7.5.2 Electrical installation

1)

The following electrical connections need to be established
on the heat pump.

„

Connection of the control line to the control panel of the heat
pump via terminal X1: L/N/PE.

„

Connection of the mains cable to the control panel of the
heat pump via terminal X5: L/N/PE.

„

Connection of the mains cable of the well pump to the con-
trol panel of the heat pump via terminal X5: L1/N1/PE.

„

Connection of the well pump (to be provided by the cus-
tomer) to the control panel of the heat pump via terminal X1:
PE and pump contactor K5: 14/24.
Ensure that the supply voltage for these terminals cannot be
switched off by the tariff contactor when connecting the
mains cable of the well pump, in order to enable the turn-off
delay of the well pump. 
All electrical components required for the operation of the
heat pump are located on the control panel. 
An disconnecting device with a contact gap of at least 3 mm
(e.g. utility blocking contactor or power contactor) as well as
a 1-pole circuit breaker have to be provided by the customer.
The required conductor cross-section is to be selected ac-
cording to the power consumption of the heat pump, the
technical connection requirements of the respective utility
company as well as all applicable regulations. Details on the
power consumption of the heat pump are listed on both the
product information sheet and the type plate. 

2)

The three-core supply cable for the heat pump manager
(heating controller N1) is fed into the heat pump . Connec-
tion of the control line to the control panel of the heat pump
via terminal X1: L/N/PE.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a constant voltage. For this reason, it
should be tapped upstream from the utility blocking contac-
tor or be connected to the household current, as important
protection functions could otherwise be lost during a utility
block.

3)

The utility blocking contactor(K22) with  main contacts  and
an auxiliary contact should be dimensioned according to the
heat pump output and must be supplied by the customer.
The NO contact of the utility blocking contactor is looped
from terminal strip G/24 V AC to connector terminal J5/ID3.

CAUTION! Extra-low voltage!

4)

The contactor (K20) for the immersion heater (E10) of mono
energy systems (HG2) should be dimensioned according to
the radiator output and must be supplied by the customer. It
is controlled (230 V AC) by the heat pump manager via ter-
minals N and N1-J13/NO4.

5)

The contactor (K21) for the flange heater (E9) in the hot
water cylinder should be dimensioned according to the radi-
ator output and must be supplied by the customer. It is con-
trolled (230 V AC) by the heat pump manager via terminals
N and N1-J16/NO 10.

6)

The contactors mentioned above in points 3, 4 and 5 are in-
stalled in the electrical distribution system. The mains cables
for the heating elements should be dimensioned and pro-
tected according to DIN VDE 0100.

7)

All cables must be installed as permanent wiring.

8)

The heat circulating pump (M13) is connected to terminals N
and 

N1-J13/NO 5

.

9)

The 

DHW loading pump

 (M18) is connected to terminals N

and 

N1-J13/NO 6

.

10) The return sensor (R2) is integrated into  heat pumps for in-

door installation. 
The heat pump manager is connected via the following ter-
minals: GND and 

N1-J2/B2

.

11) The external sensor (R1) is connected to terminals GND and

N1-J2/B1

.

12) The hot water sensor (R3) is installed in the hot water cylin-

der and is connected to terminals GND and 

N1-J2/B3

.

8 Commissioning

8.1 General Information

To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorised by the
manufacturer. This may be a condition for extending the guaran-
tee (see Warranty Service).

8.2 Preparation

The following items need to be checked prior to start-up:

„

The heat pump must be fully connected, as described in
Chapter 6.

„

The heat source system and the heating circuit must have
been filled and checked.

„

All valves that could impair proper flow in the well and heat-
ing circuits must be open.

„

The heat pump controller must be adapted to the heating
system in accordance with the controller’s operating instruc-
tions.

8.3 Start-up Procedure

The heat pump is started up via the heat pump controller.

ATTENTION!

The heat pump must be started up in accordance with the installation and
operating instructions of the heat pump controller.

