IDEAL
-
P
KOSMOS SERIE
www.ditel.es
7
The
IDEAL
-
P
model of the KOSMOS series is a universal digital indicator that allows the user to configurate the
meter according the type of input used:
PROCESS
(V, mA)
THERMOCOUPLE
(J, K, T and N)
Pt100 SENSOR
The basic instrument is a set consisting of the base and display circuits also incorporating by default, an analog
output and another one of 1 relay type SPDT 8A isolated with respect to the input signal and the general power
supply. These output circuits have independent connectors with output on the back of the instrument.
This model for the control of industrial processes has 4 digits and a programmable decimal point to visualize the
input variables, and is easily scalable in the desired engineering units, either directly by the keyboard or by the
actual input level. It also supplies a 24V DC signal as a transducer excitation and a 4
-
20mA analog output.
The
IDEAL
-
P
model is an indicator with digits of 14mm of height and maximum display range
-
9999
to
9999
.
The sign LED is outside, being placed to the left of the most significant digit.
The instrument has a keyboard with three buttons with which it is possible to interact with the internal software to
configure it and adapt it to the desired operating characteristics. The programming is done through independent
menus that incorporate messages for easy identification of the steps to follow when setting the type of input,
configuring the display and / or configuring the working mode of the two available outputs.
Device description
Dimensions and mounting
To install the instrument, prepare a
92x45mm panel cut
-
out and slide the unit
inwards making sure of placing the sealing
gasket between the front side panel and
the frontal bezel.
While holding the unit in place, put the
fixing clips on both sides of the case and
slide them through the guide tracks until
they reach the panel at the rear side.
To remove the instrument from the panel, pull outwards the rear fixing
clips latching tabs until they are disengaged, then slide fixing clips back
over the case.
Press slightly to fasten the clips to the latching slots
on the case and get the unit fully assembled and
close fitted to achieve a good sealing.