Installing and Operating Instructions 

PRELIMINARY

 

 

MANUAL  RNC 2007 053  PRELIMINARY T66 + XW60K.doc 

T66 – XW60K 

3/4 

ALL   Minimum  temperature alarm

: (-50.0 ÷ SET°C; -58÷230°F when this 

temperature is reached  the alarm is enabled, after the “ALd” delay time. 

ALd    Temperature alarm delay

: (0÷255 min) time interval between the detection 

of an alarm condition and alarm signalling. 

dAO   Exclusion of temperature alarm at startup

: (from 0.0 min to 23.5h) time 

interval between the detection of the temperature alarm condition after 
instrument power on and alarm signalling. 

 

CONFIGURABLE RELAY 
oA2    Relay 5-6 configuration: 

 

ALr

: alarm; 

LHt = 

light; 

onF

: always on; 

dEF: 

do not select it!.

; FAn: 

do not select it!. 

 

DIGITAL INPUT: depends on the jumper present on the keyboard. 
With jumper inserted (digital input disabled) set i1P = oP. 
i1P  Digital input polarity: oP: 

the digital input is activated by opening the 

contact; 

CL: 

the digital input is activated by closing the contact.

 

i1F   Digital input configuration: EAL 

= external alarm: “EA” message is 

displayed; 

bAL 

= serious alarm “CA” message is displayed. 

PAL 

pressure switch alarm, “CA” message is displayed; 

dor

 = door switch 

function; 

dEF

 = activation of a defrost cycle; 

LHt 

=not enabled; 

Htr 

= kind 

of action inversion (cooling – heating).

 

did

:

  

(0

÷

255 min) 

with

 

i1F= EAL or i1F = bAL digital input alarm delay:

 delay 

between the detection of the external alarm condition and its signalling. 

with

 

i1F= dor: door open signalling delay. with i1F = PAL: time for 

pressure switch function: 

time interval to calculate the number of the 

pressure switch activation. 

Lio = door switch turning light on. 

            with 

Lio

 = y light relay is  switched on when the door is open (i1F=dor, oA2 

= Lht) 

             with 

Lio

 = n the status of the door switch doesn’t influence the status of 

the light relay. 

nPS   Pressure switch number:

 (0 

÷

15) Number of activation of the pressure 

switch, during the “

did

” interval, before signalling the alarm event (I2F= 

PAL). 

If the nPS activation in the did time is reached, switch off and on 

the instrument to restart normal regulation.

 

odc  Compressor status when open door:

   

no,

 

Fan

 = normal; 

CPr, F_C

 = 

Compressor OFF  

OTHER 
PbC   Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC probe, 

ntC = 

NTC probe. 

dP1  First probe display 
dP2  Second probe display 
rEL Software 

release 

for internal use. 

Ptb 

Parameter table code:

 readable only. 

 

8.  DIGITAL INPUT:  

******Digital input is available only if the jumper, present in the keyboard,  is 
not inserted.***** 
If the jumper is inserted, please set i1P = op 

The free contact digital input is programmable in five different configurations by 
the “

i1F

” parameter. 

8.1  DOOR SWITCH INPUT  (I1F = DOR) 

It signals the door status and the corresponding relay output status through the 

odc

” parameter: 

no,

 

Fan

 = normal (any change); 

CPr, F_C

 = Compressor OFF; 

Since the door is opened, after the delay time set through parameter “

did

”, the 

door alarm is enabled, the display shows the message “

dA

” and 

the regulation 

restarts

. The alarm stops as soon as the external digital input is disabled again. 

With the door open, the high and low temperature alarms are disabled. 

8.2  GENERIC ALARM (I1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before 

signalling the “

EAL

” alarm message. The outputs status don’t change. The alarm 

stops just after the digital input is de-activated. 

8.3  SERIOUS ALARM MODE (I1F = BAL) 

When the digital input is activated, the unit will wait for “

did

” delay before 

signalling the “

CA

” alarm message. The relay outputs are switched OFF. The 

alarm will stop as soon as the digital input is de-activated. 