If an overflow valve is fitted to assure the minimum heating water
flow rate, the valve must be set in accordance with the require-
ments of the respective heating system. Incorrect adjustment
can lead to faulty operation and increased energy consumption.
We recommend carrying out the following procedure to correctly
adjust the overflow valve:
Close all of the heating circuits that may also be closed during
operation (depending on the type of heat pump usage) so that
the most unfavourable operating state - with respect to the water
flow rate - is achieved. This normally means the heating circuits
of the rooms on the south and west sides of the building. At least
one heating circuit must remain open (e.g. bathroom).
The overflow valve should be opened far enough to produce the
maximum temperature spread between the heating flow and re-
turn flow listed in the table below for the current heat source tem-
perature. The temperature spread should be measured as close
as possible to the heat pump. The heating element of mono en-
ergy systems should be disconnected during start-up.

Summary of Contents for WI 14ME

Page 1: ...t Pump for Indoor Installation Pompe chaleur eau eau pour installation int rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Installation and...

Page 2: ......

Page 3: ...E 5 6 Aufstellung DE 5 6 1 Allgemeine Hinweise DE 5 6 2 Schallemissionen DE 5 7 Montage DE 6 7 1 Allgemein DE 6 7 2 Heizungsseitiger Anschluss DE 6 7 3 W rmequellenseitiger Anschluss DE 6 7 4 Temperat...

Page 4: ...falls f r die Benutzung durch Laien zur Beheizung von L den B ros und anderen hnlichen Arbeitsum gebungen von landwirtschaftlichen Betrieben und von Hotels Pensionen und hnlichen oder anderen Wohneinr...

Page 5: ...zugef hrte elektrische Antriebs leistung geht nicht verloren sondern wird gr tenteils ebenfalls dem K ltemittel zugef hrt Daraufhin gelangt das K ltemittel in den Verfl ssiger und ber tr gt hier wied...

Page 6: ...m Vor und R cklauf der W rmetauscherleitungen und ein Elektronikmodul erfassen die gemessenen Werte und bertragen ein Signal an den W rmepumpenmanager der ab h ngig von der aktuellen Betriebsart der W...

Page 7: ...ur in nicht feuchten Innenr umen auf einer ebe nen glatten und waagrechten Fl che aufzustellen Dabei sollte der Rahmen rundum dicht am Boden anliegen um eine geeig nete Schallabdichtung zu gew hrleist...

Page 8: ...berstr mventils ist nur bei Fl chenheizungen und einem max Heizwasserdurchsatz von 1 3 m h ratsam Bei Nichtbeachten kann es zu St rungen der Anlage f hren Frostschutz bei frostgef hrdeter Aufstellung...

Page 9: ...evtl auch dem Warmwasserspeicher Dabei wird statt vieler Einzelkomponen ten ein kompaktes System verwendet um die Installation zu ver einfachen Weitere Informationen sind der jeweiligen Montage anwei...

Page 10: ...er Punkte 3 4 5 werden in die Elektroverteilung eingebaut Die Lastleitungen f r die Heizk rper sind entsprechend DIN VDE 0100 auszulegen und abzusichern 7 Alle installierten Leitungen m ssen als dauer...

Page 11: ...uellenseite Im W rmequelleneintritt der W rmepumpe ist ein Schmutzf n ger montiert um den Verdampfer gegen Verunreinigungen zu sch tzen Anfangs sollte das Filtersieb des Schmutzf ngers in relativ kurz...

Page 12: ...22000 3 5 Kaltwasserdurchsatz bei interner Druckdifferenz W rmequelle m h Pa 2 0 6200 3 3 19000 3 6 K ltemittel Gesamt F llgewicht Typ kg R407C 1 7 R407C 1 9 3 7 Schmiermittel Gesamt F llmenge Typ Lit...

Page 13: ...bezogene Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Na...

Page 14: ...D 12 Deutsch 13...

