17.
DEFAULT SETTING VALUES
Label
Name
Range
°C/°F Level
Set Set point
LS÷US
-5.0
- - -
rtc* Real time clock menu
-
-
Pr1
Hy Differential
0,1
÷
25.5°C/ 1
÷
255°F
2.0
Pr1
LS Minimum set point
-50°C
÷
SET/-58°F
÷
SET
-50.0
Pr2
US Maximum set point
SET
÷
110°C/ SET
÷
230°F
110
Pr2
Ot Thermostat probe calibration
-12
÷
12°C /-120
÷
120°F
0.0
Pr1
P2P Evaporator probe presence
n=not present; Y=pres.
Y
Pr1
OE Evaporator probe calibration
-12
÷
12°C /-120
÷
120°F
0.0
Pr2
P3P Third probe presence
n=not present; Y=pres.
n
Pr2
O3 Third probe calibration
-12
÷
12°C /-120
÷
120°F
0
Pr2
OdS Outputs delay at start up
0÷255 min
0
Pr2
AC Anti-short cycle delay
0
÷
50 min
1
Pr1
rtr P1-P2 percentage for regulation
0 ÷ 100 (100=P1 , 0=P2)
100
Pr2
CCt Continuous cycle duration
0.0÷24.0h
0.0
Pr2
CCS Set point for continuous cycle
(-55.0÷150,0°C) (-67÷302°F)
-5
Pr2
COn Compressor ON time with faulty probe
0
÷
255 min
15
Pr2
COF Compressor OFF time with faulty probe 0
÷
255 min
30
Pr2
CF Temperature measurement unit
°C
÷
°F
°C
Pr2
rES Resolution
in=integer; dE= dec.point
dE
Pr1
Lod Probe displayed
P1;P2
P1
Pr2
rEd
2
X-REP display
P1 – P2 – P3 – P4 – SEt – dtr
P1
Pr2
dLy Display temperature delay
0 ÷ 20.0 min (10 sec.)
0.0
Pr2
dtr P1-P2 percentage for display
1 ÷ 99
50
Pr2
EdF* Kind of interval for defrost
rtc ÷in
in
Pr2
tdF Defrost type
EL=el. heater; in= hot gas
EL
Pr1
dFP Probe selection for defrost termination
nP; P1; P2; P3; P4
P2
Pr2
dtE Defrost termination temperature
-50
÷
50 °C
8
Pr1
IdF Interval between defrost cycles
1
÷
120 ore
6
Pr1
MdF (Maximum) length for defrost
0
÷
255 min
30
Pr1
dSd Start defrost delay
0÷99min
0
Pr2
dFd Displaying during defrost
rt, it, SEt, DEF
it
Pr2
dAd MAX display delay after defrost
0 ÷ 255 min
30
Pr2
Fdt Draining time
0÷120 min
0
Pr2
dPo First defrost after start-up
n=after IdF; y=immed.
n
Pr2
dAF Defrost delay after fast freezing
0 ÷ 23h e 50’
0.0
Pr2
Fnc Fan operating mode
C-n, o-n, C-y, o-Y
o-n
Pr1
Fnd Fan delay after defrost
0÷255min
10
Pr1
Fct Differential of temperature for forced
activation of fans
0÷50°C
10
Pr2
FSt Fan stop temperature
-50÷50°C/-58÷122°F
2
Pr1
Fon Fan on time with compressor off
0÷15 (min.)
0
Pr2
FoF Fan off time with compressor off
0÷15 (min.)