8.4  PRESSURE SWITCH (I1F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached 

the number of activation of  the “

nPS

” parameter, the “

CA

” pressure alarm 

message will be displayed. The compressor and the regulation are stopped. When 
the digital input is ON the compressor is always OFF. 

If the nPS activation in the did time is reached, switch off and on the 
instrument to restart normal regulation. 

8.5  START DEFROST (I1F = DFR) 

It starts a defrost if there are the right conditions. After the defrost is finished, the 
normal regulation will restart only if the digital input is disabled otherwise the 
instrument will wait until the “MdF” safety time is expired. 

8.6  INVERSION OF  THE KIND OF ACTION: HEATING-
COOLING (I1F = HTR) 

This function allows to invert the regulation of the controller: from cooling to 
heating and viceversa. 

8.7  DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameter. If the digital input is not 

used (jumper inserted) set i1P = oP. 

i1P=CL

: the input is activated by closing the contact.

 

i1P=OP

: the input is activated by opening the contact 

 

9.  INSTALLATION AND MOUNTING 

9.1  T66 SHALL BE MOUNTED ON VERTICAL PANEL, CUT 
OUT 

 

 

10. ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a 
cross section up to 2,5 mm

2

. Before connecting cables make sure the power 

supply complies with the instrument’s requirements. Separate the probe cables 
from the power supply cables, from the outputs and the power connections. Do not 
exceed the maximum current allowed on each relay, in case of heavier loads use 
a suitable external relay. 

10.1 PROBE 

CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to 
casual liquid infiltration. It is recommended to place the thermostat probe away 
from air streams to correctly measure the average room temperature. Place the 
defrost termination probe among the evaporator fins in the coldest place, where 
most ice is formed, far from heaters or from the warmest place during defrost, to 
prevent premature defrost termination. 

11.  HOW TO USE THE HOT KEY  

11.1  HOW TO PROGRAM A HOT KEY FROM THE 
INSTRUMENT (UPLOAD) 

1. 

Program one controller with the front keypad. 

2. 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message appears followed a by flashing 

“End”

 

3. Push 

SET”

 key and the 

End

 will stop flashing. 

4. Turn 

OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push 

again 

o

 key if you want to restart the upload again or remove the “

Hot key

” to 

abort the operation. 

11.2  HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 
(DOWNLOAD) 

1. 

Turn OFF the instrument. 

2. 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn 

the Controller ON. 

3. Automatically 

the 

parameter list of the 

“Hot Key”

 is downloaded into the 

Controller memory, the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.  After 10 seconds the instrument will restart working with the new 

parameters.  

5. Remove 

the 

“Hot Key”.

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the 

unit off and then on if you want to restart the download again or remove the “

Hot 

key

” to abort the operation. 

 

12. ALARM SIGNALS 

Message 

Cause 

Outputs 

“P1” 
 

Room probe  failure 

Compressor output according 
to par. “Con” and “COF” 

“P2” 

Evaporator probe  failure 

Defrost end is timed 

“HA” Maximum 

temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

“dA” 

Door open 

Regulation restarts  

“EA”  

External alarm 

Output unchanged. 

“CA”  

Serious external alarm (i1F=bAL) 

All outputs OFF. 

“CA” 

Pressure switch alarm (i1F=PAL) 

All outputs OFF 

12.1  ALARM RECOVERY  

Probe alarms “

P1

” and “

P2

” start some seconds after the fault in the related probe; 

they automatically stop some seconds after the probe restarts normal operation. 
Check connections before replacing the probe. 
Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat 

temperature returns to normal values and when defrost starts. 
Alarms 

“EA”

 and 

“CA” 

(with i1F=bAL)

 

recover as soon as the digital input is 

disabled. 
Alarm “

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument. 

13. TECHNICAL DATA 

T66 keyboard 
Housing: 

self extinguishing ABS.

