TECHNICAL DATA
20.1 S
UPPLY VOLTAGE
Power Supply:
12Vac/dc -10% ÷ 15%, 50/60Hz, or
24Vac/dc -10% ÷ 10%, 50/60Hz
Consumption:
Max. 10VA
Connectors:
Molex connectors for power supply, probes connection,
digital inputs, analog outputs)
STELVIO screw connectors for LAN connection
STELVIO screw connectors for relay
20.2 A
NALOGUE INPUTS
Number of inputs:
4 (NTC, PTC, Digital input)
2 (NTC, PTC, 4..20mA, 0..5V, Digital input)
Type of analogue input:
(configurable via software
parameter)
NTC (-50T110°C; 10K
Ω±
1% a 25°C)
PTC (-50T150°C; 990
Ω±
1% a 25°C)
Rathiometric: 0.5..4.5V
Current: 4..20mA
Digital input (free contact)
Operation range:
-50°C ÷ 110°C (-58 °F ÷ 230°F) NTC probe
-50°C ÷ 150°C (-58 °F ÷ 302°F) PTC probe
0 bar ÷ 50 bar (0 psi ÷ 302 psi) pressure probe
Resolution:
0.1 °C
1 °F
0.1 bar
1 psi
20.3 D
IGITAL INPUT
Type:
(configurable via software
parameter)
Free contact not opto-insulated
Number of inputs:
11
Notes:
Don’t supply voltage to the digital inputs
in order to not cause
damage to the instrument