background image

 

Fon Fan ON time: (0÷15 min) with Fnc = C_n or C_y, (fan activated in parallel with compressor). it 

sets the evaporator fan ON cycling time when the compressor is off. With Fon =0 and FoF ≠ 0 

the fan are always off, with Fon=0 and FoF =0 the fan are always off. 

FoF Fan OFF time: (0÷15 min) with Fnc = C_n or C_y, (fan activated in parallel with compressor). it 

sets the evaporator fan off cycling time when the compressor is off. With Fon =0 and FoF ≠ 0 the 

fan are always off, with Fon=0 and FoF =0 the fan are always off. 

FAP  Probe selection for fan management: nP = no probe; P1 =thermostat probe; P2 = evaporator 

probe; P3 =configurable probe; P4 = NOT SET IT. 

ALARMS 
ALP  Probe selection for alarm
: nP = no probe, the temperature alarms are disabled; P1 = Probe 1 

(Thermostat probe); P2 = Probe 2 (evaporator probe); P3 = Probe 3 (display probe); P4 = NOT 

SET IT. 

ALC  Temperature alarms configuration: (Ab; rE) 

 

Ab= absolute temperature: alarm temperature is given by the ALL or ALU values.  rE  = 

temperature alarms are referred to the set point. Temperature alarm is enabled when the 

temperature exceeds the “SET+ALU” or “SET-ALL” values. 

ALU  MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

ALL Minimum temperature alarm: (-50.0 ÷ SET °C; -58÷230°F when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

AFH  Differential for temperature alarm/ fan recovery:  (0,1÷25,5°C; 1÷45°F) Intervention 

differential for recovery of temperature alarm. It’s also used for the restart of the fan when the 

FSt temperature is reached  

ALd  Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm 

condition and alarm signalling. 

dAO Exclusion of temperature alarm at start-up: (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 
AP2  Probe selection for temperature alarm of condenser: nP
 = no probe; P1 =thermostat probe; 

P2 = evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug. 

AL2 Low temperature alarm of condenser: (-55÷150°C) when this temperature is reached the LA2 

alarm is signalled, possibly after the Ad2 delay. 

Au2 High temperature alarm of condenser: (-55÷150°C) when this temperature is reached the HA2 

alarm is signalled, possibly after the Ad2 delay. 

AH2 Differential for temperature condenser alarm recovery: (0,1÷25,5°C; 1÷45°F) 

Ad2 Condenser temperature alarm delay: (0÷255 min) time interval between the detection of the 

condenser alarm condition and alarm signalling. 

dA2  Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min) 

bLL  Compressor off with low temperature alarm of condenser: n = no: compressor keeps on 

working; Y = yes, compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum. 

AC2 Compressor off with high temperature alarm of condenser: n = no: compressor keeps on 

working; Y = yes, compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum. 

DIGITAL INPUTS 
i1P  Digital input polarity: oP: 
the digital input is activated by opening the contact; CL: the digital 

input is activated by closing the contact. 

i1F Digital input configuration: EAL= external alarm: “EA” message is displayed; bAL= serious 

alarm “CA” message is displayed. PAL= pressure switch alarm, “CA” message  is displayed; 

dor= door switch function; dEF= activation of a defrost cycle; AUS=not enabled; Htr= kind of 

action inversion (cooling – heating); FAn= not set it; ES= Energy saving; HdF = Holiday defrost 

(enable only with RTC); onF = to switch the controller off. 

did (0

÷

255 min) with i1F= EAL or i1F = bAL digital input alarm delay (13-14): delay between the 

detection of the external alarm condition and its signalling. 

with i1F= dor: door open signalling delay 

with i1F= PAL: time for pressure switch function: time interval to calculate the number of the 

pressure switch activation. 

nPS Pressure switch number: (0 

÷

15) Number of activation of the pressure switch, during the “did” 

interval, before signalling the alarm event (I2F= PAL).  

If the nPS activation in the did time is reached, switch off and on the instrument to restart 

normal regulation. 

odc  Compressor and fan status when open door:  no  = normal; Fan  = Fan OFF; CPr  

Compressor OFF; F_C = Compressor and fan OFF.  

rrd  Outputs restart after doA alarm: no= outputs not affected by the doA alarm;  yES = outputs 

restart with the doA alarm. 

HES Temperature increase during the Energy Saving cycle: 

(-30,0°C

÷

30,0°C) it sets the increasing value of the set point during the Energy Saving cycle.  

TO SET CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC) 
Hur 

Current hour (0 ÷ 23 h) 

Min 

Current minute (0 ÷ 59min) 

dAY  Current day (Sun ÷ SAt) 

Hd1  First weekly holiday (Sun ÷ nu) Set the first day of the week which follows the holiday times. 

Hd2  Second weekly holiday (Sun ÷ nu) Set the second day of the week which follows the holiday 

times. 

N.B.   Hd1,Hd2 can be set also as “nu” value (Not Used).  
TO SET ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC) 
ILE 

Energy Saving cycle start during workdays: (0 ÷ 23h 50 min.) During the Energy Saving 

cycle the set point is increased by the value in HES so that the operation set point is SET + 

HES.  

dLE  Energy Saving cycle length during workdays: (0 ÷ 24h 00 min.) Sets the duration of the 

Energy Saving cycle on workdays.  

ISE 

Energy Saving cycle start on holidays. (0 ÷ 23h 50 min.) 

dSE  Energy Saving cycle length on holidays (0 ÷ 24h 00 min.) 
TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC) 
Ld1÷Ld6 Workday defrost start
 (0 ÷ 23h 50 min.) These parameters set the beginning of the 6 

programmable defrost cycles during workdays. Ex. When Ld2 = 12.4 the second defrost starts at 

12.40 during workdays.  