 

Case: 

facia 38x185 mm; depth 23mm 

Mounting :

  

 

panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

 Distance 

between 

the holes 165mm 

Protection: 

IP20.

 

Frontal protection:

 IP65 with frontal gasket mod RG-L. (optional) 

Summary of Contents for XW60K

Page 1: ...ordt aangeraden ook op de voeding van het toestel zelf een dergelijke RC keten te plaatsen 2 ALGEMENE BESCHRIJVING De XW60K afmeting 32x74 mm is een door een microprocessor gestuurde regelaar die geschikt is voor toepassing bij zowel positieve als negatieve koelkamers De regelaar is voorzien van 3 uitgangsrelais om compressor ontdooisysteem elektrisch of heetgas en verdamperventilatoren te sturen ...

Page 2: ... EN VICEVERSA Elke parameter in het VERBORGEN MENU kan verplaatst worden naar HET EERSTE NIVEAU gebruikersniveau door op de SET n te drukken Als een parameter naar gebruikersniveau is verplaatst wordt dit in het VERBORGEN MENU aangegeven door een decimale punt 6 6 HET TOETSENBORD BLOKKEREN 1 Hou de o en n toetsen gedurende 3 seconden tegelijk ingedrukt 2 De melding POF wordt weergegeven en het toe...

Page 3: ...werken CPr F_C compressor UIT Nadat de deur is geopend en een vertraging ingesteld via did is het deuralarm geactiveerd worden het scherm geeft de melding dA en de regelaar herstart Het alarm stopt zodra de digitale invoer gedeactiveerd is Met open deur is het alarm hoge en lage temperatuur uitgeschakeld 8 2 GENERIC ALARM i1F EAL Als de digitale invoer geactiveerd is wacht het toestel gedurende de...

Page 4: ...ONNECTIES 14 1 XW60K BEDRADING SCHEMA MET JUMPER 14 2 XW60K BEDRADINGSCHEMA ZONDER JUMPER 15 FABRIEKSINSTELLINGEN PARAMETERS Label Beschrijving Bereik C F Set Afstelling LS US 5 0 Hy Differential 0 1 25 5 C 1 255 F 2 0 LS Minimum afstelling 50 C SET 58 F SET 40 0 US Maximum afstelling SET 110 C SET 230 F 110 Ot CalibratieThermostaat sonde 12 12 C 120 120 F 0 0 P2P Verdamper sonde aanwezig n not pr...

Page 5: ... NTC or PTC probe inputs one for temperature control the other to be located onto the evaporator to control the defrost termination temperature The instrument is fully configurable through special parameters that can be easily programmed through the keyboard NOTE on the keyboard is present a jumper enabling or disabling the digital input Please refer to wiring diagrams to see how the connections a...

Page 6: ...he set point LS Minimum set point 50 C SET 58 F SET Sets the minimum acceptable value for the set point US Maximum set point SET 110 C SET 230 F Set the maximum acceptable value for set point Ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows to adjust possible offset of the thermostat probe P2P Evaporator probe presence n not present the defrost stops by time y present the defrost stops...

Page 7: ...h off and on the instrument to restart normal regulation 8 5 START DEFROST I1F DFR It starts a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 8 6 INVERSION OF THE KIND OF ACTION HEATING COOLING I1F HTR This function allows to inve...

Page 8: ...n 15 COF Compressor OFF time with faulty probe 0 255 min 30 CH Kind of action CL cooling Ht heating cL CF Temperature measurement unit C F C rES Resolution in integer dE dec point dE dLy Display delay 0 15 min P1 Lod Probe displayed P1 P2 0 tdF Defrost type EL el heater in hot gas EL dtE Defrost termination temperature 50 50 C 8 IdF Interval between defrost cycles 1 120 ore 6 MdF Maximum length fo...

