Process input
When programmed input type is process, for both display scaling
“
SCAL
”
and
“
tEAC
”
methods, parameters to be sequentially
introduced are identical.
It only must be considered that in
“
SCAL
”
method, all values must be
manually introduced through the three frontal keys whereas in
“
tEAC
”
method, input signal value must be present at the conector at
each point that is intended to be configured.
FIRST POINT INPUT AND DISPLAY VALUE:
InP1
:
Input value indication.
0000
:
Value entering in counts within display range.
dSP1:
Display value indication.
0000
:
Value entering in counts within display range.
DECIMAL POINT:
00.00
:
Setting of decimal point position.
(Decimal point can be located in any position, and will be
the same for Display 1 and Display 2. This position remains
fixed for all configuration steps and also for
RUN
mode).
SECOND POINT INPUT AND DISPLAY VALUE:
InP2
:
Input value indication.
0000
:
Value entering in counts within display range.
dSP2:
Display value indication.
0000
:
Value entering in counts within display range.
Temperature input
When programmed input type is temperature, for thermocouple and
Pt100 sensor, the only parameter to configure is the filter and its
configuration is done in the same way as described for process input.
Display scaling is not available for this input type, the unit then will
assume a fixed calibrated range depending on sensor type and
previously configured units resolution.
FiLt
0
FiLt
0
SCAL
InP1
tEAC
0000
dSP1
0000
00.00
InP2
0000
dSP2
0000
WEIGHTED AVERAGE FILTER:
FiLt
:
0
to
9
configurable.
Value
Fc (Hz)
Value
Fc (Hz)
0
--
5
2.2
1
7.3
6
1.6
2
5.1
7
1.1
3
3.8
8
0.5
4
2.9
9
0.2