Page 15: ...ansport EN 5 6 Set up EN 5 6 1 General Information EN 5 6 2 Sound Emissions EN 5 7 Installation EN 6 7 1 General Information EN 6 7 2 Heating System Connection EN 6 7 3 Heat Source Connection EN 6 7 4...

Page 16: ...rective It is thus also in tended for use by non professionals for heating shops offices and other similar working environments in agricultural establish ments and in hotels guest houses and similar o...

Page 17: ...not lost in this process Most of it is absorbed by the refrigerant as well Subsequently the refrigerant is passed through the condenser where it transfers its heat energy to the heating water Dependi...

Page 18: ...of the heat exchanger pipes and an electronics module acquire the measured values and transmit a signal to the heat pump manager which depending on the cur rent operating mode of the heat pump heatin...

Page 19: ...only be installed indoors in rooms with low humidity on a level smooth and horizontal surface The entire base of the frame should lie directly on the floor to ensure a good soundproof seal If this is...

Page 20: ...nd a max heating water flow of 1 3 m h System faults may result if this is not observed Antifreeze protection for installation locations prone to frost The antifreeze function of the heat pump manager...

Page 21: ...cylinder A compact system is used to simplify the installation process so that a lot of different components do not have to be installed individually Further information can be found in the relevant i...

Page 22: ...r It is con trolled 230 V AC by the heat pump manager via terminals N and N1 J16 NO 10 6 The contactors mentioned above in points 3 4 and 5 are in stalled in the electrical distribution system The mai...

Page 23: ...t the manufacturer of the chemicals 9 3 Cleaning the Heat Source System A dirt trap is inserted in the heat source inlet of the heat pump to protect the evaporator against the ingress of impurities Wh...

Page 24: ...old water flow rate at an internal pressure differential of heat source m h Pa 2 0 6200 3 3 19000 3 6 Refrigerant total filling weight type kg R407C 1 7 R407C 1 9 3 7 Lubricant total filling weight ty...

Page 25: ...Installation FR 5 6 1 G n ralit s FR 5 6 2 Emissions sonores FR 5 7 Montage FR 6 7 1 Remarques d ordre g n ral FR 6 7 2 Branchement c t installation de chauffage FR 6 7 3 Raccordement c t source de ch...

Page 26: ...on initi es des fins de chauf fage de boutiques bureaux et autres environnements de travail quivalents dans les entreprises agricoles et dans les h tels pensions et autres lieux r sidentiels La pompe...

Page 27: ...contraire galement en grande partie au fluide frigorig ne Le fluide frigorig ne arrive alors dans le condenseur o son tour il transmet l nergie thermique l eau de chauffage Ainsi l eau de chauffage c...

Page 28: ...ique et un module lectronique saisissent les donn es mesur es et transmettent un message au gestionnaire de pompe chaleur qui en fonction du mode ac tuel de la pompe chaleur chauffage eau chaude sanit...

Page 29: ...ur dans des pi ces non humi des sur une surface plane lisse et horizontale Ici le ch ssis de la pompe chaleur doit adh rer au sol sur toute sa circonf rence afin de garantir une isolation acoustique a...

Page 30: ...it tre garanti dans la pompe chaleur Cela peut par ex tre obtenu par l installa tion d un distributeur double sans pression diff rentielle ou d une soupape diff rentielle Vous trouverez des explicatio...

Page 31: ...poser aux rayons directs du soleil quelle que soit la saison C ble de sonde longueur max 40 m section de fils min 0 75 mm diam tre ext rieur du c ble 4 8 mm 7 4 3 Montage des sondes d applique Le mont...

Page 32: ...nchement de la pompe de puits Tous les composants lectriques n cessaires l utilisation de la pompe chaleur se trouvent sur le panneau de com mande Il faut pr voir une d connexion avec au moins 3 mm d...

Page 33: ...service 9 Entretien nettoyage 9 1 Entretien Pour viter des dysfonctionnements dus des d p ts dans les changeurs thermiques de la pompe chaleur il faut veiller ce qu aucune sorte de d p t ne puisse s...

Page 34: ...ne d passe pas une temp rature moyenne annuelle de 13 C Dans ce cas il suffit de respecter les valeurs limites de fer et de mangan se d p t d ocre 10 D faillances recherche de pannes Cette pompe chal...

Page 35: ...e pression interne source de chaleur m h Pa 2 0 6200 3 3 19000 3 6 Fluide frigorig ne poids au remplissage total type kg R407C 1 7 R407C 1 9 3 7 Lubrifiant poids total au remplissage type litres Polyo...

Page 36: ...FR 12 Fran ais 12...

Page 37: ...II 3 4 Legende Legend L gende A VIII 4 Hydraulisches Prinzipschema Hydraulic Plumbing Diagram Sch ma hydraulique A IX 4 1 Monovalente W rmepumpenanlage mit einem Heizkreisen Monovalent heat pump syste...

Page 38: ...HQJHZLQGH RQQHFWLRQV RQ WKH KHDWLQJ VLGH 0 H WHUQDO WKUHDG RQQHFWLRQV RQ WKH KHDW VRXUFH VLGH 0 H WHUQDO WKUHDG DWHU ILOWHU ZLWK H WHUQDO WKUHDG 5DFFRUGV F Wp FKDXIIDJH 0 LOHWDJH H WpULHXU 5DFFRUGV F...

Page 39: ...VVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ HL ZDVVHUGXUFKIOXVV LQ P K HDWLQJ ZDWHU IORZ UDWH LQ P K pELW G HDX GH FKDXIIDJH HQ P K...

Page 40: ...V LQ P K ROG ZDWHU IORZ UDWH LQ P K pELW G HDX IURLGH HQ P K HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRP...

Page 41: ...www dimplex de A V Anhang Appendix Annexes 3 1 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande 1HW 0DLQV 5pVHDX...

Page 42: ...A VI Anhang Appendix Annexes 3 2 3 2 Last Load Charge 3 3 3 UXQGIRV 0 63 0 63...

Page 43: ...HTXLUHG UDFFRUGHU VL QpFHVVDLUH SDU OH FOLHQW 1HW DVW 0DLQV RDG 5pVHDX KDUJH RQWDNW RIIHQ 3 JHVSHUUW RQWDFW RSHQ 3 GLVDEOHG RQWDFW RXYHUW 3 EORTXpH LH XQNWLRQ YRQ LVW ZlKOEDU 7KH IXQFWLRQ RI FDQ EH VH...

Page 44: ...lateur circuit M16 Zusatzumw lzpumpe Auxiliary circulating pump Circulateur suppl mentaire M18 Warmwasserladepumpe Hot water loading pump Pompe de suralimentation d eau chaude M19 Schwimmbadwasserumw...

Page 45: ...raulisches Prinzipschema Hydraulic Plumbing Diagram Sch ma hydraulique 4 1 Monovalente W rmepumpenanlage mit einem Heizkreisen Monovalent heat pump system with one heating circuits Installation monova...

Page 46: ...mpenanlage mit einem Heizkreisen und Warmwasserbereitung Monovalent heat pump system with one heating circuits and domestic hot water preparation Installation monovalente de pompe chaleur avec une cir...

Page 47: ...auch Flexible connection hose Tuyau de raccord flexible R ckschlagklappe Check valve Clapet anti retour Wasser Wasser W rmepumpe Water to water heat pump Pompe chaleur eau eau Reihen Pufferspeicher Bu...

Page 48: ...E Type s EG Richtlinien Niederspannungsrichtlinie 2006 96 EG EMV Richtlinie 2004 108 EG Druckger terichtlinie 97 23 EG EC Directives Low voltage directive 2006 95 EC EMC directive 2004 108 EC Pressure...

Page 49: ...www dimplex de A XIII Anhang Appendix Annexes 5...

Page 50: ...A XIV Anhang Appendix Annexes 5...

Page 51: ...www dimplex de A XV Anhang Appendix Annexes 5...

Page 52: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: