DEFAULT SETTING VALUES 

Label 

Name 

Range 

°C/°F  Level 

Set  Set point 

LS÷US 

-5.0 

- - - 

rtc*  Real time clock menu 

Pr1 

Hy  Differential 

0,1

÷

25.5°C/ 1

÷

 255°F 

2.0 

Pr1 

LS  Minimum set point 

-50°C

÷

SET/-58°F

÷

SET 

-50.0 

Pr2 

US  Maximum set point 

SET

÷

110°C/ SET 

÷

 230°F 

110 

Pr2 

Ot  Thermostat probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 

Pr1 

P2P  Evaporator probe presence 

n=not present; Y=pres. 

Pr1 

OE  Evaporator probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 

Pr2 

P3P  Third probe presence 

n=not present; Y=pres. 

Pr2 

O3  Third probe calibration 

-12

÷

12°C /-120

÷

120°F 

Pr2 

OdS  Outputs delay at start up 

0÷255 min 

Pr2 

AC  Anti-short cycle delay 

÷

 50 min 

Pr1 

rtr  P1-P2 percentage for regulation 

 0 ÷ 100 (100=P1 , 0=P2) 

100 

Pr2 

CCt  Continuous cycle duration 

0.0÷24.0h 

0.0 

Pr2 

CCS  Set point for continuous cycle 

 (-55.0÷150,0°C) (-67÷302°F) 

-5 

Pr2 

COn  Compressor ON time with faulty probe 

÷

 255 min 

15 

Pr2 

COF  Compressor OFF time with faulty probe  0 

÷

 255 min 

30 

Pr2 

CF  Temperature measurement unit 

°C 

÷

 °F 

°C 

Pr2 

rES  Resolution 

in=integer; dE= dec.point 

dE 

Pr1 

Lod  Probe displayed 

P1;P2 

P1 

Pr2 

rEd

X-REP display 

P1 – P2 – P3 – P4 – SEt – dtr 

P1 

Pr2 

dLy  Display temperature delay   

0 ÷ 20.0 min  (10 sec.)  

0.0 

Pr2 

dtr  P1-P2 percentage for display 

 1 ÷ 99 

50 

Pr2 

EdF* Kind of interval for defrost 

rtc ÷in 

in 

Pr2 

tdF  Defrost type 

EL=el. heater;  in= hot gas 

EL 

Pr1 

dFP  Probe selection for defrost termination 

nP; P1; P2; P3; P4 

P2 

Pr2 

dtE  Defrost termination temperature 

-50 

÷

 50 °C 

Pr1 

IdF  Interval between defrost cycles 

÷

 120 ore 

Pr1 

MdF  (Maximum) length for defrost 

÷

 255 min 

30 

Pr1 

dSd  Start defrost delay 

0÷99min 

Pr2 

dFd  Displaying during defrost 

rt, it, SEt, DEF 

it 

Pr2 

dAd  MAX display delay after defrost 

0 ÷ 255 min 

30 

Pr2 

Fdt  Draining time 

0÷120 min 

Pr2 

dPo  First defrost after start-up 

n=after IdF; y=immed. 

Pr2 

dAF  Defrost delay after fast freezing 

0 ÷ 23h e 50’ 

0.0 

Pr2 

Fnc  Fan operating mode 

C-n, o-n, C-y, o-Y 

o-n 

Pr1 

Fnd  Fan delay after defrost 

0÷255min 

10 

Pr1 

Fct  Differential of temperature for forced 

activation of fans 

0÷50°C 

10 

Pr2 

FSt  Fan stop temperature 

-50÷50°C/-58÷122°F 

Pr1 

Fon  Fan on time with compressor off 

0÷15 (min.) 

Pr2 

FoF  Fan off time with compressor off 

0÷15 (min.) 

Pr2 

FAP  Probe selection for fan management 

nP; P1; P2; P3; P4 

P2 

Pr2 

ALP  Alarm probe selection  

nP; P1; P2; P3; P4 

P1 

Pr2 

ALc  Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab 

Pr2 

ALU  MAXIMUM temperature alarm 

Set

÷

110.0°C; Set÷230°F 

110,0 

Pr1 

ALL  Minimum temperature alarm 

-50.0°C

÷

Set/ -58°F

÷

Set 

-50,0 

Pr1 

AFH  Differential for temperat. alarm recovery 

(0,1°C÷25,5°C) (1°F÷45°F) 

2,0 

Pr2 

ALd  Temperature alarm delay 

÷

 255 min 

15 

Pr2 

dAO  Delay of temperature alarm at start up 

÷

 23h e 50’ 

1,3 

Pr2 

AP2  Probe for temperat. alarm of condenser 

nP; P1; P2; P3; P4 

P4 

Pr2 

AL2  Condenser for low temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

-40 

Pr2 

AU2  Condenser for high temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

110 

Pr2 

AH2  Differ. for condenser temp. alar. recovery  [0,1°C ÷ 25,5°C]  [1°F ÷ 45°F] 

Pr2 

Ad2  Condenser temperature alarm delay  

 0 ÷ 254 (min.) , 255=nU 

15 

Pr2 

dA2  Delay of cond. temper. alarm at start up 

0.0 ÷ 23h  50’ 

