ES = Energy saving;  oFF = instrument shut down; LLi = liquid level alarm 

did 

Configurable digital input delay

: (enabled only if i1F=LL) 0÷255min  

ALIP:   Alarm input for compressors and fans polarity  

oP

: the digital input is activated by opening the contact;  

CL

: the digital input is activated by closing the contact. 

ALMr   Manual reset of alarms for compressors and fans. 

 

no 

= automatic recover of alarm: regulation restart when the correspondent digital input is disabled 

 

yES 

= manual recover for the alarms of compressors.  

12.3  DISPLAY AND MEASUREMENT UNIT  

dEU

Default measurement unit for displaying (bar=bar; °C=°C, PSI=PSI; °F=°F)   
NOTE1

:   The  dEU  parameter  sets  the  measurement  unit  also  for  the  set  point  and  the  followin 

parameters: 

CAL,  FCAL,  Pbd,  ESC,  LSE,  HSE,  Pb,  ESF,  LSF,  HSF,    LAL,  HA,  LAF, 

HAF

rES  

Resolution for °C and bar

 (

in 

= integer; 

dE

= decimal point) 

rELP   Pressure displaying

AbS 

= absolute pressure;  

rEL 

= relative pressure.  

NOTE

:  In  this  case  the  pressure  displayed,  the  set  point  and  the  following  parameters  LSE  and 

HSE, LSF and HSF are automatically decreased by 1.0 bar or 14 PSI  

12.4  COMPRESSORS REGULATION 

Pbd

Proportional band or neutral zone width

 (0.10÷5.00bar/0.5÷30°C or 1÷80PSI/1÷50°F)  

 

The band (or zone) is symmetrical compared to the target set point, with extremes: set+Pbd/2 ... set-
Pbd/2. The measurement unit depends on the dEU par.  

ESC  

Energy saving value for compressors: 

(-20÷20bar; -50÷50°C) this value is add to the compressor 

set point.

   

onon

:  

Minimum time between 2 following switching ON of the same compressor

 (0÷255 min). 

oFon

:  

Minimum  time  between  the  switching  off  of  a  compressor  and  the  following  switching  on

(0÷255min).  

Note: 

usually onon is greater than oFon. 

don

:  

Time delay between the insertion of two different compressors 

(0÷99.5min; res. 10s). 

doF:

  

T

ime delay between switching off of two different compressors

 (0÷99.5 min; res. 10s) 

donF

:  

Minimum time a stage stays switched ON 

(0÷99.5 min; res. 10s) 

FdLy

:  

“don” delay enabled also for the first call.

 If enabled, the triggering of the step is delayed for a 

“don” value, respect to the call. (

no

 = “don” not enabled;    

yES

=”don” enabled) 

FdLF

   “

doF”  delay  enabled  also  for  the  first  switching  off

.  It  enables  the  “doF”  delay  between  the 

request of a release and the actual switching off. (

no

 = “doF” not enabled;    

yES

=”doF” enabled) 

odo

:  

Regulation  delay  on  start-up:

  (0÷255s)  on  switching  ON  the  instrument  starts  working  after  the 

time delay imposed in this parameter. 

LSE

:  

Minimum set point

: The measurement unit depends on dEU parameter. It sets the minimum value 

that can be used for the set point, to prevent the end user from setting incorrect values.  

HSE

:  

Maximum  set  point

:  The  measurement  unit  depends  on  dEU  parameter.  It  sets  the  maximum 

acceptable value for set point. 

12.5  LIQUID INJECTION THERMOSTAT (TERM. 25-26) 

Lit

Set point ( °C) for liquid injection thermostat 

(0 ÷ 150°C) 

Lid

Differential for  liquid injection thermostat 

(0.1 ÷ 10.0) 

12.6  ALARMS – COMPRESSOR SECTION 

PAo:   Alarm probe exclusion at power on.

 it is the period starting from instrument switch on, before an 

alarm  probe  is  signalled.  (0÷255  min).  During  this  time  if  the  pressure  is  out  of  range  all  the 
compressor are switched on. 

LAL

:  

Low  pressure  (temperature)  alarm  –  compressor  section

:  The  measurement  unit  depends  on 

dEU  parameter.  It’s  always  subtracted  to  the  set  point.  When  the  value 

SET-LAL

  is  reached  the 

A03C alarm is enabled, (possibly after the 

tAo

 delay time). 

HAL

:  

High  pressure  (temperature)  alarm–  compressor  section

:  The  measurement  unit  depends  on 

dEU parameter. It’s always added  to the set point. When the value SET+HAL is reached the A04C 
alarm is enabled, (possibly after the 

tAo

 delay time). 

tAo

:  

Low  and  High  pressure  (temperature)  alarms  delay–  compressor  section

:  (0÷255  min)  time 

interval between the detection of a pressure (temperature) alarm condition and alarm signalling. 

Summary of Contents for XC642C

Page 1: ...Compressor racks controller XC642C Operating manual...

Page 2: ...UNNING HOURS OF LOADS _______________________________________________ 8 8 1 How to display the running hours of a load ____________________________________________ 8 8 2 How to reset the running hours...

Page 3: ...enance Fit the probe where it is not accessible by the End User The instrument must not be opened In case of failure or faulty operation send the instrument back to the distributor or to Dixell S p a...

Page 4: ...1 use the parameter PA04 Adjustment of read out corresponding to 4mA PA20 Adjustment of read out corresponding to 20mA Practically these parameters has to be set with the start and end scale of the p...

Page 5: ...nt in programming mode it selects a parameter or confirm an operation Alarm menu By holding it pressed for 3s the current alarm is erased o o o o UP To enter the Alarm menu In programming mode it brow...

Page 6: ...How to see and modify the set point 5 1 HOW TO SEE THE SET POINT OF COMPRESSORS 1 Push and release the SET key 2 The Lower display will show the SEtC label will the Upper display will show its value...

Page 7: ...key 5 Repeat operations 2 and 3 for the other digits NOTE each parameter in Pr2 can be removed or put into Pr1 user level by pressing SET n n n n When a parameter is present also in Pr1 decimal point...

Page 8: ...rs of the first output 3 To see the running hours of the following load press the UP key To exit push the CLOCK key or wait 30 sec 8 2 HOW TO RESET THE RUNNING HOURS OF A LOAD 1 Display the running ho...

Page 9: ...T KEY DOWNLOAD 1 Turn OFF the instrument 2 Insert a programmed Hot Key into the 5 PIN receptacle and then turn the Controller ON 3 Automatically the parameter list of the Hot Key is downloaded into th...

Page 10: ...f sequence YES rotation this algorithm distributes the working time between the various loads to ensure even run times no fixed sequence the compressors are enabled and disabled in fixed sequence firs...

Page 11: ...min res 10s doF Time delay between switching off of two different compressors 0 99 5 min res 10s donF Minimum time a stage stays switched ON 0 99 5 min res 10s FdLy don delay enabled also for the firs...

Page 12: ...ON OFF enabling from keyboard no disabled yES enabled It permits the switching ON OFF of the instrument by pressing the SET key for more than 4s Ad1 Compressors address 1 247 It is used in monitoring...

Page 13: ...ts If the pressure is greater than SET Pbd 2 the loads are switching on with timing given by parameters don and doF A load is turned on only if the his safety times onon oFon donF are over Regulation...

Page 14: ...rature is lower than the regulation band all the compressors are off Naturally also for this regulations all the delays don and doF safety times onon oFon and donF are valid Regulation according to th...

Page 15: ...erminal blocks for wires having section not bigger than 1 0 mm2 14 ways for analogue and digital inputs 12 ways for relays Note terminals 17 19 are connected inside the controller they are the common...

Page 16: ...ting in a 29x71 mm panel cut out Protection IP65 Frontal protection IP65 with frontal gasket mod RG C model Connections Removable terminal block 12 and 14 ways Power supply 12Vac dc 10 24Vac dc 10 50...

Page 17: ...suction and condensing sections Terminals Low pressure switch input 9 10 high pressure switch input HP Parameters SEP Low pressure switch polarity It establishes if the input is activated by closing S...

Page 18: ...ow pressure temperature alarms This alarm signals that the pressure temperature is out of limits established by parameters LAL and HAL for compressors and LAF HAF for fans The tAo and AFd parameters s...

Page 19: ...isabled Recovery depends on ALMr parameter With ALMr no The instrument restart the standard operating mode when the input is disabled With ALMr yES manual recover for the alarms of compressors and fan...

Page 20: ...7 134 717 rtY db db db db Pr2 Type of regulation db Pb StY yES yES yES yES Pr2 Compressor rotation no YES Pbc Cur Cur Cur Cur Pr2 Probe 1 setting cur Ptc ntc PA04 0 5 7 0 5 7 Pr2 Adjustment of read ou...

Page 21: ...point for cooling thermostat Lid 10 18 10 18 Pr2 Differential for cooling thermostat PAo 30 30 30 30 Pr2 Alarm probe exclusion at power on 0 255 min LAL 15 0 30 1 5 21 Pr1 Low pressure temperature ala...

Reviews: