Troubleshooting Guide 

Controller is powered but does not turn on 

Fuse has blown 

Disconnect the power. Check the fuse integrity. Reconnect the power. 

Power supply polarity 

Verify that consistent polarity is maintained between all controllers and the transformer. Ensure that the 24VCOM terminal 

of each controller is connected to the same terminal on the secondary side of the transformer. Se

Figure 8

. 

Controller cannot communicate on the L

ON

W

ORKS

 network 

Absent or incorrect supply voltage 

1. Check power supply voltage between 24VAC ±15% and 24VCOM pins and ensure that it is within acceptable limits. 

2. Check for tripped fuse or circuit breaker. 

Overloaded power transformer 

Verify that the transformer used is powerful enough to supply all controllers. 

Network not wired properly 

Double check that the wire connections are correct. 

Absent or incorrect network termination 

Check the network termination(s). 

Too many Allure EC-Smart-Vue Sensors are 

providing network access 

Disable the 

Net to Subnet Port Settings

 jumpers on all controllers (for jumper location, see Figure 9). If communications 

are re-established, re-enable only a few Allure EC-Smart-Vue sensors to have network access.  

Controller communicates well over a short network, but does not communicate on large network

 

Network length 

Check that the total wire length does not exceed the specifications of the 

Junction Box and Wiring Guideline for Twisted 

Pair L

ON

W

ORKS

 Networks

Wire type 

Check that the wire type agrees with the specification of the 

Junction Box and Wiring Guideline for Twisted Pair 

L

ON

W

ORKS

 Networks

Network wiring problem 

Double check that the wire connections are correct. 

Absent or incorrect network termination 

Check the network termination(s). Incorrect or broken termination(s) will make the communication integrity dependent 

upon a controller’s position on the network. 

Extra capacitance 

Make sure that no extra capacitance is being connected to the network other than the standard FTT circuit and a 

maximum of a 3 meter stub (in bus topology). 

Number of controllers on network segment 

exceeded 

The number of controllers on a channel should never exceed 64. Use a router or a repeater in accordance to the 

Junction 

Box and Wiring Guideline for Twisted Pair L

ON

W

ORKS

 Networks

 . 

Network traffic 

Query node statistics to check for errors. 

Use a L

ON

W

ORKS

 protocol analyzer to check network traffic. 

Hardware input is not reading the correct value

 

Input wiring problem 

Check that the wiring is correct according to this manual and according to the peripheral device’s manufacturer. 

Open circuit or short circuit 

Using a voltmeter, check the voltage on the input terminal. For example, for a digital input, a short circuit shows 

approximately 0V DC and an open circuit shows approximately 5V DC. 

Configuration problem 

Using EC-

gfx

Program, check the configuration of the input. Refer to the controller’s user guide for more information. 

Over-voltage or over-current at an input 

An over-voltage or over-current at one input can affect the reading of other inputs. Respect the allowed voltage / current 

range limits of all inputs. Consult the appropriate datasheet for the input range limits of this controller. 

Hardware output is not operating correctly 

Fuse has blown (auto-reset fuse) 

Disconnect the power and outputs terminals. Then wait a few seconds to allow the auto-reset fuse to cool down. Check 

the power supply and the output wiring. Reconnect the power. 

Output wiring problem 

Check that the wiring is correct according to this manual and according to the peripheral device’s manufacturer. 

Configuration problem 

Using the controller configuration plug-in or wizard, check the configuration of the output. Refer to the controller’s user 

guide for more information. 

0-10V output, 24VAC powered actuator is not 

moving. 

Check the polarity of the 24VAC power supply connected to the actuator while connected to the controller. Reverse the 

24VAC wire if necessary. Check the jumper settings for the external power supply as shown i

Table 3

Wireless devices not working correctly 

Device not associated to controller 

Using EC-

gfx

Program, check the configuration of the input. Refer to the device’s user guide for more information. 

Power discharge 

1. Recharge device with light (if solar-powered) or replace battery (if battery-powered), 

2. Ensure sufficient light intensity (200lx for 4 hours/day). 

Device too far from the Wireless Receiver 

Reposition the device to be within the range of the Wireless Receiver. For information on typical transmission ranges, 

refer to the Open-to-Wireless Solution Guide. 

Configuration problem 

Using the device configuration plug-in or wizard, check the configuration of the input. Refer to the Wireless Battery-less 

Sensors and Switches Solutions Guide for more information. 

Flow sensor is not giving proper readings 

Tubing connection problem 

1. Make sure that the tubing is installed properly and that the tubing is not bent. 

2. Verify that the high and low pressure sensors are not inversed. 

Controller is not calibrated properly 

Recalibrate the controller. Refer to the controller’s user guide for more information. 

Damper is not opening or closing properly 

Mechanical stops not in proper position 

The two mechanical stops must be positioned to stop the damper motion when it is completely closed and completely 

opened. The mechanical stops can be moved by increments of 5°. 

Controller in Override 

Set the Override to OFF in the wizard. 

Rx/Tx LEDs

 

RX LED not blinking 

Data is not being received from the L

ON

W

ORKS 

data bus. 

TX LED not blinking 

Data is not being transmitted onto the L

ON

W

ORKS 

data bus. 

Summary of Contents for ECL-103

Page 1: ...ure during shipping storage to evaporate Upon unpacking the product inspect the contents of the carton for shipping damages Do not install damaged controllers Avoid areas where corroding deteriorating...

Page 2: ...3 wire voltage and current inputs and outputs as well as triac outputs should be kept apart from other types of wiring to avoid any ambient noise transmission to other wires The board connectors accep...

Page 3: ...urn the controller s shaft coupler until it touches the mechanical end stop to either the fully closed position 90 boxes or the fully open position 45 and 60 boxes 6 For 90 VAV boxes If the damper clo...

Page 4: ...wires when daisy chaining devices Use a wire nut with a pig tail to make such a connection Use an external fuse on the 24VAC side secondary side of the transformer as shown in Figure 8 to protect all...

Page 5: ...COM To Analog To Digital Converter Potentiometer 10k 0 to 20mA input used with a 2 wire 0 to 20mA sensor powered by the controller s internal 15VDC power supply Sensor 0 20mA UIx COM 15VDC To Control...

Page 6: ...UOx COM Linear 0 to 10VDC digital to analog output UOx 0 10V Common From Digital To Analog Output UOx COM 0 to 10VDC voltage output controlling an analog actuator that is powered by an external 24VAC...

Page 7: ...network topology and wire length restrictions refer to the Network Guide It can be downloaded from our website It is important to use proper network terminators depending on the type of network topolo...

Page 8: ...evices are not to be thrown away in municipal waste Products must be disposed of at the end of their useful life according to local regulations and the WEEE Directive North American Emissions Complian...

Page 9: ...Heating Floating Actuator LONWORKS Network Back of Allure EC Smart Vue Wireless Port beneath cover E D E D Service PIN Button BAC LON Figure 14 Typical Power and Network Connections with an Allure EC...

Page 10: ...rcuit shows approximately 0V DC and an open circuit shows approximately 5V DC Configuration problem Using EC gfxProgram check the configuration of the input Refer to the controller s user guide for mo...

Page 11: ...eats every 2 seconds highest priority shown first Long blink continuous 1s On 1s Off continuous The controller is unconfigured Appropriate action Commission the controller Long Long Long blink 800ms O...

Page 12: ...VAC specialist installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change...

Reviews: