1592022010 Quick reference guide iCHILL 100CX EVO rel. 1.0
15/40
•
COSn
Read and reset the number of compressor starts-up
•
COdt
Read the compressor discharge temperature
•
Cond
Read the condensing fan speed percentage of the proportional output
•
Pout
Read the percentage of the proportional output 0 ÷ 10 Vdc
•
PoEn
Enable
–
disable evaporator or condenser water pumps
•
dF
Time counting to next defrost cycle, under heat pump mode,
•
uS
Read the probe temperatures that enabled to control the auxiliary output
•
SoL
Read temperature, Set point and output status of solar panel
•
FC
Read temperature, Set point and output status of Free cooling
•
trEM
Read probe temperature of the remote panels
•
Et1
Read temperature, pressure, set point of the electronic expansion valve 1
•
Et2
Read temperature, pressure, set point of the electronic expansion valve 2
•
REC
Enable / disable recovery function
11.1
ALARM
LIST:
READ
AND
RESET
ALrM FUNCTION
1.
Push MENU key
2.
The display shows AlrM label
3.
Push
SET
key (Nothing happens if there are not alarms)
4.
The bottom display shows the alarm code and the top display shows the label
rSt,
if it is possible to reset
the alarm, or
NO
if it is not possible to reset the alarm
5.
Push
UP
or
DOWN
to scroll the alarm list (if more than one alarm is active)
6.
Repeat the reset procedure for each alarm
7.
To exit the ALrM reset, push
MENU
or wait the timeout.
11.2
ALARM
LOG
LIST
ALOG FUNCTION
1.
Push
MENU
key
2.
Push
UP
or
DOWN
to select ALOG
3.
Push
SET
key
4.
The bottom display shows the alarm label, the top display shows a number in the range 00 to 99.
5.
Use the
UP
or
DOWN
keys to scroll the list.
6.
To exit the ALOG function push
MENU
or wait the timeout.
Erase the Alarm log list
1.
Push
MENU
key
2.
Push
UP
or
DOWN
to select ALOG
3.
Push the
SET
key
4.
Push
UP
or
DOWN
keys and search the
ArSt
label on the bottom display; the top display shows PAS.
5.
Push
SET
; the bottom display shows
PAS
and the top display shows
“
0
”
blinking
6.
Push
UP
or
DOWN
to set the password
7.
If the password is OK the label
ArST
blinks for 5 seconds then the display returns to normal condition
read-out
8.
If the password is not correct the display shows
PAS
again