Sd1÷Sd6 Holiday defrost start  (0 ÷ 23h 50 min.) These parameters set the beginning of the 6 

programmable defrost cycles on holidays. Ex. When Sd2 = 3.4 the second defrost starts at 3.40 

on holidays.  

N.B. :To disable a defrost cycle set it to “nu”(not used). Ex.  If Ld6=nu ;  the sixth defrost 

cycle is disabled 

OTHER 
Adr   Serial address
  (1÷244): Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntc 

NTC probe. 

onF  on/off key enabling: nu = disabled; oFF = enabled; ES = not set it

dP1  Thermostat probe display 

dP2  Evaporator probe display 

dP3  Third probe displayoptional

rSE  Real set point:  it shows the set point used during the energy saving cycle or during the 

continuous cycle. 

rEL  Software release for internal use

Ptb  Parameter table code: readable only

8.

 

DIGITAL INPUT 

The digital input is enabled  with P3P = n. 

8.1

 

GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for “did” time delay before signalling the 

EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 

de-activated. 

8.2

 

SERIOUS ALARM MODE (i1F =  bAL) 

When the digital input is activated, the unit will wait for “did” delay before signalling the “CA” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-

activated. 

8.3

 

PRESSURE SWITCH (i1F = PAL) 

If during the interval time set by “did” parameter, the pressure switch has reached the number of 

activation of  the “nPS” parameter, the “CA” pressure alarm message will be displayed. The 

compressor and the regulation are stopped. When the digital input is ON the compressor is always 

OFF. If the nPS activation in the did time is reached, switch off and on the instrument to restart 

normal regulation. 

8.4

 

DOOR SWITCH INPUT  (i1F = dor) 

It signals the door status and the corresponding relay output status through the “odc” parameter: no = 

normal (any change); Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “did”, the door alarm is enabled, 

the display shows the message “dA” and the regulation restarts is rtr = yES. The alarm stops as 

soon as the external digital input is disabled again. With the door open, the high and low temperature 

alarms are disabled. 

8.5

 

START DEFROST (i1F = dEF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 

restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety time 

is expired. 

8.6

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F =Htr)  

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

8.7

 

ENERGY SAVING (i1F = ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES 

(parameter) sum. This function is enabled until the digital input is activated. 

8.8

 

HOLIDAY DEFROST (i1F = HDF) –ONLY FOR MODELS WITH RTC 

This function enabled the holiday defrost setting. 

8.9

 

ON OFF FUNCTION (i1F = onF)  

To switch the controller on and off. 

8.10

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “i1P parameter. 

i1P or i2P =CL: the input is activated by closing the contact. 

i1P or i2P=OP: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector, allows by means of the external 

TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitoring system ModBUS-RTU 

compatible  such as the  X-WEB500/3000/300. 

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the HOY KEY 
connector. The X-REP output 

EXCLUDES 

 the serial connection.

 

 

To connect the X-REP to the 
instrument the following connectors 
must be used CAB-51F(1m), CAB-
52F(2m), CAB-55F(5m), 

11.

 

INSTALLATION AND MOUNTING 

The controller XW60LS, shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two 

screws 

 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). 

The temperature range allowed for correct operation is 0 -  60 °C. Avoid places subject to strong 

vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. 

Let the air circulate by the cooling holes. 

 

1592027350 XW60LS RTC GB r1.0 18.03.2015 

XW60LS 

3/5 

Summary of Contents for XW60LS

Page 1: ...in real time depending on the hours set in the parameters Ld1 Ld6 on workdays and in Sd1 Sd6 in holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTROL OF EVAPOR...

Page 2: ...P Third probe presence P3 n not present the terminals 13 14 operate as digital input y present the terminals 13 14 operate as third probe O3 Third probe calibration P3 12 0 12 0 C 120 120 F allows to adjust possible offset of the third probe OdS Outputs activation delay at start up 0 255min This function is enabled at the initial start up of the instrument and inhibits any output activation for th...

Page 3: ...alue Not Used TO SET ENERGY SAVING TIMES ONLY FOR MODELS WITH RTC ILE Energy Saving cycle start during workdays 0 23h 50 min During the Energy Saving cycle the set point is increased by the value in HES so that the operation set point is SET HES dLE Energy Saving cycle length during workdays 0 24h 00 min Sets the duration of the Energy Saving cycle on workdays ISE Energy Saving cycle start on holi...

Page 4: ...re It depends on the Ac2 parameter LA2 Condenser low temperature It depends on the bLL parameter Message Cause Outputs dA Door open Compressor and fans restarts EA External alarm Output unchanged CA Serious external alarm i1F bAL All outputs OFF PA Pressure switch alarm i1F PAL All outputs OFF rtc Real time clock alarm Alarm output ON Other outputs unchanged Defrosts according to par IdF Set real ...

Page 5: ...ferential for temperat alarm recovery 0 1 C 25 5 C 1 F 45 F 2 0 Pr2 ALd Temperature alarm delay 0 255 min 15 Pr2 dAO Delay of temperature alarm at start up 0 23h e 50 1 3 Pr2 AP2 Probe for temperat alarm of condenser nP P1 P2 P3 P4 P4 Pr2 AL2 Condenser for low temperat alarm 55 150 C 67 302 F 40 Pr2 AU2 Condenser for high temperat alarm 55 150 C 67 302 F 110 Pr2 AH2 Differ for condenser temp alar ...