24
ASSEMBLY PROCEDURE
1. Position the supplied paper template on the wall and using a pencil mark the positions of the two holes to be drilled and the posi-
tion of the support bracket at a height of around 200 cm from the floor and 15 cm from the ceiling.
Unusual installation positions must be worked out case by case.
Whenever the paper template has not been provided, see the dimensions shown in the drawing on Page 11.
2. Drill adequate holes for the suction and expulsion of the air using drill bits.
These holes must slope slightly downward by approximately 0.5 cm from the inside to the outside in order to prevent rain or dirt
from entering the room and the air conditioner.
3 Drill the holes for the fastening of the air conditioner support bracket. The support bracket must be fastened using expansion
bolts of no less than 1 cm while also bearing in mind the type of wall in
which the air conditioner will be installed and that the air conditioner is
heavier on its right side (looking at the wall from inside the room).
IMPORTANT: whenever auxiliary condensate drainage will be provided (see
the respective paragraphs on Page 18) provide an adequate recess in the
wall.
4. Insert the plastic pipes of diameter and length adequate to the depth of
the wall into the holes drilled for air suction and expulsion, making sure
that the pipe lined with condensate-proof material can be fitted into hole A
as shown in Figure 1.
N.B.: The air inlet and outlet pipes supplied have a maximum length of 40
cm; for this reason, if the depth of the wall is less, these pipes must be cut.
For installations with pipes longer than 40 cm, please contact your nearest
Technical Assistance Center or your Manufacturer's technical/commercial
contact person.
5. Make sure that the air expulsion pipe (hole A in Figure 1) is lined with
condensate-proof insulation material along its entire length.
Whenever the kit supplied is not used, remember to internally line the air
expulsion pipe (to be fitted in hole A in Figure 1) with condensate-proof
material for its entire length.
6. Apply junk rings or appropriately insulated flanges on the pipes in order
to guarantee ideal contact between the air conditioner and the holes.
IMPORTANT: the cut flange must be applied near hole A shown in Figure 1
where the insulated pipe will be connected.
WALL INSTALLATION
IMPORTANT: Cordon off the outdoor area immediately beneath the installation area to prevent falling masonry
debris or chunks of plaster from damaging or injuring property and people below.
Make sure that there are no electric hoses or gas or water pipes inside the parts of the wall to be drilled.
Figure 1
A air expulsion hole
B air suction hole
C support bracket
A
C
B
200 cm cir
ca