0
Pr2
FAP Probe selection for fan management
nP; P1; P2; P3; P4
P2
Pr2
ALP Alarm probe selection
nP; P1; P2; P3; P4
P1
Pr2
ALc Temperat. alarms configuration
rE= related to set;
Ab = absolute
Ab
Pr2
ALU MAXIMUM temperature alarm
Set
÷
110.0°C; Set÷230°F
110,0
Pr1
ALL Minimum temperature alarm
-50.0°C
÷
Set/ -58°F
÷
Set
-50,0
Pr1
AFH Differential for temperat. alarm recovery
(0,1°C÷25,5°C) (1°F÷45°F)
2,0
Pr2
ALd Temperature alarm delay
0
÷
255 min
15
Pr2
dAO Delay of temperature alarm at start up
0
÷
23h e 50’
1,3
Pr2
AP2 Probe for temperat. alarm of condenser
nP; P1; P2; P3; P4
P4
Pr2
AL2 Condenser for low temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
-40
Pr2
AU2 Condenser for high temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
110
Pr2
AH2 Differ. for condenser temp. alar. recovery [0,1°C ÷ 25,5°C] [1°F ÷ 45°F]
5
Pr2
Ad2 Condenser temperature alarm delay
0 ÷ 254 (min.) , 255=nU
15
Pr2
dA2 Delay of cond. temper. alarm at start up
0.0 ÷ 23h 50’
1,3
Pr2
bLL
Compr. off for condenser low temperature
alarm
n(0) - Y(1)
n
Pr2
AoP Alarm relay polarity (oA3=ALr)
oP; cL
cL
Pr2
i1P Digital input polarity (13-14)
oP=opening;CL=closing
cL
Pr1
i1F Digital input 1 configuration (13-14)
EAL, bAL, PAL, dor; dEF; Htr,
AUS
dor
Pr1
did Digital input alarm delay (13-14)
0÷255min
15
Pr1
nPS Number of activation of pressure switch
0 ÷15
15
Pr2
odc Compress and fan status when open door
no; Fan; CPr; F_C
F-c
Pr2
rrd Regulation restart with door open alarm
n – Y
y
Pr2
HES Differential for Energy Saving
(-30°C÷30°C) (-54°F÷54°F)
0
Pr2
Hur* Current hour
0 ÷ 23
-
rtc
Min* Current minute
0 ÷ 59
-
rtc
dAY* Current day
Sun ÷ SAt
-
rtc
Hd1* First weekly holiday
Sun÷ SAt – nu
nu
rtc
Hd2* Second weekly holiday
Sun÷ SAt – nu
nu
rtc
ILE* Energy Saving cycle start during
workdays
0 ÷ 23h 50 min.
0
rtc
dLE* Energy Saving cycle length during
workdays
0 ÷ 24h 00 min.
0
rtc
ISE* Energy Saving cycle start on holidays
0 ÷ 23h 50 min.
0
rtc
dSE* Energy Saving cycle length on holidays
0 ÷ 24h 00 min.
0
rtc
Ld1* 1
st
workdays defrost start
0 ÷ 23h 50 min. - nu
6.0
rtc
Ld2* 2
nd
workdays defrost start
0 ÷ 23h 50 min. - nu
13.0
rtc
Ld3* 3
rd
workdays defrost start
0 ÷ 23h 50 min. - nu
21.0
rtc
Ld4* 4
th
workdays defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Ld5* 5
th
workdays defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Ld6* 6
th
workdays defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Sd1* 1
st
holiday defrost start
0 ÷ 23h 50 min. - nu
6.0
rtc
Label
Name
Range
°C/°F Level
Sd2* 2
nd
holiday defrost start
0 ÷ 23h 50 min. - nu
13.0
rtc
Sd3* 3
rd
holiday defrost start
0 ÷ 23h 50 min. - nu
21.0
rtc
Sd4* 4
th
holiday defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Sd5* 5
th
holiday defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Sd6* 6
th
holiday defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Adr Serial address
1÷247
1
Pr2
PbC Kind of probe
Ptc; ntc
ntc
Pr2
onF on/off key enabling
nu, oFF; ES
oFF
Pr2
dP1 Room probe display
--
-
Pr2
dP2 Evaporator probe display
--
-
Pr2
dP3 Third probe display
--
-
Pr2
rSE Real set
actual set
-
Pr2
rEL Software release
--
1.8
Pr2
Ptb Map code
--
Pr2
* Only for model with real time clock
2
Only for XW60LS with X-REP output
1592027350 XW60LS RTC GB r1.0 18.03.2015
XW60LS
5/5