Page 9: ...ées sonde NTC ou PTC la première pour le contrôle de la température la seconde placée près de l évaporateur pour contrôler la température de fin de dégivrage Ce régulateur est entièrement configurable grâce à ses paramètres facilement programmables à partir du clavier NOTE sur le clavier est present un switch qui permet d activer ou de désactiver le vérouillage Se referrer aux diagrames de connexi...

Page 10: ...igurée au paramètre CCt Le cycle peut être terminé avant la fin du temps programmé en appuyant sur la même touche o pendant 3 secondes 7 LISTE DES PARAMETRES REGULATION Hy Différentiel 0 1 25 5 C 1 255 F Différentiel du point de consigne toujours positif Le compresseur fonctionne lorsque point de consigne différentiel Hy Le compresseur s arrête lorsque la température atteint le point de consigne L...

Page 11: ...on de l entrée digitale 8 3 MODE ALARME SERIEUSE i1F bAL Quand l entrée digitale est activée le régulateur attend la temporisation did avant de signaler le message d alarme CA Les sorties relais sont désactivées L alarme sera arrêtée juste après la désactivation de l entrée digitale 8 4 SWITCH PRESSION i1F PAL Si durant l intervalle de temps paramétré en did le switch pression atteint le nombre d ...

Page 12: ...e 0 255 min 0 AC Temporisation anti court cycle 0 50 min 1 Code Désignation Gamme Par défaut CCt Durée cycle continu 0 24 0h 0 0 Con Compresseur ON en cas de défaut de sonde 0 255 min 15 CoF Compresseur OFF en cas de défaut de sonde 0 255 min 30 CH Type d action CL froid Ht chaud CL CF Unité de mesure de la température C F C rES Résolution sans avec point décimal dE in dE dLy Temporisation afficha...

Page 13: ...IBUNG Aktualisierung Das Tafeleinbaugerät XW60K T66 mit dem Frontmass 74x32mm ist ein Mikroprozessors Gesteuerter Kühlstellenregler für Normal und Tiefkühltemperaturen Mit drei Relais Ausgängen für die Regelung des Verdichter Abtauungen welche elektrisch oder Heissgas sein kann und Verdampfer Gebläse Abhängig von der Ausführung können zu drei Fühler NTC oder PTC gleichzeitig angeschlossen werden J...

Page 14: ...FRIEREN Kann nur aktiviert werden wenn nicht gerade eine Abtauung aktiv ist Die HOCH Taste mind 3s gedrückt halten Der Verdichter bleibt für die Zeit CCt kontinuierlich eingeschaltet Solange bis der Sollwert ccS erreicht wurde Zum Schockgefrieren zu beenden nochmals mind 3s HOCH Taste gedrückt halten 7 PARAMETER BESCHREIBUNG REGELUNG Hy Schalthysterese 0 1 C 25 5 C Zur Regelung des Verdichters EIN...

Page 15: ...dampfer Fühler rEL Software Version Release Ptb Parameter Tabelle Werksnummer 8 DIGITALER EINGANG Digital Eingang ist vorhanden nur wenn der überbrücker Geschenk in der Tastatur nicht eingesetzt wird Wenn der überbrücker eingesetzt wird stellen Sie bitte i1P OP ein Ein potentialfreier digitaler Eingang steht zur Verfügung Diese kann via Parameter i1F konfiguriert werden Nur wenn Par P3P n 8 1 TÜRK...

Page 16: ...ur für Betrieb 0 60 C Lager Temperatur 25 60 C Rel Feuchte 20 85 ohne Kondensierung Mess Bereich NTC Fühler 40 bis 110 C Auflösung 0 1 K oder 1 K oder 1 F vorgebbar Genauigkeit bei 25 C 0 5 C 1 Ziffer 14 ANSCHLUSS PLAN 14 1 XW60K ELEKTRISCHE ANSCHLÜSSE MIT DEM ÜBERBRÜCKER EINGESETZT 14 2 XW60K ELEKTRISCHE ANSCHLÜSSE MIT DEM ÜBERBRÜCKER NICHT EINGESETZT 15 PARAMETER WERKSVORGABEN Label Beschreibung...