1,3 

Pr2 

bLL 

Compr. off for condenser low temperature 

alarm 

n(0) - Y(1) 

Pr2 

AoP  Alarm relay  polarity  (oA3=ALr) 

oP; cL 

cL 

Pr2 

i1P  Digital input polarity (13-14) 

oP=opening;CL=closing 

cL 

Pr1 

i1F  Digital input 1 configuration (13-14) 

EAL, bAL, PAL, dor; dEF; Htr, 

AUS 

dor 

Pr1 

did  Digital input alarm delay (13-14) 

0÷255min 

15 

Pr1 

nPS  Number of activation of pressure switch 

0 ÷15  

15 

Pr2 

odc  Compress and fan status when open door 

no; Fan; CPr; F_C  

F-c 

Pr2 

rrd  Regulation restart with door open alarm 

n – Y 

Pr2 

HES  Differential for Energy Saving 

 (-30°C÷30°C) (-54°F÷54°F) 

Pr2 

Hur*  Current hour 

0 ÷ 23 

rtc 

Min*  Current minute 

0 ÷ 59 

rtc 

dAY* Current day 

Sun ÷ SAt 

rtc 

Hd1* First weekly holiday 

Sun÷ SAt – nu 

nu 

rtc 

Hd2* Second weekly holiday 

Sun÷ SAt – nu 

nu 

rtc 

ILE*  Energy Saving cycle start during 

workdays 

0 ÷ 23h 50 min. 

rtc 

dLE* Energy Saving cycle length during 

workdays 

0 ÷ 24h 00 min. 

rtc 

ISE*  Energy Saving cycle start on holidays 

0 ÷ 23h 50 min. 

rtc 

dSE* Energy Saving cycle length on holidays 

0 ÷ 24h 00 min. 

rtc 

Ld1*  1

st

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

rtc 

Ld2*  2

nd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

rtc 

Ld3*  3

rd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

rtc 

Ld4*  4

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

0.0 

rtc 

Ld5*  5

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

0.0 

rtc 

Ld6*  6

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

0.0 

rtc 

Sd1*  1

st

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

rtc 

Label 

Name 

Range 

°C/°F  Level 

Sd2*  2

nd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

rtc 

Sd3*  3

rd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

rtc 

Sd4*  4

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

0.0 

rtc 

Sd5*  5

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

0.0 

rtc 

Sd6*  6

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

0.0 

rtc 

Adr  Serial address 

1÷247 

Pr2 

PbC  Kind of probe 

Ptc; ntc 

ntc 

Pr2 

onF  on/off key enabling 

nu, oFF; ES 

oFF 

Pr2 

dP1  Room probe display 

-- 

Pr2 

dP2  Evaporator probe display 

-- 

Pr2 

dP3  Third probe display 

-- 

Pr2 

rSE  Real set 

actual set 

Pr2 

rEL  Software release 

-- 

1.8 

Pr2 

Ptb  Map code 

-- 

  

Pr2 

* Only for model with real time clock 

2

 Only for XW60LS with X-REP output 

 

 

1592027350 XW60LS RTC GB r1.0 18.03.2015 

XW60LS 

5/5 

Summary of Contents for XW60LS

Page 1: ...in real time depending on the hours set in the parameters Ld1 Ld6 on workdays and in Sd1 Sd6 in holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTROL OF EVAPOR...

Page 2: ...P Third probe presence P3 n not present the terminals 13 14 operate as digital input y present the terminals 13 14 operate as third probe O3 Third probe calibration P3 12 0 12 0 C 120 120 F allows to adjust possible offset of the third probe OdS Outputs activation delay at start up 0 255min This function is enabled at the initial start up of the instrument and inhibits any output activation for th...

Page 3: ...alue Not Used TO SET ENERGY SAVING TIMES ONLY FOR MODELS WITH RTC ILE Energy Saving cycle start during workdays 0 23h 50 min During the Energy Saving cycle the set point is increased by the value in HES so that the operation set point is SET HES dLE Energy Saving cycle length during workdays 0 24h 00 min Sets the duration of the Energy Saving cycle on workdays ISE Energy Saving cycle start on holi...

Page 4: ...re It depends on the Ac2 parameter LA2 Condenser low temperature It depends on the bLL parameter Message Cause Outputs dA Door open Compressor and fans restarts EA External alarm Output unchanged CA Serious external alarm i1F bAL All outputs OFF PA Pressure switch alarm i1F PAL All outputs OFF rtc Real time clock alarm Alarm output ON Other outputs unchanged Defrosts according to par IdF Set real ...

Page 5: ...ferential for temperat alarm recovery 0 1 C 25 5 C 1 F 45 F 2 0 Pr2 ALd Temperature alarm delay 0 255 min 15 Pr2 dAO Delay of temperature alarm at start up 0 23h e 50 1 3 Pr2 AP2 Probe for temperat alarm of condenser nP P1 P2 P3 P4 P4 Pr2 AL2 Condenser for low temperat alarm 55 150 C 67 302 F 40 Pr2 AU2 Condenser for high temperat alarm 55 150 C 67 302 F 110 Pr2 AH2 Differ for condenser temp alar ...

Reviews: