt   Fans stop temperature: (-50÷50°C/122°F) setting of temperature, detected by evaporator 

probe, above which fans are always OFF. 

1592027350 XW60LS RTC GB r1.0 18.03.2015 

XW60LS 

2/5 

Summary of Contents for XW60LS

Page 1: ...in real time depending on the hours set in the parameters Ld1 Ld6 on workdays and in Sd1 Sd6 in holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTROL OF EVAPOR...

Page 2: ...P Third probe presence P3 n not present the terminals 13 14 operate as digital input y present the terminals 13 14 operate as third probe O3 Third probe calibration P3 12 0 12 0 C 120 120 F allows to adjust possible offset of the third probe OdS Outputs activation delay at start up 0 255min This function is enabled at the initial start up of the instrument and inhibits any output activation for th...

Page 3: ...alue Not Used TO SET ENERGY SAVING TIMES ONLY FOR MODELS WITH RTC ILE Energy Saving cycle start during workdays 0 23h 50 min During the Energy Saving cycle the set point is increased by the value in HES so that the operation set point is SET HES dLE Energy Saving cycle length during workdays 0 24h 00 min Sets the duration of the Energy Saving cycle on workdays ISE Energy Saving cycle start on holi...

Page 4: ...re It depends on the Ac2 parameter LA2 Condenser low temperature It depends on the bLL parameter Message Cause Outputs dA Door open Compressor and fans restarts EA External alarm Output unchanged CA Serious external alarm i1F bAL All outputs OFF PA Pressure switch alarm i1F PAL All outputs OFF rtc Real time clock alarm Alarm output ON Other outputs unchanged Defrosts according to par IdF Set real ...

Page 5: ...ferential for temperat alarm recovery 0 1 C 25 5 C 1 F 45 F 2 0 Pr2 ALd Temperature alarm delay 0 255 min 15 Pr2 dAO Delay of temperature alarm at start up 0 23h e 50 1 3 Pr2 AP2 Probe for temperat alarm of condenser nP P1 P2 P3 P4 P4 Pr2 AL2 Condenser for low temperat alarm 55 150 C 67 302 F 40 Pr2 AU2 Condenser for high temperat alarm 55 150 C 67 302 F 110 Pr2 AH2 Differ for condenser temp alar ...

Reviews: