the label A12  is shown on the upper display, while the lower display signals what wrong setting has created 
the error:  
The following table contains the displayed messages:  
 

 

Mess. 

Errata 

Corrige 

nLod

 

Number of loads higher than 
loads available in the controller 

 

Check number of oAi set as load, this number 
has to be lower of equal to the number of 
relay of the controller. 

cStP

 

Load (step) configuration error  

 

A relay oA(i) has been set as compressor 
without a previous relay oA(i-1) has been set 
as compressor. EI oA1 = StP 

AOP2

 

P2 probe not available for the 
4÷20mA output 

 

P2 probe not available P2P =no. Enable the 
probe setting: P2P =yES 

 

The second probe P2 is used to control the 
temperature of the engine of screw 
compressors. Check CtyP and set it different 
from Scr. 

dSP2

 

P2 probe not available for the 
dynamic set point function  

 

P2 probe not available P2P =no. Enable the 
probe setting: P2P =yES 

 

The second probe P2 is used to control the 
temperature of the engine of screw 
compressors. Check CtyP and set it different 
from Scr. 

CSP2

 

P2 probe not available for screw 
compressor 

 

Check CtyP and set it different from Scr. 

P2CF

 

Wrong second probe 
configuration (EI.: If Cty= Scr P2 
ha to be  PTC)  

 

Set P2P = yES and PbC2 = PTC  

20.1.2

 

E0H, E0L Pressure switch alarm, suction and condensing sections 

Terminals 

Low pressure switch input: 9-10, high pressure switch input: HP. 
 

Parameters

 

SEP:  Low  pressure  switch  polarity:

  It  establishes  if  the  input  is  activated  by  closing  (SEP=cL)  or  by 

opening (SEP=oP) the terminals. 

HPP:  High  pressure  switch  polarity:

  It  establishes  if  the  input  is  activated  by  closing  (HPP=cL)  or  by 

opening (HPP=oP) the terminals. 
 

Actions

 

Low  pressure:

  every  time  the  inputs  are  activated  all  the  compressors  are  switched  off.  The  instrument 

restart the standard operating mode when the input is disabled.  If there are PEn activation in the PEi time, 
only manual resetting is allowed, by pressing the 

DOWN

 key for 3s or by turning off and on the instrument. 

High  pressure:

  every  time  the  inputs  are  activated  all  the  compressors  are  switched  off  and  fans  are 

switched  on.  The  instrument  restart  the  standard  operating  mode  when  the  input  is  disabled.    If  there  are 
PnF  activation  in  the  PiF  time,  only  manual  resetting  is  allowed,  by  pressing  the 

DOWN

  key  for  3s  or  by 

turning off and on the instrument. 

 

20.1.3

 

EA1÷EA4: Compressors safeties alarm 

Terminals

 

WARNING: THESE TERMINALS REQUIRE A FREE OF VOLTAGE CONNECTION.

  

The terminals (from 10, 11, 12, 13, 14+ ID5) really used depends on the number of loads. The protections 
regarding the compressors  and fans  are  connected to these inputs. If one  of  these  protections  is enabling 
(E.I. for lack of oil or overheating, etc,) the corresponding load is turn off. 
 

Parameters

 

ALIP: 

It establishes if the input is activated by closing (ALIP=cL) or by opening (ALIP=oP) the terminals. 

Summary of Contents for XC642C

Page 1: ...Compressor racks controller XC642C Operating manual...

Page 2: ...UNNING HOURS OF LOADS _______________________________________________ 8 8 1 How to display the running hours of a load ____________________________________________ 8 8 2 How to reset the running hours...

Page 3: ...enance Fit the probe where it is not accessible by the End User The instrument must not be opened In case of failure or faulty operation send the instrument back to the distributor or to Dixell S p a...

Page 4: ...1 use the parameter PA04 Adjustment of read out corresponding to 4mA PA20 Adjustment of read out corresponding to 20mA Practically these parameters has to be set with the start and end scale of the p...

Page 5: ...nt in programming mode it selects a parameter or confirm an operation Alarm menu By holding it pressed for 3s the current alarm is erased o o o o UP To enter the Alarm menu In programming mode it brow...

Page 6: ...How to see and modify the set point 5 1 HOW TO SEE THE SET POINT OF COMPRESSORS 1 Push and release the SET key 2 The Lower display will show the SEtC label will the Upper display will show its value...

Page 7: ...key 5 Repeat operations 2 and 3 for the other digits NOTE each parameter in Pr2 can be removed or put into Pr1 user level by pressing SET n n n n When a parameter is present also in Pr1 decimal point...

Page 8: ...rs of the first output 3 To see the running hours of the following load press the UP key To exit push the CLOCK key or wait 30 sec 8 2 HOW TO RESET THE RUNNING HOURS OF A LOAD 1 Display the running ho...

Page 9: ...T KEY DOWNLOAD 1 Turn OFF the instrument 2 Insert a programmed Hot Key into the 5 PIN receptacle and then turn the Controller ON 3 Automatically the parameter list of the Hot Key is downloaded into th...

Page 10: ...f sequence YES rotation this algorithm distributes the working time between the various loads to ensure even run times no fixed sequence the compressors are enabled and disabled in fixed sequence firs...

Page 11: ...min res 10s doF Time delay between switching off of two different compressors 0 99 5 min res 10s donF Minimum time a stage stays switched ON 0 99 5 min res 10s FdLy don delay enabled also for the firs...

Page 12: ...ON OFF enabling from keyboard no disabled yES enabled It permits the switching ON OFF of the instrument by pressing the SET key for more than 4s Ad1 Compressors address 1 247 It is used in monitoring...

Page 13: ...ts If the pressure is greater than SET Pbd 2 the loads are switching on with timing given by parameters don and doF A load is turned on only if the his safety times onon oFon donF are over Regulation...

Page 14: ...rature is lower than the regulation band all the compressors are off Naturally also for this regulations all the delays don and doF safety times onon oFon and donF are valid Regulation according to th...

Page 15: ...erminal blocks for wires having section not bigger than 1 0 mm2 14 ways for analogue and digital inputs 12 ways for relays Note terminals 17 19 are connected inside the controller they are the common...

Page 16: ...ting in a 29x71 mm panel cut out Protection IP65 Frontal protection IP65 with frontal gasket mod RG C model Connections Removable terminal block 12 and 14 ways Power supply 12Vac dc 10 24Vac dc 10 50...

Page 17: ...suction and condensing sections Terminals Low pressure switch input 9 10 high pressure switch input HP Parameters SEP Low pressure switch polarity It establishes if the input is activated by closing S...

Page 18: ...ow pressure temperature alarms This alarm signals that the pressure temperature is out of limits established by parameters LAL and HAL for compressors and LAF HAF for fans The tAo and AFd parameters s...

Page 19: ...isabled Recovery depends on ALMr parameter With ALMr no The instrument restart the standard operating mode when the input is disabled With ALMr yES manual recover for the alarms of compressors and fan...

Page 20: ...7 134 717 rtY db db db db Pr2 Type of regulation db Pb StY yES yES yES yES Pr2 Compressor rotation no YES Pbc Cur Cur Cur Cur Pr2 Probe 1 setting cur Ptc ntc PA04 0 5 7 0 5 7 Pr2 Adjustment of read ou...

Page 21: ...point for cooling thermostat Lid 10 18 10 18 Pr2 Differential for cooling thermostat PAo 30 30 30 30 Pr2 Alarm probe exclusion at power on 0 255 min LAL 15 0 30 1 5 21 Pr1 Low pressure temperature ala...

Reviews: