6/12 

 

Output Wiring 

Table 3 shows the available output wiring methods. 

 

Before connecting an output device (actuator, relay, etc.) to the controller, refer to the  datasheet and  installation guide of the equipment 

manufacturer. 

 

 

For a wire length less than 75’ (23m) long, either a shielded or unshielded 18AWG wire may be used. 

For a wire length up to 200’ (61m) long, a shielded 18AWG wire is recommended. 

The shield of the wire should be grounded on the controller side and the shield length should be kept as short as possible. 

For relay outputs (DOx); select appropriately-sized wiring suitable to the current load. 

 

Table 3: Output Wiring 

Control Output Type 

Output 

Designation 

Output Connection Diagram 

Discrete 0 or 12VDC digital, Pulse, or PWM output controlling a 12VDC 

relay. 

UOx 

From 

Digital 

Output

12VDC Relay

A1
A2

UOx

COM

 

Linear 0 to 10VDC digital to analog output. 

UOx 

0-10V
Common

From Digital-

To-Analog 

Output

UOx

COM

 

0 to 10VDC voltage  output  controlling an analog actuator that is 

powered by an external 24VAC power source. 

UOx 

0-10V
~ or +

From Digital-

To-Analog 

Output

UOx

COM

Actuator

or -

24VAC

 

24VAC externally-powered triac output controlling a relay

1

.  

Set the jumper according to Figure 9. 

DOx  

JUMPER

SETTINGS

24VAC Relay

A1
A2

DOx

Cx-x

AC

 

24VAC internally-powered triac output controlling a relay

1

.  

Set the jumper according to Figure 9. 

DOx  

JUMPER

SETTINGS

24VAC Relay

A1
A2

DOx

Cx-x

 

24VAC externally-powered triac output controlling a floating actuator

1

.  

Set the jumper according to Figure 9. 

DOx  

DOx

Cx-x

Actuator

~

DOx

~

JUMPER

SETTINGS

24VAC

 

24VAC externally-powered triac output controlling a floating actuator

1

.  

Set the jumper according to Figure 9. 

DOx  

DOx

Cx-x

Actuator

~

DOx

~

JUMPER

SETTINGS

 

Maximum output current for all digital triac outputs is 0.5A continuous or 1A @ 15% duty cycle for a 10-minute period. 

Summary of Contents for ECL-103

Page 1: ...ure during shipping storage to evaporate Upon unpacking the product inspect the contents of the carton for shipping damages Do not install damaged controllers Avoid areas where corroding deteriorating...

Page 2: ...3 wire voltage and current inputs and outputs as well as triac outputs should be kept apart from other types of wiring to avoid any ambient noise transmission to other wires The board connectors accep...

Page 3: ...urn the controller s shaft coupler until it touches the mechanical end stop to either the fully closed position 90 boxes or the fully open position 45 and 60 boxes 6 For 90 VAV boxes If the damper clo...

Page 4: ...wires when daisy chaining devices Use a wire nut with a pig tail to make such a connection Use an external fuse on the 24VAC side secondary side of the transformer as shown in Figure 8 to protect all...

Page 5: ...COM To Analog To Digital Converter Potentiometer 10k 0 to 20mA input used with a 2 wire 0 to 20mA sensor powered by the controller s internal 15VDC power supply Sensor 0 20mA UIx COM 15VDC To Control...

Page 6: ...UOx COM Linear 0 to 10VDC digital to analog output UOx 0 10V Common From Digital To Analog Output UOx COM 0 to 10VDC voltage output controlling an analog actuator that is powered by an external 24VAC...

Page 7: ...network topology and wire length restrictions refer to the Network Guide It can be downloaded from our website It is important to use proper network terminators depending on the type of network topolo...

Page 8: ...evices are not to be thrown away in municipal waste Products must be disposed of at the end of their useful life according to local regulations and the WEEE Directive North American Emissions Complian...

Page 9: ...Heating Floating Actuator LONWORKS Network Back of Allure EC Smart Vue Wireless Port beneath cover E D E D Service PIN Button BAC LON Figure 14 Typical Power and Network Connections with an Allure EC...

Page 10: ...rcuit shows approximately 0V DC and an open circuit shows approximately 5V DC Configuration problem Using EC gfxProgram check the configuration of the input Refer to the controller s user guide for mo...

Page 11: ...eats every 2 seconds highest priority shown first Long blink continuous 1s On 1s Off continuous The controller is unconfigured Appropriate action Commission the controller Long Long Long blink 800ms O...

Page 12: ...VAC specialist installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change...

Reviews: