1592022010 Quick reference guide iCHILL 100CX EVO rel. 1.0
13/40
•
Select the UPL function (on the bottom display)
•
Push SET key and immediately the instrument starts transfer the parameters into the Hot key.
During the upload the regulation is locked and the top display shows the “UPL” blinking label. At the end of the
UPLOAD will appear:
1.
“End” if the programming procedure is completely OK, after 30seconds the regulation st
arts
automatically.
2.
“Err” if the programming procedure has found an error and the parameter have not been transferred.
Repeat the procedure.
To exit the UPL function push the MENU key or wait the time-out (15 sec).
10
PROGRAMMING USING LOCAL USER INTERFACE
Though the keyboard it is possible to modify the values of the parameters and set for each one of them the
visibility and editability; each parameter can be made visible at different levels of users:
•
Pr1 User level (default Password = 1)
•
Pr2 Maintenance level (default Password = 2)
•
Pr3 OEM level (default Password = 3)
The default password for resetting the alarm history and compressor overload alarm is 4.
Passwords can be customized using specific parameters; in the case in which it is necessary to access the
parameters and the passwords have been changed, it is necessary to contact the machine manufacturer to
obtain the necessary information.
10.1
ENTER
PARAMETERS
PROGRAMMING
LEVEL
PR1
Enter the Pr1 “User level”:
1.
Push
SET
+
DOWN
keys together for 3 seconds. The top display shows
“
PAS
”
and the bottom display
shows
“
Pr1
”
.
2.
Push
SET
key and the top display shows
“0”
blinking
3.
Push
UP
or
DOWN
to select Pr1 password
4.
Push
SET
and, if the value is correct, the top display shows the first family of parameters
“ALL”
5.
Push
UP
or
DOWN
to select the parameter family
6.
Push
SET
to enter; the bottom display shows the first available parameter while the top display shows its
value.
7.
Push
UP
or
DOWN
to modify its value
8.
Push
SET
to confirm the new value
9.
If necessary, modify others parameter
10.
Push
SET
+
UP
keys together to exit parameters programming
10.2
ENTER
PARAMETERS
PROGRAMMING
LEVEL
PR2
Enter the Pr2 “
service level
”:
1.
Push
SET
+
DOWN
keys together for 3 seconds. The top display shows
“
PAS
”
and the bottom display
shows
“
Pr1
”
2.
Push
UP
key for 2 seconds and the top display will show Pr2
3.
Push
SET
key and the top display shows “0” blinking