Analog output configuration menu
ANALOG OUTPUT CONFIGURATION
The fourth menu corresponds to the analog output. For more details on the operating
modes, consult the section corresponding to this output later in this manual. The
parameters to configure are the following:
RANGE OF ACTION:
Enter the two display values by 4 digits that will define the variation of the 4
-
20mA output
signal.
Upper limit:
outH
:
Higher output value indication.
0000
:
Enter the value in display points within the available range. It will match an
output signal of 20mA.
Lower limit:
outL
:
Lower value indication.
0000
:
Enter the value in display points within the available range. It will match an
output signal of 4mA.
AnA
outH
0000
outL
0000
no
diMM
ProG
Stor
dFLt
LASt
0000
SEtG
SEt
GENERATOR OF ANALOG SETPOINT:
SEtG
:
Setpoint generator indication.
no
:
Disable the setpoint generator.
Adjustment mode:
diMM
:
Enables the setpoint generator in regulator mode
or 'Dimmer'.
ProG
:
Enables the set point generator in Programmed
mode.
Initial value by default:
dFLt
:
Default value indication.
LASt
:
The initial default value will be the last one
provided in 'Dimmer' mode or the last one
entered in programmed mode.
SEt
:
Value setting indication.
0000
:
Enter the four digits of the default initial value.
NOTE: It is not possible to change the position of the
decimal point, this position is determined by the one that
has been configured in the '
dSP
' display menú.
Pro
0000
0050
To adjust the value of the setpoint generator in programmed mode
'
ProG
', from the '
run
' mode press the
ENTER
key and while the
indication "
Pro
" is shown, press the '
SHIFT
'
/
'
DOWN
' key.
Enter the desired value digit by digit using the keyboard. Press the
'
ENTER