F
Operating instructions
cod. 1592001330
1592001330 XC642C GB r1.0 07.06.2004.doc
rel. 1.0
Pa. 21 / 21
Name °C
°F
bar
PSI Level Description
Range
ESc
0
0
0
0
Pr2 Energy saving value for compressors
- + 20.0 bar / - + 50.0 °C / - +
300 PSI / - + 90 °F
onon
5
5
5
5
Pr2
Minimum time between 2 following switching ON of the
same compressor
0 ÷ 255 min.
oFon
2
2
2
2
Pr2
Minimum time between the switching off of a
compressor and the following switching on
0 ÷ 255 min.
don
0,3
0,3
0,3
0,3
Pr2
Time delay between the insertion of two different
compressors
0 ÷ 99.5 min. ( res. 10 sec. )
doF
0,1
0,1
0,1
0,1
Pr2
Time delay between switching off of two different
compressors
0 ÷ 99.5 min. (res.10 sec. )
donF
0,3
0,3
0,3
0,3
Pr2 Minimum time a stage stays switched ON
0 ÷ 99.5 min. (res.10 sec. )
FdLY
no
no
no
no
Pr2 “don” delay enabled also for the first call
no / YES
FdLF
no
no
no
no
Pr2 doF” delay enabled also for the first switching off
no / YES
odo
20
20
20
20
Pr2 Regulation delay on start-up
0 ÷ 255 sec.
LSE
-40
-40
0,3
5
Pr2 Minimum set point for compressors
PA04 ÷ HSE
HSE
10
50
7,2
100
Pr2 Maximum set point for compressors
LSE ÷ PA20
Lit
100
212
100
212
Pr2 Set point for cooling thermostat
Lid
10
18
10
18
Pr2 Differential for cooling thermostat
PAo
30
30
30
30
Pr2 Alarm probe exclusion at power on
0 ÷ 255 min.
LAL
15,0
30
1,5
21
Pr1
Low pressure (temperature) alarm – compressor
section
> 0 ÷ 30.0 bar / 100.0 °C / 430
PSI / 200 °F
HAL
20.0
40
2,5
46
Pr1
High pressure (temperature) alarm– compressor
section
> 0 ÷ 30.0 bar / 100.0 °C / 430
PSI / 200 °F
tAo
15
15
15
15
Pr1
Low and High pressure (temperature) alarms delay–
compressor section
0 ÷ 255 min.
SEr
999
999
999
999
Pr2 Service request
( 0 = disable ) 1 ÷ 999; res 10h
PEn
5
5
5
5
Pr2 Low pressure-switch intervention numbers
0 ÷ 15
PEi
15
15
15
15
Pr2 Pressure-switch interventions time
0 ÷ 255 min.
SPr
2
2
2
2
Pr2 Number of steps engaged with faulty probe
0 ÷ # compressors
PnF
5
5
5
5
Pr2
High pressure-switch intervention numbers – fans
section
0 ÷ 15
PiF
15
15
15
15
Pr2 Pressure-switch interventions time – fans section
0 ÷ 255 min.
tbA
yES yES yES yES
Pr2 Alarm relay silencing
no / YES
oFF
no
no
no
no
Pr2 Switching ON/OFF enabling from keyboard
no / YES
Ad1
1
1
1
1
Pr2 Compressors address
1 ÷ 247
Ptb
-
-
-
Pr1 Parameter table code
readable only
Pr2
Pr1 Password protected menu
readable only