background image

3/12 

 

 

Service Pin

Connectors

Integrated 

Mounting 

Brackets

Pressure Sensor Inputs (when equipped)

PRESSURE

LOW

HIGH

Integrated 

Mounting 

Bracket

E

D

E

D

 

Figure 5:  

VAV-N & ECL-103 series components 

Mounting Instructions 

 

The following mounting instructions pertain to controllers that 

have a built-in actuator (ECL-VAVS-O,  ECL-VAVS, ECL-

VAV, or ECL-VVTS). If mounting a controller without a built-

in actuator (ECL-VAV-N and ECL-103), simply mount the 

controller using the integrated mounting bracket(s) and 

screw(s) that are provided with the controller. 

 

Each controller is specially designed for easy installation either directly 

on an air duct or in a panel by using the integrated mounting collar and 

the screw that is provided with the controller. This mounting 

arrangement  opposes the torque applied to the damper shaft. Mount 

the controller as follows: 
1.  Orient the controller into position on to the damper shaft so that 

wiring connections are easily accessible. The controller must be 

fitted onto the shaft such that the base of the controller is parallel 

to the VAV box (perpendicular to the damper shaft). If the damper 

shaft has an external bushing that prevents the controller from 

being mounted flush to the side of the VAV box, use a spacer of 

the same thickness to compensate and to ensure the controller is 

at a right-angle to the shaft to prevent binding. 

 

Condensation from the damper shaft will damage the 

controller’s electronics. When the VAV box air supply is 

below 10°C (50°F), ensure that any condensation from the 

damper shaft or from the VAV box does not enter the 

controller’s electronics. Under these conditions, mount the 

controller vertically above the damper shaft so that any 

condensation from the damper shaft will fall away from the 

controller. Further countermeasures may be required in 

some installations. 

2.  Using a power screwdriver, attach the controller to the VAV box 

with the screw provided with the controller through the controller’s 

mounting bracket slider. Otherwise, mark the screw’s position on 

the VAV box with a punch and then drill a hole into the VAV box. 

Then attach the controller to the VAV box with the screw provided 

with the controller. 

 

Avoid over tightening the mounting screw so as to not strip 

the threads. Make sure the screws do not interfere with 

damper blade movement. 

3.  Find the damper position by the marking typically found on the end 

of the damper shaft.  

 

Figure 6:  

Typical Damper Shaft End Marking 

4.  Determine the direction required to close the damper: Clockwise 

(CW) or Counterclockwise (CCW). Turn the damper shaft with a 

pair of pliers to fully close the damper for 90° boxes or fully open 

the damper for 45° or 60° boxes. 

5.  Press and hold down the 

Actuator Clutch for Manual Adjustment

 

button (see Figure 4), and turn the controller’s shaft coupler until it 

touches the mechanical end-stop to either the fully closed position 

(90° boxes) or the fully open position (45° and 60° boxes). 

6.  For 90° VAV boxes: If the damper closes CCW, turn the coupler to 

the CCW mechanical stop limit. If the damper closes CW, turn the 

coupler to the CW mechanical stop limit. The open mechanical 

stop is factory preset for 90° boxes. 

For 45° and 60° VAV boxes: The mechanical stops must be set for 

both the fully closed and fully open damper positions. By installing 

the controller at the fully open position, the controller provides the 

open mechanical stop for 45° and 60° boxes. The closed damper 

seal provides the fully closed stop. 

7.  Tighten the U-Bolt clamp on to the damper shaft using an 8 mm 

(5/16 in.) wrench or socket. Tighten the bolts between 11 and 15 

N·m (100 and 130 lb·in). 

8.  Test for free damper shaft movement: Press and hold down the 

Actuator Clutch For Manual Adjustment

  button and manually turn 

the actuator coupling to be certain that the actuator can rotate from 

full closed to full open positions without binding. 

9.  Connect the VAV box’s flow sensor tubing to the controller’s 

Pressure Sensor Inputs

. Create a condensation  trap in the 

pneumatic tubing by forming it into a vertical loop. 

10. Finalize the installation by rotating the damper to the full open 

position. 

 

CAUTION: Risk of Property Damage.

  Ensure that the 

damper is at the full open position before starting the air 

handler. Failure to rotate the damper to its full-open position 

may result in damage to the Variable Air Volume (VAV) box 

or ductwork when the air handler is started. 

 

 

min. 40 mm (1.5")

 

 

Figure 7:  

Mounting a controller on a damper shaft 

Power Wiring 

Voltage:

 24VAC/DC; ± 15%, Class 2 

 

This is a Class 2 Product. Use a Class 2 transformer only 

(rated at 100VA or less at 24VAC) to power the controller(s).  

 
The  Network Guide  provides extensive information and requirements 

for powering a VAV that uses a L

ON

W

ORKS

  network for 

communications. It can be downloaded from our website. 
When calculating a controller’s power consumption to size the 24VAC 

transformer, you must also add the external loads the controller is 

going to supply, including the power consumption of any connected 

subnet module (for example, for Allure™  Series Communicating 

Sensors). See the room device calculator spreadsheet available for 

download from our website to determine the power requirements for 

the ECL-VAV model: 

VAV-Smart Room Control  Device 

Calculator.xlsm 

It is recommended to wire only one controller per 24VAC transformer. 
If only one 24VAC transformer is available, determine the maximum 

number of daisy-chained VAVs that can be supplied on a single power 

cable supplied by a 100 VA transformer, according to the controller’s 

expected power consumption including external loads, the cable’s wire 

gauge, and the total cable length from the following table. Any 

installation condition that is outside of the parameters of  Table  1 

should be avoided. 

Summary of Contents for ECL-103

Page 1: ...ure during shipping storage to evaporate Upon unpacking the product inspect the contents of the carton for shipping damages Do not install damaged controllers Avoid areas where corroding deteriorating...

Page 2: ...3 wire voltage and current inputs and outputs as well as triac outputs should be kept apart from other types of wiring to avoid any ambient noise transmission to other wires The board connectors accep...

Page 3: ...urn the controller s shaft coupler until it touches the mechanical end stop to either the fully closed position 90 boxes or the fully open position 45 and 60 boxes 6 For 90 VAV boxes If the damper clo...

Page 4: ...wires when daisy chaining devices Use a wire nut with a pig tail to make such a connection Use an external fuse on the 24VAC side secondary side of the transformer as shown in Figure 8 to protect all...

Page 5: ...COM To Analog To Digital Converter Potentiometer 10k 0 to 20mA input used with a 2 wire 0 to 20mA sensor powered by the controller s internal 15VDC power supply Sensor 0 20mA UIx COM 15VDC To Control...

Page 6: ...UOx COM Linear 0 to 10VDC digital to analog output UOx 0 10V Common From Digital To Analog Output UOx COM 0 to 10VDC voltage output controlling an analog actuator that is powered by an external 24VAC...

Page 7: ...network topology and wire length restrictions refer to the Network Guide It can be downloaded from our website It is important to use proper network terminators depending on the type of network topolo...

Page 8: ...evices are not to be thrown away in municipal waste Products must be disposed of at the end of their useful life according to local regulations and the WEEE Directive North American Emissions Complian...

Page 9: ...Heating Floating Actuator LONWORKS Network Back of Allure EC Smart Vue Wireless Port beneath cover E D E D Service PIN Button BAC LON Figure 14 Typical Power and Network Connections with an Allure EC...

Page 10: ...rcuit shows approximately 0V DC and an open circuit shows approximately 5V DC Configuration problem Using EC gfxProgram check the configuration of the input Refer to the controller s user guide for mo...

Page 11: ...eats every 2 seconds highest priority shown first Long blink continuous 1s On 1s Off continuous The controller is unconfigured Appropriate action Commission the controller Long Long Long blink 800ms O...

Page 12: ...VAC specialist installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change...

Reviews: